IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a Comfort Panel script cannot restart a USB port

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

Comfort Panel scripts have no documented function to disable and re-enable a USB port, so a script cannot restart the RFID reader connection. Sort each drop-out into one of two logged failure states, recover it by USB reconnection or a panel power cycle, and escalate to Siemens support with the Option+ and TIA Portal versions.

On this page
  1. What the Comfort Panel runtime lets a script reach
  2. The two failure states and how each one recovers
  3. Sorting a 10-day log with 24 drop-outs and 2 dead-LED events
  4. What goes into the Siemens service request
  5. The decision at each failure
  6. Questions asked

A Comfort Panel script cannot restart a USB port. The runtime on these panels exposes no documented scripting function that cuts USB port power or forces a connected device to re-enumerate, so no script command can reproduce what pulling and reinserting the USB cable does. The drop-outs with a Siemens USB RFID reader behind PM-LOGON Basic are an integration fault between the reader, the login software and Option+ — not a missing script function. Sort every drop-out into one of two logged failure states, recover each one the way it has already been shown to recover, and put the log in front of Siemens support with the Option+ and TIA Portal versions in hand.

What the Comfort Panel runtime lets a script reach #

Comfort Panel scripts work with tags, screens and the documented set of system functions. None of that set includes a call that switches power on a USB port or detaches and re-attaches a connected device. Loading a project over the panel's USB interface is a documented transfer path, but transfer support is not power control: nothing in that path gives a script a way to turn the port off and back on.

A USB lock, which is documented as a security feature, blocks unauthorized devices from connecting through the port. It does not cycle power and it will not change how often a hung reader needs intervention, so it does not answer the recovery question. Because no supported command exists, treat any proposed script snippet that claims one as unverified until the documentation for your exact Option+ and TIA Portal versions says otherwise.

The two failure states and how each one recovers #

The observed behavior falls into two states, and each one has a recovery that has already proven itself across several installations:

  • Reader stops reading, LED still lit. Disconnect the USB cable, wait a few seconds, reconnect it. Confirm recovery by completing one RFID login through PM-LOGON Basic before handing the station back to production.
  • Reader LED off, and reconnection does not revive it. Power the panel off and back on. After startup, check the reader indication and complete an RFID read through the configured login workflow.
  • Either state: write it down. Record the date, the LED state and which recovery cleared it. The log is what turns repeatable behavior into evidence.

The LED-off case matters because a device that only returns when the whole panel restarts is a known failure pattern. The same shape appears where an HMI Ethernet port stays locked until someone cycles power, and where drive rack output drop-outs recover only after a full rack power cycle. It is the one state the reader cannot clear through its own cable connection, and it is the detail support asks about first.

Sorting a 10-day log with 24 drop-outs and 2 dead-LED events #

The inputs, from an example log sized to match the reported rate of two or three drop-outs a day: a window of 10 operating days on a single-shift line; 24 events where the reader stopped reading with its LED lit and a cable reconnection cleared it; 2 events where the LED was dark and only a panel power cycle restored reading.

The rule: classify every event by LED state and by the recovery that cleared it, count each class over the window, and divide by the window length to compare against the reported rate.

The arithmetic: 24 cable-reconnect drop-outs ÷ 10 operating days = 2.4 drop-outs per operating day. 2 LED-off events ÷ 10 operating days = 0.2 events per operating day, which is one dead-LED event every five operating days. Total event load: 24 + 2 = 26 events, and 26 ÷ 10 = 2.6 events per operating day.

The result: 2.4 sits inside the reported band of two or three a day, and the LED-off class is real but rare. The decision it leads to: the cable-reconnect class alone already justifies the service request, because two or three drop-outs a day across several installations is an integration fault, not normal wear. The first LED-off event that a cable reconnection does not clear is the escalation trigger — do not wait for the 10-day window to close.

What goes into the Siemens service request #

Because the reader is a Siemens device used with Option+, the escalation path is a service request, and it should carry:

  • The panel model (TP900 in the reported cases)
  • Option+ version 3.2.4
  • The TIA Portal version of each affected installation, which ranged from V16 through V18
  • The drop-out frequency from your log
  • The reader LED state at each failure
  • Which recovery cleared each one: cable reconnection or full panel restart

Ask two questions explicitly: whether this reader is covered by the Option+ documentation, and whether a supported USB-interface recovery mechanism exists for Comfort Panels. Siemens documents which RFID readers work with PM-LOGON — its own RF1040R, RF1060R and RF1070R plus readers from other manufacturers — so a coverage check against that list belongs in the same request.

The login configuration itself is a separate matter: the RFID card login setup on a Comfort Panel with PM-LOGON Basic covers that side, and a recurring drop-out is not a configuration error to be fixed there.

The decision at each failure #

  • LED lit, reader dead: reseat the cable, verify one RFID login, log the event.
  • LED dark, or the cable swap fails: power cycle the panel, verify the login workflow, log the event, and treat the first occurrence as your escalation trigger.
  • Rate of two or more a day on more than one installation: open the service request now, with the log attached.
  • Looking for the script command: stop — none is documented to exist, and deploying an unverified one risks the login path the station depends on.

One coordination note: a power cycle takes the RFID login down with the panel, so time the restart with production rather than letting a locked-out operator improvise around a station that should be idle.


When the reader keeps failing after Siemens has ruled on the reader coverage and no supported recovery exists, the durable fix is at the hardware layer: replacing the reader, its cable run or the panel it hangs off, and an integration like that is where industrial panel PCs and touchscreen computers earn their place, because the USB, power and mounting details are specified as one assembly instead of being improvised in the field.

Questions asked

Can a Comfort Panel script disable and re-enable a USB port?

No. The Comfort Panel runtime exposes no documented scripting function that switches USB port power or forces a connected device to re-enumerate, so nothing in a screen script can reproduce pulling the cable or cycling panel power. Verify any proposed command against the Siemens documentation for your exact Option+ and TIA Portal versions before you rely on it.

Does a USB lock stop the reader drop-outs?

No. A USB lock is a security feature that blocks unauthorized devices from connecting; it does not control port power and it does not recover a hung reader. It addresses device policy, so installing one will not change how often the reader needs a cable reconnection or how often the panel needs a restart.

What should the service request to Siemens include?

The panel model, the Option+ version (3.2.4 in the reported cases), the exact TIA Portal version for each affected installation, the drop-out frequency from your log, the reader LED state at each failure, and whether a USB reconnection or a full panel power cycle restored operation. Ask explicitly whether the reader is covered by the Option+ documentation and whether a supported recovery mechanism exists.

Why does a dark reader LED need a full panel power cycle?

In the reported state, unplugging and reconnecting the USB cable no longer revived the reader; only powering the panel off and on did. That pattern points to a fault the reader cannot clear through its own cable connection, which is exactly the detail support needs, so record the LED state at every drop-out.

Keep reading

  • How-to

    Sharing One USB Host Port With a Powered Hub on an HMI

    Yes: a four-port USB hub on the CMT-FHDX-820's single host port carries the touchscreen interface and the 32 GB DataLog stick together. Use an independently powered hub — two devices budgeted at 500 mA each draw 5.0 W, more than the 4.5 W a bus-powered hub shares — then commission touch and logging one at a time through the hub before accepting the shared link.

    HMI and touchscreens

  • How-to

    Run and Stop a SIMOTION CPU from a Comfort Panel HMI

    Write the device system variable modeOfOperation from the Comfort Panel connection: 0 puts the SIMOTION CPU in STOP and 3 puts it in RUN. Find it in SCOUT's Symbol Browser under the selected CPU, bind it as a tag, and drive two separate momentary buttons.

    HMI and touchscreens

  • Troubleshooting

    Why a TP900 Comfort boots to a black screen

    Measure the 24 V DC input at the TP900 Comfort terminals under load first. Correct voltage plus ProSave or TIA Portal communication means you can attempt the documented OS update or factory reset; correct voltage with no communication means a service evaluation, while TIA Portal simulation with the PG/PC interface set to the PC's TCP/IP card keeps the operator screens running meanwhile.

    HMI and touchscreens

Why a USB HMI transfer cable cannot be hand built