Troubleshooting
Why a C-more Numeric Entry Handshake Times Out With a Valid Write
Short answer
When the destination tag writes correctly and the acknowledge bit is verifiably true, the handshake timeout comes from the panel's handshake state machine, not from communication or PLC logic. C-more software v8.24 release notes list a fix for handshake not working on Numeric Entry objects, so a v8.23 project must be updated, recompiled and re-downloaded; otherwise replace the built-in handshake with a staging-tag write and your own request/acknowledge logic.
On this page
- How handshake control on a numeric entry works
- Where the failure is, by what you observe
- Example: why a longer timeout delays the same error by 4 seconds
- The documented fix: software version and re-download
- When the v8.24 upgrade is blocked by a .NET Framework error
- The fallback: replace the built-in handshake with your own logic
- Decision
- Questions asked
A numeric entry handshake timeout with a confirmed good write is not a communication fault and no timeout value will fix it: the panel is failing to evaluate the acknowledge, not waiting too short a time. The v8.24 C-more programming software release notes list a fix for handshake not working on Numeric Entry objects, so a CM5 panel running a project downloaded from v8.23 sits on the defective side of that fix. Update, recompile and re-download — or drop the built-in handshake and run a staging-tag write with your own request/acknowledge logic in the PLC. This article gives you the sequence the panel expects, the test that isolates the failure, and the workaround for the case where the v8.24 upgrade itself is blocked.
How handshake control on a numeric entry works #
Handshake control adds a closed-loop confirmation to what is otherwise a fire-and-forget write. The panel expects this sequence:
- The operator commits a value on the keypad popup.
- The panel writes the value to the configured destination tag.
- The panel asserts the configured request element.
- The PLC logic detects the request, consumes the value, and drives the acknowledge element back.
- The panel reads the acknowledge, clears the request, and releases the entry object.
- If the acknowledge is not observed within the configured timeout window, the panel aborts and posts a handshake timeout.
Any failure in steps 4 through 6 shows the same on-screen error, so the whole troubleshooting job is to prove which step actually broke.
Where the failure is, by what you observe #
- Destination tag never changes — addressing, driver or communication fault, not a handshake defect. That path is covered in the serial timeout article.
- Request element never asserted — the PLC never sees the trigger; check the object's handshake tag mapping.
- Acknowledge never asserted — the acknowledge bit stays low in PLC data; a logic issue such as a missing edge detection or a scan-order problem.
- Acknowledge asserted and confirmed, timeout still raised — the panel-side handshake handling is defective. This is the reported case.
- Acknowledge pulses for one scan only — the panel may read the element between polls and miss the transition. Drive the acknowledge as a level held until the request clears.
The fourth row is the decision point. Once you have watched the destination tag take the entered value and seen the acknowledge bit true — with a data trace or a trend, not just the HMI — the network path and the PLC program are proven good and the fault is inside the panel's handshake state machine.
Example: why a longer timeout delays the same error by 4 seconds #
The timeout parameter only sets how long the panel waits before raising the error; it does not change whether the panel reads the acknowledge. Take the reported case: the write completes at t = 0, the PLC sets the acknowledge two scans later at t = 20 ms with a 10 ms scan time, and the panel polls the element on a 200 ms communication cycle. With the handshake state machine on the defective side of the v8.24 fix, the panel never reads that acknowledge at all.
- Timeout configured to 1 s: error appears at t = 1,000 ms.
- Timeout configured to 5 s: error appears at t = 5,000 ms.
Raising the timeout from 1 s to 5 s moves the error 4,000 ms later and changes nothing else. That measured behavior — same failure at both settings — is itself the diagnostic: the panel is not missing a slow acknowledge, it is failing to look at it.
The documented fix: software version and re-download #
The release notes for C-more programming software v8.24 list the fix for handshake handling on Numeric Entry objects. Getting it onto the panel takes three steps, because the panel runs the compiled project, not the PC software:
- Record the exact programming software version and the panel firmware revision from the panel's system setup screens.
- Update the panel firmware to the revision matching the software version you standardize on.
- Recompile the project under that version and re-download it. A project last downloaded from v8.23 does not inherit the v8.24 fix because v8.24 is later installed on the PC.
One qualifier from the field: the fix does not close every instance. At least one CM5 installation running v8.24 continues to see numeric entry handshake timeouts, so if the error survives the upgrade, move to the PLC-side handshake below instead of tuning the object further.
When the v8.24 upgrade is blocked by a .NET Framework error #
A repeatable .NET Framework error when running the v8.24 programming software is a workstation fault, independent of the panel, and a legitimate reason a project stays on v8.23. Work it as its own problem: uninstall the software completely, reboot, and reinstall as administrator with antivirus temporarily disabled; repair the Windows .NET Framework components through Windows Features or Microsoft's repair tool; and test one install on a clean machine or virtual machine to determine whether the fault is environmental or genuinely a software defect. Keep the exact exception text, the Windows build and the software version in one support ticket together with the handshake timeout report, so support sees the version pairing.
The fallback: replace the built-in handshake with your own logic #
Where production cannot wait for a software fix, remove the dependence on the defective object feature entirely:
- Disable handshake control on the numeric entry object and point it at a dedicated staging register, not at the live setpoint.
- Add a separate momentary pushbutton object on the same screen that sets a request bit.
- In the PLC, on the rising edge of the request bit, copy the staging register to the live setpoint, apply range and validity checks, then set an accepted bit and clear the request bit.
- Display the accepted bit and the live setpoint on the screen so the operator gets explicit confirmation instead of relying on the panel's internal state machine.
This pattern is more diagnosable than the built-in handshake: every state is a PLC tag you can trend, force and log, and the write path is the same one covered when you separate PLC scan behavior from communication faults.
Decision #
- Destination tag writes correctly and the acknowledge bit is confirmed true with a trace: the fault is the panel's handshake state machine. Update to v8.24, update the matching firmware, recompile and re-download. If the error survives that, or the upgrade is blocked, disable handshake control and run the staging-tag write with your own request/acknowledge logic.
- Destination tag does not update: stop here — it is a communication or addressing fault, not a handshake defect, and no timeout setting applies.
- Acknowledge pulses for one scan: hold it as a level until the request clears and retest before concluding anything about the panel.
Questions asked
Why does increasing the handshake timeout value change nothing on my numeric entry object?
The timeout parameter only sets how long the panel waits before it raises the error. If the panel's handshake state machine never reads the acknowledge element, extending the window from one second to five seconds only delays the same message by four seconds. A timeout that survives a confirmed acknowledge points at the object's handshake handling, which the v8.24 release notes document as fixed, not at a speed problem.
Do I need to re-download the project after upgrading the C-more software to get the handshake fix?
Yes. A panel runs the compiled project, not the PC software. If the project was last compiled and downloaded under v8.23, installing v8.24 on the workstation changes nothing on the panel. Recompile with the new version, update the panel firmware to the matching revision, and re-download before you retest the handshake.
v8.24 throws a .NET Framework error on my PC, so I stayed on v8.23. What are my options?
Treat the .NET Framework error as a separate workstation fault. Meanwhile, the staging-tag pattern in this article removes the dependence on the handshake feature entirely.
Is a one-scan acknowledge pulse long enough for the panel to see it?
It can be missed. The panel reads the acknowledge element on its communication scan, so a pulse shorter than the panel's poll interval can complete and clear between reads. Drive the acknowledge as a level that stays set until the request bit is cleared, and confirm it with a data trace before you blame the panel.