Which WinCC Version Links to an S7-200 CPU 224XP

HMI and touchscreens Published 7 min read

Short answer

The installed product name decides the link. WinCC flexible connects through its own S7-200 driver over PPI; the classic WinCC SCADA line has no S7-200 channel and needs SIMATIC PC Access as an OPC server between the runtime and the CPU, with the tags created in PC Access first.

On this page
  1. Which package the trial actually is
  2. The WinCC route runs through PC Access
  3. The WinCC flexible route uses its own driver
  4. Drawing the screens needs no code
  5. Windows XP, the trial and the station
  6. Working the case: a CPU 224XP feeding a WinCC 7.0 trial
  7. The order to build it in
  8. Questions asked

The installed product name decides the whole link. WinCC flexible carries its own S7-200 driver and talks PPI to the CPU 224XP through the same programming cable Micro/WIN uses. WinCC itself, the classic SCADA line, has no S7-200 channel at all: SIMATIC PC Access has to sit between them, speaking PPI to the CPU on one side and OPC Data Access to WinCC on the other. So before a single screen is drawn, open the software information dialog of the installed trial and read the product name; every step below follows from that one word.

Which package the trial actually is #

WinCC and WinCC flexible are separate engineering environments: the editors, drivers and sample projects of one do not load in the other. The name usually settles it, because WinCC flexible says so in its own name while a plain WinCC names the SCADA product. Matching tools to targets in general is covered in which HMI software works with which HMI panel hardware; here the target is fixed, a CPU 224XP, and only the software side is open.

Installed package Route to the CPU 224XP What sits on the PC
WinCC flexible built-in S7-200 driver over PPI WinCC flexible, programming cable
WinCC 6.0 or 7.0 OPC channel to SIMATIC PC Access, which speaks PPI WinCC, PC Access, programming cable
TIA-generation WinCC runtime OPC Data Access client to the same PC Access bridge runtime, PC Access, programming cable

The third row exists because the current WinCC engineering tools never gained an S7-200 driver: the runtime works as an OPC Data Access client, and that client side is the part you configure.

The WinCC route runs through PC Access #

The vendor-documented pairing for the SCADA line puts SIMATIC PC Access between the two, and the whole chain lives on one PC. Build it in this order:

  • Install SIMATIC PC Access on the WinCC PC.
  • In PC Access, add a new PLC, which shows as NewPLC, with the PC/PG interface set to PPI and its port set to the COM or USB port the programming cable occupies.
  • Set the CPU's PPI address from STEP 7 Micro/WIN to the value the NewPLC connection expects; if the old Micro/WIN installer no longer offers the 224XP, getting the right Micro/WIN version for an S7-200 CPU 224 settles which release to run.
  • Create every tag in PC Access first; WinCC binds to those items, it does not create them.
  • In the WinCC Explorer, add the OPC driver in the tag management, point the connection at the PC Access server, and create the WinCC tags on top of its items.
  • Keep PC Access and WinCC on the same PC, so the OPC exchange stays local and DCOM configuration never enters the job.

The S7-300 and S7-400 side of the same WinCC connects over networks configured in STEP 7 instead; that different setup is covered in configuring WinCC 7.0 PLC connections with STEP 7. Any OPC server with an S7-200 serial driver, and third-party ones cover PPI and PPM, can stand in for PC Access; the WinCC side does not change.

The WinCC flexible route uses its own driver #

WinCC flexible needs no middleman: its driver list includes an S7-200 driver, the connection is PPI over the same programming cable, and each tag maps straight to a PLC address, one configuration layer instead of two. For a first project, Siemens lists a sample built for exactly this pairing, a WinCC flexible application with its STEP 7 Micro/WIN program, under support entry 22354065; walking that project teaches more than any checklist. If you ever want flexible as an OPC client instead, with one PC Access server feeding several stations, the project tree does it: double-click Communication > Connections, create a new connection and select OPC as the communications driver.

Drawing the screens needs no code #

Screens are drawn, not programmed. Objects such as indicators, numeric fields and buttons are placed in the graphics editor and their properties are bound to tags; no code is needed for a connected screen, and scripts appear only when a behavior exceeds the built-in functions. Build the first screen small, on four values:

  • a status indicator on a read-only PLC bit;
  • a numeric field carrying the address, data type and scaling of a known value;
  • a momentary command writing a dedicated PLC variable, never a physical output;
  • a setpoint entry with its permitted range.

Give unavailable data a visible difference from a live zero, through a quality-dependent color or text, because static artwork looks correct even with the link dead. Wire this first screen on the bench with the machine's outputs disabled: an HMI button is an operator aid, not a safety function, and the setpoint field writes straight into the program.

Windows XP, the trial and the station #

Windows XP carries the project for the software generations this CPU was sold with: WinCC flexible and the 6.0/7.0 SCADA line were released for that system, and the installer is the arbiter, because a package whose setup refuses XP is a newer generation and belongs on a newer Windows. The link itself does not change with the OS; PPI, PC Access and the OPC channel behave the same wherever they run. Read the trial's terms before judging anything on it, and confirm they permit runtime, not just engineering, for the length of the test. The only extra bench hardware is the programming cable, USB or serial, from the PC to the CPU's RS-485 port. When the trial graduates to the machine, the station becomes hardware you choose, and an industrial panel PC puts the screen, the touch surface and the runtime computer in one sealed unit at the machine.

Working the case: a CPU 224XP feeding a WinCC 7.0 trial #

The inputs, each with its source:

  • One S7-200 CPU 224XP, its PPI address and port configured from Micro/WIN: your own controller.
  • A WinCC 7.0 trial on the Windows XP PC you already have: the pairing the vendor documents for this OPC route.
  • The link: the programming cable from a COM or USB port to the CPU's RS-485 port.
  • A first screen of four values: the status bit, the numeric field, the momentary command and the setpoint from the drawing section.

The rule: on the WinCC path every value is configured twice, once as a PC Access item and once as a WinCC tag bound to that item, and each layer carries one connection object. On the flexible path each value is a single tag, with one connection shared by all of them.

The arithmetic for that same screen:

  • WinCC path: 4 values × 2 entries = 8 named entries, plus 1 NewPLC connection and 1 WinCC OPC connection = 10 objects.
  • Flexible path: 4 values × 1 tag = 4, plus 1 connection = 5 objects.
  • Difference: 10 - 5 = 5 extra objects, one more name per value and one more connection, and every value also crosses one extra protocol hop, the OPC Data Access exchange between PC Access and WinCC.

The result: the identical first screen costs 10 configured objects on the SCADA route and 5 on the flexible route.

The decision: commit by the installed name before creating anything. If it is the SCADA line, accept the double pass and build the PC Access items before a single WinCC tag, because a WinCC tag with no item behind it shows bad quality from the first second. Diagnose by pattern: one bad value among good ones is a name mismatch between the layers; all values bad with the OPC connection up is the PPI side, so check the cable and the CPU's PPI address first. If the name is WinCC flexible, skip PC Access entirely and the screen is the 5-object build.

The order to build it in #

  1. Read the installed product name in the software information dialog; everything branches there.
  2. Set the CPU's PPI address from Micro/WIN and download, before opening either package.
  3. Flexible branch: new project, one connection on the S7-200 driver with the matching PPI address, tags, then the first screen.
  4. SCADA branch: install PC Access, add the NewPLC connection on the PPI PC/PG interface and the cable's port, create the items, then the WinCC OPC driver, its connection and the tags.
  5. Prove it on the bench with the outputs disabled: one read-only tag live first, then one write to a dedicated variable.
  6. Confirm the trial's runtime terms, then license the station for production and choose the machine station when the trial graduates.

Questions asked

Can Micro/WIN stay online while the HMI link is polling?

Not on the same serial port: a COM port serves one application at a time, so on a single link you download, then close the Micro/WIN connection and let PC Access own the port. The CPU 224XP has two RS-485 ports, so the cleaner split is Micro/WIN on one port and the HMI link on the other, and both stay live.

Can one PC Access server feed several clients?

Yes. PC Access is an OPC Data Access server, and OPC DA is built for multiple clients, so the WinCC station and any other OPC DA client can read the same items at once. Keep the clients on the server's own PC where you can; a client on a different PC also needs DCOM to permit the connection, and the usual symptom of a blocked DCOM setup is a client that browses the server but reads nothing.

Does an S7-200 SMART follow the same steps?

Not one for one. The SMART line is a separate controller family, and its documented route to WinCC also runs through a PC Access OPC server, but its connections and addressing are its own. Build that link from the SMART documentation rather than reusing the serial settings of the CPU 224XP.

What does the production system need beyond the trial?

Two licenses and the manuals: the WinCC runtime license for the station PC and the SIMATIC PC Access license for the OPC server, both through the vendor or an authorized distributor. The trial only proves the engineering steps, so confirm its terms permit runtime at all before you judge the link on it.

Keep reading

  • How-to

    How to Simulate a PLC Behind WinCC Flexible 2008 SP3

    WinCC Flexible 2008 SP3 simulation runs your screens on the engineering PC and executes no PLC program, so give every animated object a real data source: STEP 7 with PLCSIM for an S7-300 test, PC Access or KepServerEx OPC for an S7-200, or a PC Adapter USB cable to the physical controller. Then wire M0.0 in parallel with I0.0, M0.1 in series as the stop, and animate the motor symbol on Q0.0, not on the command bit.

    HMI and touchscreens

  • How-to

    Connecting an Omron CV1000 PLC to WinCC over an OPC server

    Classic WinCC has no Omron CV-series channel, so the working route is an OPC server that speaks Host Link to the CV1000 and OPC DA to WinCC. Configure the server against the PLC first, prove one read, then build WinCC tags from the server's item addresses. Use the documented CV1000-CPU01-EV1 Host Link reference values: ASCII, 7 data bits, even parity, 2 stop bits, unit 00, 9600 or 19200 bps.