Which HMI programming package an 840D sl needs by software version

HMI and touchscreens Published 5 min read

Short answer

The 840D sl's controller software version picks the toolchain. On SW 2.x, the existing 6FC5253-7BX20-6AG0 HMI Programming Package and your HMI Advanced applications carry over with minor adaptations. On SW 4.x the operator interface is Sinumerik Operate, applications must be rewritten with Create MyHMI/3GL (6FC5861-1YC41-1YA0, version 4.5 SP1) in .NET or C++ with Qt, and a different HMI OA option must be activated on the control.

On this page
  1. The two toolchains side by side
  2. Read the software version first
  3. SW 2.x: keep your HMI Programming Package
  4. SW 4.x: Create MyHMI/3GL and a rewrite
  5. The HMI OA option
  6. Worked example: a six-machine shop
  7. The decision
  8. Questions asked

The answer depends on one number: the controller software version on your 840D sl. If the machine runs SW 2.x, your existing 6FC5253-7BX20-6AG0 HMI Programming Package stays valid, HMI Advanced remains the operator interface, and your applications carry over with minor adaptations. If the machine runs SW 4.x, the operator interface is Sinumerik Operate, HMI Advanced applications will not run, and you rewrite them with Create MyHMI/3GL (6FC5861-1YC41-1YA0, version 4.5 SP1) in .NET or in C++ with Qt, with Visual Studio 2008 as the supported programming environment. The HMI OA option you must activate on the control is also different between the two trains.

The two toolchains side by side #

Controller software Operator interface Programming package Application languages Fate of existing HMI Advanced applications
SW 2.x HMI Advanced 6FC5253-7BX20-6AG0 HMI Programming Package Existing HMI Advanced toolchain Run, with minor adaptations
SW 4.x Sinumerik Operate Create MyHMI/3GL, 6FC5861-1YC41-1YA0 .NET or C++ with Qt Must be rewritten

There is no crossover: the HMI Advanced package does not produce anything Operate can load, and Create MyHMI/3GL targets the Operate extension model, not the older runtime. Match the toolchain to the train before you write a line of code.

Read the software version first #

Start at the control and note the software version it reports at power-up, before touching the engineering PC. Two published releases frame the two trains. On the 2.x side, CNC Software Version 2.5 SP3 HF2 was released as an update release, so a machine kept current on that train is still an HMI Advanced machine. On the 4.x side, CNC software SW 4.93 was released for sale and delivery, and any controller on that train is a Sinumerik Operate machine. If the version screen shows 3.x, that is not a standard public train for the 840D sl: confirm the NCU type and its actual software release with the manufacturer's support data before choosing a package.

SW 2.x: keep your HMI Programming Package #

On the 2.x train you reuse the package you already own. Two published delivery releases show how the package version is paired with the HMI software release rather than the CNC number alone: the SINUMERIK HMI Programming Package sl V 2.1 was released for use together with NCU system software running HMI sl Software Release 2.4, and HMI Programming Package 7.6 requires SINUMERIK HMI advanced Software Version 7.6 on the control. The practical rule: when you install or order a programming package for a 2.x machine, check that its release matches the HMI software release shown on that machine, not just the CNC version. Your investment in existing screens and applications survives this train; only minor adaptations are expected when moving them onto 840D sl hardware.

SW 4.x: Create MyHMI/3GL and a rewrite #

From SW 4.x the operator interface is Sinumerik Operate and the OEM extension package is Create MyHMI/3GL, latest published version 4.5 SP1, order code 6FC5861-1YC41-1YA0. It builds HMI extensions and high-level language applications for the control, in .NET or in C++ with Qt. The release notes name Microsoft Visual Studio 2008 on Windows 7 (64-bit) as the supported programming environment for this version, so plan the engineering station around that IDE even on current hardware. Understand the scope honestly: this is a rewrite, not a recompile. HMI Advanced screens do not convert; every customized screen, form and extension is rebuilt against the Operate model. When that rewrite coincides with aging operator hardware, qualify the machine side first, using the checklist for qualifying a SINUMERIK 840D operator PC retrofit before you buy, so the software port and the hardware decision do not collide mid-shutdown.

The HMI OA option #

Whichever train you are on, OEM applications only load if the HMI OA option is activated on the control, and the option you activate differs between HMI Advanced (SW 2.x) and Sinumerik Operate (SW 4.x). Budget this as a commissioning step in its own right: after the port, activate the Operate-side HMI OA option on the control and confirm your extension appears in the running interface before you call the job done.

Worked example: a six-machine shop #

Take a shop with six 840D sl machines and one library of HMI Advanced applications written under the 6FC5253-7BX20-6AG0 package. The version screens report SW 2.5 on four machines and SW 4.93 on two. The split is decided machine by machine:

  • Machines on the 2.x train: 4 machines x 0 rewrites = 4 machines keep the existing applications with minor adaptations under the current package.
  • Machines on the 4.x train: 6 - 4 = 2 machines move to Sinumerik Operate and need Create MyHMI/3GL.

So the purchase is one Create MyHMI/3GL engineering environment (6FC5861-1YC41-1YA0, version 4.5 SP1) with Visual Studio 2008, used to port the shared application library once for the two 4.x machines, while the four 2.x machines stay on the package already owned. Port the application on a bench system before touching a production controller, because flashing a machine from the 2.x train to the 4.x train is a controlled, machine-down change: back up the control first and treat the HMI rewrite as finished only when the ported screens run on that bench system.

The decision #

  • SW 2.x on the version screen: keep the 6FC5253-7BX20-6AG0 HMI Programming Package, match its release to the HMI software release shown on the machine, adapt the existing HMI Advanced applications minimally, and activate the 2.x-side HMI OA option.
  • SW 4.x on the version screen: the operator interface is Sinumerik Operate; get Create MyHMI/3GL version 4.5 SP1 (6FC5861-1YC41-1YA0), develop in .NET or C++ with Qt under Visual Studio 2008, rewrite the applications, and activate the Operate-side HMI OA option.
  • A 3.x version display: confirm the NCU and its real software release with the manufacturer's support data, then apply one of the two lines above.
  • A planned 2.x-to-4.x controller upgrade: treat it as an application rewrite project, port and test on a bench first, and only then flash the production control.

Questions asked

Why does Create MyHMI/3GL 4.5 SP1 still require Visual Studio 2008?

Because the programming environment is fixed by the Operate release the package targets, not by what is current. The published release notes list Microsoft Visual Studio 2008 on Windows 7 (64-bit) as the supported environment for this version. Build the Operate extensions in that validated IDE rather than a newer one, since only that combination is covered by the release.

Can WinCC Flexible 2008 screens be shown in Sinumerik Operate?

No. WinCC Flexible 2008 is a screen development tool for the HMI Advanced side, and Sinumerik Operate does not load HMI Advanced applications. On an SW 4.x controller the customized screens have to be rebuilt as Operate extensions with Create MyHMI/3GL, in .NET or in C++ with Qt.

Does updating to CNC software 4.93 change the programming package?

No. 4.93 sits in the SW 4.x train, so the operator interface stays Sinumerik Operate and the development package stays Create MyHMI/3GL. A delivery release of a new 4.x CNC version does not move you between the two toolchains described in this comparison; only the 2.x to 4.x step does.

Where is Create MyHMI/3GL installed?

On the engineering PC, together with Visual Studio 2008. The package provides the project environment for building HMI extensions and high-level language applications for the control; the release notes name Windows 7 (64-bit) with Visual Studio 2008 as the validated combination. The compiled application then runs on the control's Operate runtime.

What if my 840D sl reports software version 3.x?

SW 3.x is not a standard public release train for the 840D sl, so do not pick a toolchain from that number alone. Confirm the NCU type and its actual software release against the manufacturer's support information first, then apply the same decision: the 2.x train keeps HMI Advanced and its programming package, the 4.x train requires Sinumerik Operate with Create MyHMI/3GL.

Keep reading

  • Comparison

    Which HMI Software Works With Which HMI Panel Hardware

    Match the terminal's exact model and firmware to its engineering tool. PanelView 800 uses Connected Components Workbench, PanelView Plus uses FactoryTalk View Studio for Machine Edition, and PanelView 5000 uses Studio 5000 View Designer. Check PLC driver support separately.

    HMI and touchscreens

  • Troubleshooting

    Why HMI Programming Software Needs a Ping Reply to Download

    The programming software sends an ICMP echo request to the panel and aborts the download when the reply is blocked, even while remote viewing still works. Ask for one scoped firewall rule: the echo request from your authorized source to the panel address, with its stateful reply. Do not disable the firewall or fake the reply.

    HMI and touchscreens

  • Explainer

    Is There One Software That Programs Every HMI Panel

    No single software programs every HMI panel. Each manufacturer ties its panels to its own engineering tool, and one maker can use a different tool per panel family. Identify the panel from its nameplate, confirm the editor against the manufacturer's documentation, and plan on one editor per panel family.

    HMI and touchscreens