Troubleshooting
Where an HMI Overview Window Gets Its Pages and Alarms
Short answer
The runtime page menu you want is the Overview Window, not a Screen Navigator object. It is populated from the Picture Tree, generated at OS compile or maintained in WinCC Explorer, ordered in the OS Project Editor, and its alarm counts only appear when each alarm has a group display assignment.

On this page
- You are looking for the Overview Window, not a Screen Navigator
- Choose one source for the Picture Tree
- Set the operator-facing page order in the OS Project Editor
- Why the alarm count beside a page stays empty
- Worked example: one missing page and one missing alarm count in a three-area tree
- Runtime checks and what each mismatch means
- Questions asked
There is no object to search for called a Screen Navigator. The runtime menu that lists your process pages, each with a count of active alarms beside it, is the Overview Window, and its content is built from the Picture Tree. This article covers where that tree comes from, who controls the page order, and why an alarm can be active on a page yet add nothing to the count.
You are looking for the Overview Window, not a Screen Navigator #
Start by confirming the function, because two different requirements hide behind this question:
- If you need a hierarchical menu of process pages with alarm information beside each name, the object is the Overview Window and its data source is the Picture Tree.
- If the requirement is keyboard-only operation of an existing runtime, open the Computer Properties dialog and check the Graphics Runtime tab instead.
Do not confuse the two. Mouseless operation changes how operators call up runtime functions; it creates no page hierarchy and no cumulative alarm indication. Also, the Overview Window is a runtime window like any other: on a station with two screens, where it lands follows the same placement rules described in how one HMI runtime places windows on two monitors.
Choose one source for the Picture Tree #
The Picture Tree that feeds the Overview Window can be created two ways, and you must pick one as the authority:
- Automatic route: generate the pages from SIMATIC Manager, and during OS compile select the Generate Picture Tree checkbox. The tree is then rebuilt from the project structure at each compile.
- Manual route: maintain the tree yourself. In WinCC Explorer, open the Picture Tree editor (the Picture Tree Manager); the editor gives you one window in which to build and arrange the hierarchy.
The decisive rule is that the generation source stays the controlling source. If the tree is generated at OS compile, edits made by hand in the Picture Tree Manager survive only until the next compile. This matters most in PCS 7 projects that use the DBA utility to create the Picture Tree: its output overwrites manual edits made in SIMATIC Picture Tree Manager, so with DBA in use you do not maintain the tree manually at all. Mixing the two routes is the classic cause of a hierarchy that keeps disappearing after compiles.
Dialog layout and checkbox wording differ between PCS 7 releases, so use the configuration manuals installed with your own version and the Help in each dialog rather than a procedure written for a different release.
Set the operator-facing page order in the OS Project Editor #
A page can be in the tree and still appear in the wrong position at runtime. The displayed order is set separately: in WinCC Explorer, double-click the OS Project Editor icon and use its tabs to arrange the pages the way operators should see them. The rule to carry forward is that the Overview Window shows tree membership and OS Project Editor order. A page that operators cannot find is a tree problem; a page in the wrong sequence is an OS Project Editor problem. After changing either, recompile or update the OS with the same route you chose above, then restart runtime.
Why the alarm count beside a page stays empty #
The number beside a page name is cumulative: it is the total of alarms in that tree branch that are both active and configured to participate in the overview. Two conditions must hold for each alarm:
- The alarm must belong to a page or area inside the branch, so it accumulates upward through the tree.
- The alarm must have an alarm group display assignment. Without the group display, the alarm is announced normally but contributes nothing to the count in the Overview Window.
So an empty or low count does not prove the tree is wrong. It points to alarm grouping: check the group display assignment of the alarms that should be counted, and add the association there rather than rebuilding the navigation tree. This is the same separation of display configuration from data configuration you meet elsewhere, for example when an alarm count behaves differently from the trend data behind a chart page, as in the article on the HMI data group registration error.
Worked example: one missing page and one missing alarm count in a three-area tree #
This example is illustrative; the inputs are chosen to show the method, not measured from a specific project.
Inputs. A project has three areas in its hierarchy. Area 2 contains 4 process pictures in the project. Only 3 of them are entered in the Picture Tree under the Area 2 branch. Area 2 has 4 alarms configured in total; 3 of them have an alarm group display assignment, 1 does not. At runtime, 3 alarms are active on Area 2 pages: each of the 3 assigned alarms is active, and the unassigned one is also active.
Rule in words. The Overview Window lists pages that are members of the tree branch, and the count beside the branch is the sum of active alarms in the branch that have a group display assignment.
Arithmetic. Pages displayed under Area 2: 3 of the 4 project pictures are tree members, so 3 pages appear and 1 never will. Alarm count beside Area 2: 1 + 1 + 1 = 3 from the three assigned active alarms; the active but unassigned alarm adds 0. The window shows 3 while 4 alarms are actually active on the branch.
Result and decision. A missing page means a tree membership problem: enter the fourth picture in the Picture Tree under the intended branch and recompile. A count lower than the number of active alarms means at least one alarm lacks its group display assignment: add the assignment to the fourth alarm. In both cases the fix is one configuration object, not a rebuild.
Runtime checks and what each mismatch means #
Compile or update the OS, start runtime, and read the Overview Window against this list:
- Page presence: every required process page appears. A missing page sends you back to the Picture Tree source, whichever route you chose.
- Page order: the runtime sequence matches the OS Project Editor arrangement. A mismatch points to the editor settings or a compile that ran before the change.
- Navigation: selecting each page opens it. A dead entry means the tree entry references a picture that no longer exists under that name.
- Alarm counts: with a known active alarm on a branch, the branch count rises by 1. If it does not, the alarm lacks its group display assignment.
- Hierarchy stability: after the next compile, the tree is unchanged. If manual edits vanish, the generation route you chose is overriding them.
If the goal is to reduce operator dependence on manual page selection altogether, per-page automatic window switching is a separate mechanism, covered in cycling HMI windows automatically with per-page action triggers; it complements the Overview Window but does not replace it.
The decision, per case: no menu at runtime means build or regenerate the Picture Tree; a page missing means add it to the tree; pages in the wrong order means change the OS Project Editor; a count lower than the active alarms means assign an alarm group display to the uncounted alarm; a hierarchy that disappears on compile means one route, not two.
Questions asked
Can I maintain the Picture Tree in WinCC Explorer while also generating it during OS compile?
No. Pick one source and keep it as the authority. If your project uses the DBA utility to create the Picture Tree, the generated result overwrites anything maintained manually in SIMATIC Picture Tree Manager, so manual edits are lost on the next run. Automatic generation and manual maintenance are two separate workflows, not two layers you can mix.
Do the dialogs and checkboxes look the same in every PCS 7 release?
No. The Generate Picture Tree checkbox, the Picture Tree editor layout and the OS Project Editor tabs differ between PCS 7 versions. Use the configuration manuals installed with your own PCS 7 installation and the Help button in each dialog rather than screenshots from another release. The workflows described here exist across releases, but their exact wording does not.
Where is mouseless runtime operation configured?
In WinCC Explorer, open the Computer Properties dialog and use the Graphics Runtime tab. Its Help button describes the available settings. Note that mouseless operation only changes how operators invoke runtime functions from a keyboard or keypad; it does not build the page hierarchy or configure the alarm counts, so it is not a substitute for the Overview Window.
Does adding a picture to the project make it selectable in the Overview Window?
No. A process picture can exist in the project and still never appear in the Overview Window, because the window lists Picture Tree members only. The picture must be entered in the tree under the intended branch. Likewise, an alarm that exists in the project contributes nothing to the branch count until it has an alarm group display assignment.


