Why a Dark Mark Stays Fixed on an HMI Screen
Short answer
Stop the HMI runtime and look at the same spot on the operating system desktop. A mark that stays at one physical location outside the application is a display or mounting fault: ease the frame clamping as a test, and if the mark survives, book display repair or replacement. A mark that shows up only on one application screen is content, and you fix it in the project.
On this page
Stop the HMI runtime before you touch anything else. If the dark mark is still on the operating system desktop, in the same physical spot and the same shape, the application is not the cause: the fault sits in the display hardware or in the way the mounting frame loads it, and no project edit, firmware update or screen redesign will remove it. If the mark disappears the moment the runtime stops, it is drawn content, and you fix it in the project. The case this article works through is a Comfort panel that served a heat-treatment furnace line for three years and then showed a fixed dark patch; the same test sequence settles the content-versus-hardware question on any HMI that runs an application on top of a full operating system.
Stop the runtime first: content or hardware #
Runtime is the software process that executes the HMI application and draws every object you see. A dark rectangle drawn by the application can look exactly like a damaged screen area, so the first job is to establish which of the two you have.
Open two or three existing application screens with deliberately different backgrounds, for example a dark trend view and a white alarm list, and watch the mark. Then stop the runtime by the route the device manual documents; on a Comfort-class panel this leaves you on the Windows CE desktop. Compare the mark's position, shape and size against the photographs you took before changing anything.
If the values on screen are wrong rather than the picture itself, the same layer-by-layer split applies, and Is It the Driver, the Tag or the Screen? works that diagnosis for data.
| Observation | What it means | Next action |
|---|---|---|
| Mark shows on one application screen only | Drawn content: an object, overlay or background element | Open that screen in the engineering tool and inspect its objects |
| Mark holds its place on every screen and on the OS desktop | Display hardware or mounting, not the application | Run the surface, mounting and repair checks below |
| Mark changes when the mounting clamps are eased | Frame stress loading the display assembly | Correct the frame or cut-out, refit to the documented torque, re-test |
| Mark clears after cleaning with the documented method | Deposit on the front surface | Clean as the manual specifies; no repair needed |
| Blemish still visible with the display switched off | Damage or contamination on the front surface | Establish whether it sits on the glass or inside the stack |
The diagnostic sequence #
- Photograph the operating screen and note the mark's position relative to the edges or corners of the display.
- Cycle through the application screens with different backgrounds and record whether the mark moves with the content.
- Stop the runtime and inspect the operating system desktop; record position, shape and size again.
- Switch the display off and view the face under good ambient light, then switch on and compare: a surface deposit stays visible without illumination, while an internal defect reads better against lit content.
- Clean only with the method the panel's documentation specifies, with no pressure on the glass.
- Support the panel so it cannot fall or shift when the clamping force is released, keep the furnace under an approved operating arrangement while its interface is down, then ease the mounting clamps slightly and compare the desktop once more.
- Refit the panel to the flatness, gasket placement and tightening torque given in the installation documentation, and repeat the desktop comparison.
- Read the result against the table above and route the fault.
Mounting stress and furnace heat #
A frame that is not flat, or a distorted cut-out, clamps the enclosure unevenly and can pass stress into the display assembly, where it shows as shading or a darkened local region. Easing the clamps is a diagnostic intervention, not a repair: if the appearance changes, correct the geometry and refit to the documented torque; if the mark survives the correction unchanged, no live load is moving it now, although earlier stress may still have left permanent damage.
The furnace location adds heat to the picture. Measure the conditions at the installed panel and compare them with the limits in the manual for the exact order number: radiant load from nearby burners, enclosure ventilation, and any condensation or contamination. Service age alone does not identify a cause. Mounting geometry and heat derating interact, which the portrait HMI mounting and temperature derating article shows for panels mounted on edge.
A fixed local mark is also a different fault from a panel that goes dark across the whole image after a restart; that symptom has its own panel PC HMI dark screen troubleshooting guide.
Worked example: a fixed dark mark on a Comfort panel after three years at a furnace #
Inputs, and where each comes from:
- Device: KP1200 Comfort panel, order number 6AV2124-1MC01-0AX0, read from the panel label.
- Service history: installed and commissioned three years earlier at a heat-treatment furnace line.
- Symptom: a dark black mark, fixed in place, appeared a few days before the complaint.
- Example screen set, chosen for the test: three application screens with different backgrounds, namely a dark-grey trend overview, a white alarm list and a mid-blue recipe screen.
- The operating system desktop, reached by stopping the runtime.
The rule, in words: a mark that keeps the same physical position while the displayed content behind it changes completely is not drawn by the application; it belongs to the display path. The runtime stop is the decisive view, because the desktop replaces every drawn object at once.
The arithmetic, counted as position changes against content changes:
- Content change 1, trend overview to alarm list: mark position unchanged.
- Content change 2, alarm list to recipe screen: mark position unchanged.
- Content change 3, runtime stopped for the desktop: mark unchanged in position, shape and size.
- Position moved with 0 of the 3 content changes; across 4 views the mark is identical.
- Mounting clamps eased slightly with the panel supported: mark unchanged.
Result: the mark held through every content and mounting change, so nothing in the application or in the live frame load is drawing it.
Decision: the pass line is a single observation, visible with the runtime stopped or not. Here it was visible, so the fault is display hardware: book the repair and leave the project alone. Had the mark vanished on the desktop, it would have been content on one screen, and the fix would be an object edit in the engineering tool.
What is actually failing inside #
An LCD forms the image by controlling how much light from the backlight passes through each point, so a fixed dark region can originate in the image-forming layers, in the illumination behind them, in the optical layers in between, or in mechanical pressure on the stack. A photograph alone cannot separate those mechanisms; the repair assessment opens the panel to do it.
Resist naming the failed part from the outside. Backlight LEDs illuminate regions of the image; they are not the individual picture elements, so a dark patch does not by itself prove which layer failed. What you can document from the outside is the behavior, meaning fixed or moving with content, changed by cleaning, changed by clamping load, and that record is what makes the repair assessment fast.
Repair or replace #
With the mounting corrected and the mark still on the desktop, arrange assessment through the manufacturer's service channel or an authorized display repair service, and send the order number from the panel label, the photographs and the results of your runtime, cleaning and clamping tests. Neither a project download nor a screen-object edit addresses a defect that is visible outside the runtime.
Before the panel comes out of the door, preserve the HMI project and a device backup using the method the manual documents, and confirm what that backup includes.
If a repair is not worth pursuing, one replacement path is a PC-based runtime on industrial panel PCs, provided the project's drivers, ports and license support the new target. Compare cut-out dimensions before committing either way, because the door opening was cut for the old panel.
Checks after the fix #
- Operating system desktop: no persistent dark region where the mark was.
- Application screens that expose the affected area: text, symbols and backgrounds legible.
- Day-one photographs against the screen after final clamping: securing the panel has not recreated or enlarged the mark.
- Operator functions: keys and touch controls, as fitted on the panel, act as intended under controlled process conditions.
- Displayed values and statuses: verified against the controller before the line returns to production.
Questions asked
Will the dark mark keep growing across the screen?
It depends on the mechanism. A defect in a display layer or a mark driven by frame stress usually widens slowly as the fault or the clamping load progresses, and backlight-region failures can extend as more elements drop. A surface deposit or an application object never moves, which is why the runtime-stop test comes first. Photograph the mark next to a scale and compare after a week of normal running; visible growth points to a progressing hardware fault.
Does a firmware update or a fresh project download clear the mark?
No, not once the mark shows with the runtime stopped. Firmware and project files decide only what the panel draws; they cannot change the physical display layers or the light source behind them. Software work is the wrong tool here, and the useful effort goes into the surface, mounting and repair steps instead. Re-downloading the project risks losing the current backup for no gain.
Can the line keep running with the mark on screen?
A fixed mark does not stop the panel working, so if every value, alarm and button the operators need stays legible and reachable, running to a planned maintenance window is a normal choice. Treat it as a deadline: a progressing defect can take the operator interface out with no warning. If the mark already covers alarms, setpoints or touch targets, fix the interface first and keep the furnace supervised in the meantime.
What should go to the repair service with the panel?
The order number printed on the panel label, photographs of the mark taken on the operating system desktop and on two application screens with different backgrounds, and the outcome of your tests: whether stopping the runtime left the mark in place, whether easing the mounting clamps changed it, and whether cleaning with the documented method removed anything. Add the environment at the panel: furnace radiant heat, ambient temperature and ventilation, because installation conditions and the internal defect can be linked.
How do I stop a replacement developing the same fault?
Three installation checks cover the causes this article describes. Confirm the cut-out is flat, undistorted and the correct size, so the frame is never forced to close a gap. Tighten the clamping screws to the torque in the installation documentation for that model instead of by feel. And keep the heat around the panel inside the manual's limits, which on a furnace line usually means a radiant shield or extra ventilation between the burner and the operator station.