IMDTouchKnowledge BaseShop main store

Troubleshooting

When Proficy Crashes Downloading to a QuickPanel+

HMI and touchscreens Published 5 min read

Short answer

Run Proficy Machine Edition as administrator first: on V9.5, elevation alone fixed a download that crashed Proficy even though the QuickPanel+ answered ping. The crash is a permissions fault on the engineering PC, not a panel firmware or Runtime Viewer problem, so fix the PC before hunting files for the panel.

On this page
  1. Separate the PC fault from the panel fault
  2. What the target conversion did and did not prove
  3. Run Proficy as administrator, in this order
  4. Make the elevation permanent
  5. Check the SIM level before blaming the panel
  6. The missing Runtime Viewer and the USB dead end
  7. If elevation does not fix the crash
  8. The decision for each symptom
  9. Questions asked

Run Proficy Machine Edition as administrator before you touch the panel, its firmware, or its Runtime Viewer. In the case this article walks through, Proficy V9.5 crashed on every download to a QuickPanel+ IC755CBS12CDB even though the panel answered ping, and elevation alone let the transfer finish. That result puts the fault on the engineering PC, in a permissions problem, not on the panel. A successful ping proves only that the panel's IP stack replies, which is the same gap that explains why an HMI transfer fails in initial start mode despite ping. A PC application crash and a transfer failure are separate investigations, and you work them in that order.

Separate the PC fault from the panel fault #

Proficy closing mid-download is a desktop application crash: the request dies on the PC, possibly before a single byte reaches the panel. A transfer timeout with Proficy still open is a different fault on a different machine. Place the boundary before you change anything.

Symptom Where the fault lives First move
Proficy closes during download Engineering PC: permissions or software level Elevate, then check the SIM
Proficy stays open, transfer times out Transfer path or panel transfer service Destination address and port policy
Transfer completes, application does not start Panel runtime or deployed application Panel diagnostics, runtime from the manufacturer
Application runs, no process data HMI-to-controller communications Controller addressing in the converted project

Record the last status line you see, whether building, connecting, or transferring, because it places the crash inside that chain.

Example addresses, to show what the ping proved: engineering PC 192.168.1.10 with mask 255.255.255.0, panel 192.168.1.50. 192.168.1.10 AND 255.255.255.0 gives 192.168.1.0, and 192.168.1.50 AND 255.255.255.0 gives 192.168.1.0. Both hosts sit on 192.168.1.0/24, so the ping never left the local segment and crossed no router. The reply says the panel's IP stack is alive; it says nothing about the panel's transfer service and nothing about the health of the software on your PC. In this case the ping was green while the PC application died, which is two unrelated systems.

What the target conversion did and did not prove #

Switching the project target from the QuickPanel View ES1221R to the QuickPanel+ completed without errors here, and the upload from the old panel had already succeeded. Both are migration steps, not proof that the converted project runs on the new target. Validate the converted project once the transfer completes, and keep the uploaded application as the fallback copy. For the wider job around it, planning an HMI terminal replacement from an older operator panel lists what else a swap of this kind has to cover.

Run Proficy as administrator, in this order #

  1. Save the project and close Proficy completely.
  2. Right-click the Proficy launcher and choose Run as administrator, with an account your site authorizes for engineering software.
  3. Reopen the saved project and confirm the target is still the QuickPanel+ and the transfer destination is the panel's address.
  4. Run the same download with the machine in a commissioning state, so a changed operator application cannot start motion or a process.
  5. Accept the step only when Proficy reports the transfer complete without closing. Reaching a later progress indicator than before is not a result.

That launch change alone completed this download, and nothing was done to the panel. Windows elevation gives an application access to the protected files, configuration stores, and components it touches while building and deploying a runtime; which specific resource was blocked here stays unknown, but the launch privilege is what changed the outcome.

Make the elevation permanent #

Right-click the Proficy launcher, open Properties, then the Compatibility tab, and check the option to run the program as an administrator; on a shortcut, the Advanced button carries the same setting. Configuring Machine Edition to always launch elevated is the documented workaround for its compatibility faults on Windows 10. The pattern is not Proficy-specific: an administrator elevation fix for another Windows HMI design package documents the same fault class. Where a site locks that setting on shared launchers, elevate per launch from step 2 above.

Check the SIM level before blaming the panel #

For any Proficy download fault, the first documented check is the SIM level: confirm you are on the highest SIM released for your installed version, and apply it if you are below it. Take SIMs only from the manufacturer or its authorized distributors. Keep the evidence straight in your notes: elevation fixed this case, so an update is the next suspect, not the demonstrated fix.

The missing Runtime Viewer and the USB dead end #

No Runtime Viewer was visible on the QuickPanel+, which is what pushed this job toward a USB stick. Resist that substitution. A Proficy download installs a built runtime application on the panel; copying project files onto removable media performs no install and cannot stand in for the transfer.

Decide the viewer question only after a transfer completes. The panel answered ping throughout, and the network stack and the runtime are independent, so the ping never told you whether a viewer was present. If a completed transfer still leaves the panel without a runnable application, the runtime or firmware package comes from the manufacturer's support portal, matched to the exact model, and getting the right firmware file for a legacy HMI panel is the matching discipline to apply before you load anything.

If elevation does not fix the crash #

  • Apply the highest SIM for your version, then retest with nothing else changed.
  • Retry on a second engineering PC; a PC swap is a documented separator for Proficy crash faults.
  • Capture the failure: the last status line, plus the Windows application error entry that names the Proficy process.
  • Take the version, SIM level, target model IC755CBS12CDB, and the crash point to the vendor's support line.

The decision for each symptom #

  • Proficy closes during download and ping is green: elevate first. That alone completed the documented transfer, and the panel needed nothing.
  • Proficy still closes when elevated: SIM, then a second PC, then the support call with the captured evidence.
  • Proficy stays open but the transfer fails: work the destination address and port policy; the panel and its viewer are not the fault.
  • Transfer completes but no application runs and no viewer appears: runtime or firmware from the manufacturer's portal, matched to the model, never a USB file copy.

Questions asked

Where do you confirm the crash is Proficy and not the panel?

Open Event Viewer on the engineering PC and read Windows Logs, then Application: an error entry naming the Proficy process, timestamped at the failed download, confirms the fault sits on the PC. The panel logs nothing for a transfer that never left it. The entry's faulting module also gives the support line something concrete, which shortens the case.

Did converting the target from a QuickPanel View break the download?

No. A target mismatch shows up as validation errors in the project or a transfer the panel rejects, not as a closed application on the PC. In this case the conversion from an ES1221R to IC755CBS12CDB completed without errors and the download still crashed until Proficy ran elevated. Keep the converted target; fix the PC first, then revalidate the project once the transfer completes.

When do you install a Runtime Viewer on a QuickPanel+ by hand?

Only when a transfer that Proficy reports as complete leaves the panel unable to start the application. Before that point the viewer is invisible to the crash, because the download dies on the PC. The package comes from the manufacturer's support portal or an authorized distributor, matched to the exact panel model, so register for portal access at the start of the job rather than during the failure.

Proficy still crashes elevated: which account should it be installed under?

A documented fix for Machine Edition crashes that survive normal elevation is to install the software while logged in as the Windows built-in Administrator account, then keep launching it elevated afterwards. A standard account answering an elevation prompt can still lack rights the installing account had. If reinstalling is not an option that day, run the second-PC test first.

Keep reading

  • Troubleshooting

    Fixing HMIRTM.EXE Runtime Crashes on a Comfort Panel

    The HMIRTM.EXE serious error is the HMI runtime crashing on the panel itself, most often because internal storage filled with accumulated logs. Back up to a USB stick from the panel operating system, delete the logs, and stop the runtime before changing the IP address; the failed ping is a network fault that sits below the project layer.

    HMI and touchscreens

  • Troubleshooting

    Getting the Right Firmware File for a Legacy HMI Panel

    Before you chase a firmware file, decide which of three things the panel actually lacks: a communications fix, an application restore, or an operating-system image. A panel that boots and navigates almost never needs firmware, and the only safe source for the image is the manufacturer or an authorized distributor, matched to the exact nameplate model and revision.

    HMI and touchscreens

  • How-to

    How One Spare HMI Panel Covers Seven Machines

    Yes. Keep one backup archive per machine on a USB stick or memory card, and restore the needed archive to the single spare panel at the panel itself. This works without WinCC flexible only if the backup transfer option was enabled when each project was downloaded; otherwise you need a PC with ProSave, and archives restore only to the same panel model.

    HMI and touchscreens