Why a KTP 1000 DP reaches two S7-224XP PLCs over MPI
Short answer
The KTP 1000 DP has no Ethernet port, so the usual TIA Portal IP-address advice does not apply. You wire both S7-224XP PLCs onto one MPI network through the panel's RS-485 port, give every station a unique address, and configure two connections in WinCC flexible, one per PLC. Each HMI tag belongs to one connection, and that assignment decides which PLC a displayed value comes from.

On this page
- Can a KTP 1000 DP without Ethernet really read two S7-224XP PLCs?
- How do two PLCs share one MPI cable without mixing their data?
- What has to be set in each S7-224XP before you wire it?
- Where do the two connections get created in WinCC flexible?
- Why does a screen object show the wrong PLC's value?
- What cable, termination and length does the MPI segment need?
- How do you commission and prove both connections safely?
- Why doesn't the TIA Portal IP-address advice apply here?
- Questions asked
Yes. A KTP 1000 DP with no Ethernet port can display live data from two S7-224XP PLCs at the same time. The arrangement is one MPI network on the panel's RS-485 port, two controller connections configured in WinCC flexible, and HMI tags that are each bound to one of those connections. This article gives the addresses, the port settings, the cable, the length arithmetic and the test that proves both connections — and it explains why the usual TIA Portal IP-address instructions do nothing for this panel.
Can a KTP 1000 DP without Ethernet really read two S7-224XP PLCs? #
Yes. The panel's DP interface is an RS-485 port that also carries MPI traffic, and MPI is a multipoint network, so one cable, one panel port and one configured project reach every addressed station on the segment. The DP in the panel's name describes the connector and protocol family, not a requirement to run a DP master configuration; on this network the panel is simply a station that polls two others.
Two things must both be true for the arrangement to work, and they fail independently:
- Electrically, the panel port, both PLC ports and the cable must form the documented bus.
- Logically, the panel project must contain two configured connections, one per PLC. Wiring a second PLC onto the cable does not create a second connection — that is the single most common reason only one PLC's data appears.
If your controllers are on a plain serial link instead of MPI, the general case is covered in connecting one HMI panel to two PLCs over serial.
How do two PLCs share one MPI cable without mixing their data? #
Every station on the bus carries a unique MPI station address, with valid values from 0 to 126, and the panel addresses each request to exactly one station, so the two PLCs never mistake each other's traffic for their own. One MPI segment accepts up to 32 stations, which leaves room for both PLCs, the panel and a programming PC on the same cable.
Duplicate addresses are the failure to design out. Two stations answering to one address produce intermittent or misleading behavior — replies from either device, one connection flapping, diagnostics blaming the wrong station — not a clean configuration error. Keep a written address list covering every device on the segment and verify each entry in the device itself before commissioning.
Where HMIs multiply instead of PLCs, the per-port client count of the CPU becomes the limit; the MPI case is documented in why an S7-226 MPI port limits you to three HMI clients, and the same counting discipline applies when you plan growth.
What has to be set in each S7-224XP before you wire it? #
In the S7-200 programming software you configure the port that will face the panel — port 0 or port 1 — with the network's transmission rate and its unique station address; the S7-224XP supports MPI at up to 187.5 kbps. The settings live in the CPU's System Block port configuration, and they only take effect after the block is downloaded to the PLC.
Three rules when you touch those ports:
- Record what the port does today before changing it. A port may already serve programming downloads or another network, and reconfiguring it drops that traffic.
- Match the transmission rate exactly across the panel and both PLCs. A station at a different rate is not slow — it is invisible, and the fault looks like broken wiring.
- Use the port that is currently free on each PLC, and leave the other port for programming or existing duties.
Where do the two connections get created in WinCC flexible? #
In the project's Connections editor you create two new connections with the driver documented for S7-200 controllers over MPI, each pointing at one PLC's station address; the panel's own station address is configured in the same editor. Name the two connections after the equipment they serve — for example LineA and LineB — so the tag table stays readable a year from now.
Each connection is a complete, independent path: its own station address on the far end, its own diagnostic, its own behavior when its PLC drops off the bus. The panel schedules the requests of both connections over the shared cable, so more connections and faster acquisition cycles mean more bus traffic, not more physical channels. Group your tag acquisition by operational need rather than polling every value at the fastest available cycle.
Why does a screen object show the wrong PLC's value? #
Because every HMI tag carries the name of the connection it belongs to, and a tag copied from the first PLC keeps that first connection even after you edit its address or rename it. The panel has no other way of knowing which controller you meant — the connection name on the tag is the entire ownership record.
A worked example with two nearly identical machines: both programs store a parts counter in the same V-memory word, say VW100. In the tag table you create:
- LineA_Count, connection LineA, address VW100
- LineB_Count, connection LineB, address VW100
Both addresses are identical and that is fine — the connection field separates them. But if LineB_Count was built by copying LineA_Count and its connection field was left at LineA, the panel reads PLC A twice. The telltale is that both displayed counters track each other exactly, even while the two PLCs count different parts. When you see two displays moving in lockstep that should not, check the connection field before you check any wiring.
What cable, termination and length does the MPI segment need? #
Use the specified PROFIBUS-type RS-485 cable, terminate at the two physical ends of the segment, and keep the total segment within 1000 m at the network's transmission rate. Intermediate stations tap the bus through their connectors without terminating; the termination setting belongs to the connectors at the two ends, following the connector manufacturer's instructions. Avoid improvised star wiring — a branch that works on the bench is the intermittent fault you will chase in production.
The length check is simple addition. Example: the trunk runs 180 m from the control room to the panel, 220 m from the panel to the first PLC, and 95 m from the first PLC to the second:
180 m + 220 m + 95 m = 495 m, under the 1000 m limit — one segment, no repeater.
If a planned reroute adds another 560 m of cable, the total becomes 1055 m, over the limit — either re-route or split the network with a repeater at a documented point. Do the arithmetic on the as-installed lengths, not the drawing.
How do you commission and prove both connections safely? #
On an isolated bench or in a maintenance window, test each connection alone using a read-only value you can distinguish between the PLCs, then test both together, then interrupt one side and confirm the fault appears only there. Use values that cannot change an output — for example, let PLC A hold a counter in the thousands and PLC B in the tens of thousands, so a swapped connection is obvious at a glance.
The sequence:
- Compare the panel's LineA value against the online view in the programming software; they must agree with no communication message.
- Repeat for LineB with its own tag; the second display must follow PLC B, not PLC A.
- Run both connections together and confirm each value keeps tracking its own controller.
- During the authorized test window, disconnect one PLC's connector without disturbing bus termination. The affected tags must show a communication error, not a stale value presented as fresh, while the other connection keeps updating.
- Reconnect and confirm the diagnostic clears and the values return to agreement.
One safety limit: a screen refresh is not an interlock. Never use what the panel displays as the coordination mechanism between the two machines — controller-to-controller coordination belongs in the PLCs' own network instructions. When one panel must also send commands to both machines, that is the separate arrangement described in connecting one HMI to two PLCs with independent modes.
Why doesn't the TIA Portal IP-address advice apply here? #
Because this panel has no Ethernet interface and no project in TIA Portal: the KTP 1000 DP is engineered in WinCC flexible, and on MPI there is no IP address anywhere — only station addresses and one shared transmission rate. Advice that says to open a Connections view and enter the right IP addresses describes a different panel family with a different engineering tool, and following it on this hardware leads nowhere.
The decision tree, once:
- If your engineering software asks for IP parameters for the HMI connection, you selected the wrong panel device in the project — reselect the DP-interface panel.
- If the project is correct and only one PLC shows data, the missing or mis-addressed second connection is the fault, not the cable.
- If both displays show the same controller, the tag connection fields are the fault, not the network.
Questions asked
Can the two S7-224XP PLCs exchange data with each other through the KTP 1000 DP?
No. The panel reads and writes each PLC independently over its own connection and never routes data between controllers. For controller-to-controller coordination, use the S7-200 network read and write instructions on a port of their own, designed and tested separately from the HMI traffic.
Can a third PLC or another HMI join this MPI network later?
The segment accepts up to 32 stations and the address space runs to 126, so the bus has room; the real gates are the panel's documented connection count and the polling load you add. Give the newcomer a fresh address, keep the transmission rate identical everywhere, and repeat the connection test with three stations before trusting the panel.
Does the DP in the panel's name mean I need a PROFIBUS DP master on the network?
No. In this arrangement the DP-designated port carries MPI traffic, and the panel is an ordinary station that polls the two PLCs. Nothing on the segment needs a DP master configuration. If a tool demands DP master parameters for the HMI connection, the wrong connection type was selected in the project.
What happens if both PLCs are accidentally given the same station address?
Expect intermittent or misleading behavior rather than a clean rejection: replies can arrive from either PLC, one connection may flap, and diagnostics may blame the wrong station. Keep a written address list covering the panel and every PLC, and verify each address in the PLC's port settings before commissioning.
Can the programming PC stay on the same network while the panel runs?
Only if it takes its own unused station address and matches the network's transmission rate. On an S7-200 the same port serves programming and runtime communication, so a download to one PLC interrupts the panel's data from that PLC. Schedule downloads for a maintenance window instead of sharing the bus during production.