Selection guide
Runtime tag license tiers for an HMI panel PC
Short answer
Buy the engineering license for your own PC; the panel PC needs a WinCC flexible runtime license sized to controller-connected tags in tiers of 128, 512, 1024, 2048 and 4096, plus a separate recipe license for native recipes. An array counts as one tag and an indexed variable as several, but array elements cannot carry the per-element limits recipe setpoints need.
On this page
Order the runtime license in tiers of 128, 512, 1024, 2048 and 4096 controller-connected tags for WinCC flexible 2008 Runtime, plus a separate recipe license when native recipes are used. The count that picks the tier is the number of tags the runtime exchanges with the controller: an array counts as one tag, an indexed variable as several, everything else tag by tag. Put the engineering license on the PC you develop on; the customer's panel PC needs only the runtime. Worked example from this article: a 512-tag project with 60 servo feedback positions consolidated into one array tag lands at 512 - 59 = 453 licensed tags, inside the 512 tier with 59 tags of headroom. The sections below turn that into a counted order.
Two licenses, two machines #
WinCC flexible splits development from runtime, and the licenses split with it. The engineering system and its development license belong on the PC where projects are opened, edited, compiled and downloaded. The machine on the plant floor needs neither: it runs WinCC flexible 2008 Runtime alone, and the runtime manual states plainly that installing Runtime on a standard PC or a panel PC requires a license for unrestricted use. No runtime license, no unrestricted use.
That split settles who licenses what. One development license lives on your engineering PC and serves every project you deliver; each customer machine carries exactly one runtime license sized to its tag count. The box itself is the second decision: a runtime wants a touchscreen computer at the machine, and the hardware class built for the job is industrial panel PCs, panel-mount units that hold the visualization in the cabinet door.
Commissioning is the one case that reaches back to your PC. Small changes on site need the engineering environment, and the supported route is moving the authorization rather than adding a second development seat: how WinCC flexible license authorization transfer to a panel works walks the move. Deliver runtime only, and the development license never leaves your bench.
What counts against the tag total #
The runtime license depends on the number of tags connected to the controller, and two counting rules decide that number. An array counts as one tag. An indexed variable counts as multiple tags. Everything else exchanged with the PLC counts tag by tag.
The gap between those rules is where sizing happens. Sixty servo feedback positions of one data type, held in a single PLC data block and consumed as one array tag, occupy one licensed tag; the same sixty values declared as separate variables occupy sixty. Consolidation is legitimate only where the data really is uniform: sixty identical feedback values qualify, a mixture of setpoints, statuses and text strings does not.
A hardware panel draws the same boundary differently, because its tag ceiling is fixed by the panel model rather than bought in tiers: why a WinCC flexible panel tag limit comes from the panel itself covers that side. On a PC runtime, the tier you license is the ceiling, and the next section is the ladder you pick it from.
The five runtime tag tiers #
The ladder reported for WinCC flexible 2008 Runtime is 128, 512, 1024, 2048 and 4096 controller-connected tags, and the TIA Portal licensing documentation uses a runtime with 128 tags as its example of a license for a PC-based device. The generation is a mature one; WinCC flexible 2008 lifecycle and the Runtime Advanced license sets out where the product stands and what its licenses carry into TIA Portal.
Apply the counting rules, count the result, order the smallest tier at or above it. A count that lands exactly on a tier boundary runs, but the first added screen pushes past it, so a boundary-exact count goes one tier up whenever revisions are planned.
| Runtime tier | Controller-connected tag count it covers |
|---|---|
| 128 | 1 to 128 |
| 512 | 129 to 512 |
| 1024 | 513 to 1024 |
| 2048 | 1025 to 2048 |
| 4096 | 2049 to 4096 |
Who licenses what:
| License | Lives on | Sized by |
|---|---|---|
| Development (engineering) | Your engineering PC | One license for the seat |
| Runtime | Customer panel PC | The tier from the counted total |
| Recipe | Customer panel PC | A separate order code, when native recipes are used |
Sizing the runtime for a 512-tag supervision project #
The inputs, and where each comes from:
- 512 controller-connected tags: the working count from the screen, alarm and trend design of the supervision project; confirm it against the finished tag list before the order goes in.
- 60 servo feedback positions of one data type, held in a single PLC data block: the documented pattern that lets them reach the runtime as one array tag.
- Native recipes for the setpoints: a design decision from the project specification.
- The tier ladder from the table above.
The rule in words: licensed tags equal separately declared controller-connected tags plus one for each array tag, and the order goes to the smallest tier at or above that total.
The arithmetic:
- Declared separately: 60 position tags + 452 other tags = 512 licensed tags (452 = 512 - 60).
- As one array: the 60 positions collapse to 1, a saving of 60 - 1 = 59, so 512 - 59 = 453 licensed tags.
The result: 453 licensed tags, inside the 512 tier with 59 tags of headroom. Declared separately, the same project sits exactly on the 512 boundary with nothing spare.
The decision: order the runtime license from the result plus the recipe license, and keep recipe setpoints out of the array. An array element cannot be given its own minimum and maximum limit checking, and a setpoint needs exactly that; setpoints stay scalar tags, or their limits are enforced in the PLC program, where the check runs no matter what the panel sends. Past the remaining headroom, the next tier is 1024.
Recipes: a separate license and a separate limit rule #
Native recipes ride on their own license with its own order code; no tag tier includes them. A project that stores and transfers recipe records puts that code on the order next to the runtime license.
The runtime manual also documents how recipe values behave: they move between the PLC and the runtime as recipe tags, and immediate transfer of each individually modified value takes settings made in the recipe itself. The recipe configuration, not the license, decides how quickly a changed setpoint reaches the controller.
This is where consolidation stops. Array elements cannot carry the per-element minimum and maximum checking a setpoint needs, so the array trick that pulls a count down must never swallow recipe values. Setpoints stay scalar, or their limits live in the PLC program.
The order list, and what it does not settle #
The list:
- One development license, on your engineering PC.
- One runtime license at the tier from the counted total, on the customer panel PC.
- One recipe license, only when native recipes are used.
- Nothing further on the customer machine; site edits travel over authorization transfer, not a second development seat.
Two points stay open in the material at hand. No documented maximum exists here for the size of an array tag exchanged with the PLC, so the consolidation ceiling is not on record in this article. And nothing in the runtime manual or the licensing notes shows a development license doubling as runtime authorization on the same machine, so plan on two licenses, because two is what the split documents.
The tiers size tags and nothing else: screen, alarm, trend and ODBC logging limits are not part of the tag ladder, and the ladder is not a statement about them.
Verify on the bench before delivery: runtime starts clean under its license, the project tag count matches the tier ordered, recipes read and write, array elements land on the intended PLC data, and the setpoint limits trip where they should. A license sized by a count you ran yourself is one you can defend.
Questions asked
Can a runtime license be upgraded when the project outgrows its tier?
Yes. Siemens documents upgrades of WinCC flexible 2008 runtime licenses in its TIA Portal licensing notes, so a runtime sized at one tier can move up when the controller-connected tag count grows instead of being bought from zero again. It matters at a boundary: a project sitting exactly on its tier limit has nothing spare, while the example project above holds 59 tags of headroom inside the 512 tier.
Do archived or logged tags count toward the runtime license?
The runtime license is sized on tags connected to the controller. Counting rules differ across the WinCC family: for classic WinCC, the installation documentation states that tags for process value archives are counted individually. So a project that archives or logs values on top of exchanging them applies the counting rule of its exact package and version, and the runtime tier is sized on the exchange count, not on stored history.
How do recipe records get updated on the panel after commissioning?
Recipe records change after download, and the supported path needs no engineering tool on the panel side: export the recipe data records from the panel into a CSV file, edit them at a PC, and import the file back. Design for that route early, because it is how recipe data gets corrected on a machine already running.