Explainer
Why a Comfort Panel trend axis shows points instead of time
Short answer
A Comfort Panel trend plots point indices instead of clock time when its axis mode is Points >> F(x). Switch the trend view's axis mode to Time >> F(t) and the horizontal axis becomes time. WinCC RT cannot be installed on a Comfort Panel, so the fix is a setting, not a runtime change.
On this page
A Comfort Panel trend plots sample numbers instead of clock time because its axis mode is set to Points >> F(x), not because the panel lacks a time trend. The panel's Trend View has two axis modes, Time >> F(t) and Points >> F(x); select Time >> F(t) and the horizontal axis becomes time. WinCC RT cannot be installed on a Comfort Panel, so no runtime swap, copied icon or extra library will fix this: the fix is one setting in the trend view's properties.
The two axis modes and what each one draws #
The Comfort Panel Trend View offers exactly two axis modes:
- Time >> F(t): the value is plotted as a function of time. The x-axis carries timestamps or an elapsed-time window, and the trend advances as the panel clock moves.
- Points >> F(x): the value is plotted against whatever you supply as the horizontal coordinate, another tag or a constant series. With nothing driving the x position, the plot falls back to sample indices, which is exactly the "points instead of time" look.
F(x) exists for curves whose x-axis genuinely is not time, such as a pump curve or a position-to-pressure profile. If your screen was built around an F(x) trend and you then wanted it to behave like a normal historical trend, the mode, not the object, is the problem. Set the axis mode to Time >> F(t) and the same control plots against the panel clock.
Where the setting lives #
Open the Trend View on the screen, then in the Inspector window go to Properties > Properties > Time axis. Under Settings you will find the axis mode; change it from Tag/constant to Time. On the same page you add time-axis configurations with Add, which is where you set the visible window, so the same properties page covers both the mode and the range. The names above are from the current TIA Portal documentation for panels and RT Professional; older engineering versions group the same settings under the trend view's time-axis properties with the same Time versus value-axis distinction.
This setting belongs to the panel's Trend View object. It has no connection to the PC-runtime object named "F(t) Trend" that you may have seen in WinCC RT projects; the similar names describe the same math, not a shared object.
Why WinCC RT is not the answer on the panel #
WinCC RT runs on a PC. A Comfort Panel runs Siemens panel firmware with its own runtime, and there is no supported way to install WinCC RT on it. That applies equally to the two workarounds that come up every time this question is asked:
- Copying screen objects or icons from an RT project into a Comfort Panel project does not transfer RT object behavior. A graphic may import; the runtime code behind an RT-only object does not.
- Adding extra libraries to the panel project does not extend the panel runtime. Libraries carry graphics and templates, not runtime capabilities the firmware does not have.
So if the requirement is truly the RT F(t) trend object with all of its PC behavior, the decision is a target change, not a panel hack. Run the application on a PC at the machine, which is what industrial panel PCs are for when HMI runtime software needs a touchscreen computer instead of a proprietary terminal. For a plain time-based trend, none of this is needed: the panel's own Time >> F(t) mode covers it.
Example: how many points a 120 s window shows at a 2 s sample time #
Say the tag is logged every 2 s and the Time >> F(t) axis is configured for a 120 s visible window. Each sample occupies 2 s of that window, so the number of plotted points is:
120 s / 2 s per sample = 60 points on screen
The axis resolution follows the same two figures. With 60 points spread over the full window, the smallest change the plot can represent is:
120 s / 60 points = 2 s per point
So at that sample rate there is no benefit to shrinking the window below 60 points' worth of time: every sample is already drawn, and each drawn point moves the line by 2 s. Halve the sample time to 1 s and the same window carries 120 s / 1 s = 120 points, doubling both the plot density and the panel memory the trend consumes. Choose the sample time from the fastest process change you need to see, then read the point count off the window size the way the arithmetic above does.
Verifying it on the running panel #
The editor setting is only half the check; the other half is the loaded project.
- Set the axis mode to Time >> F(t) and configure the time-axis window.
- Compile and download to the panel through the normal transfer workflow.
- Open the screen and run the process. Confirm the x-axis shows time values that advance as samples arrive.
- If index numbers appear instead, the active configuration is still on the F(x) setting; return to the time-axis properties and repeat.
If trend data stays empty after the axis reads time, the axis mode was only one of the problems; the logging and tag configuration are the next suspects, and the checks for a missing trend trace on an HMI trend that shows no curves apply there. Keep the two faults separate: an empty plot is a data problem, an index-labeled plot is an axis-mode problem.
The decision #
- You want time on the x-axis of a panel trend: set the Trend View axis mode to Time >> F(t), configure the window, download, verify the advancing timestamps. Done with one setting.
- You are drawing a curve whose x-axis is a process value, not time: stay on Points >> F(x) and supply the x tag.
- You need an RT-only trend feature, not just a time axis: move the application to a PC runtime target; it will not run on the panel, and no icon or library import changes that.
Questions asked
Can WinCC RT run on a Comfort Panel?
No. WinCC RT is a PC runtime and the Comfort Panel runs its own panel firmware and runtime; there is no supported way to install WinCC RT on the panel, and copying RT screen objects or libraries into the panel project does not add RT features. If a trend behavior exists only in WinCC RT, run that project on an industrial PC, or configure the panel's own Trend View with the Time >> F(t) axis mode.
Why does my Comfort Panel trend show points on the x-axis?
The trend view is set to the Points >> F(x) axis mode, which plots each sample against its position in the record rather than against a timestamp. Open the trend view's Properties, go to the Time axis settings, and change the axis mode from Tag/constant (the F(x) behavior) to Time. After a recompile and download, the horizontal axis shows time values that advance with the data.
What does the F(x) trend mode on a Comfort Panel do?
Points >> F(x) plots the tag value against whatever you supply for the horizontal position: another tag or a constant series. It is meant for curves like a pump characteristic or a ramp profile, where the x-axis is not time. With no x-value supplied, the plot defaults to sample indices, which is why an F(x) trend used as a normal trend looks like it has no time axis.
How do I verify the panel trend is time-based before release?
Compile and download to the panel, open the screen with the trend view, and watch the horizontal axis while the machine runs. A time-based trend shows timestamps or elapsed time on the x-axis that advance as new samples arrive. If you see plain index numbers instead, the axis mode is still on the F(x) setting; return to the trend view's Time axis properties and set it back to Time.