Why a KTP600 Basic DP needs a PC Adapter USB A2 for transfer

HMI and touchscreens Published 7 min read

Short answer

A KTP600 Basic Color DP has no Ethernet port, so its project cannot be loaded through the S7-1200's Ethernet connection: the CM 1243-5 is a DP master for process data, not an engineering gateway. The documented path is a PC Adapter USB A2 (6GK1 571-0BA00-0XA0) on the panel's PROFIBUS socket, with transfer channel, baud rate and station addresses matched. The USB/PPI Multi-Master Cable is a different adapter for the S7-200 world.

On this page
  1. The DP in the panel's name is its only transfer channel
  2. Why the transfer cannot ride the CPU's Ethernet connection
  3. The adapter the vendor lists, and the one you already have
  4. The settings that decide the transfer
  5. Working the transfer path: 1214C, CM 1243-5 and a KTP600 Basic Color DP
  6. Questions asked

Your KTP600 Basic Color DP will not accept a transfer through the CPU's Ethernet port, and the USB/PPI Multi-Master Cable you already have is not the tool for it either. The panel has no Ethernet interface at all: its project downloads over PROFIBUS, and the adapter the vendor lists for that job is the PC Adapter USB A2, order number 6GK1 571-0BA00-0XA0. With that adapter on the panel's DP socket, the panel in transfer mode, and baud rate and station addresses matched, TIA Portal V16 offers the panel as a download target. What follows is why the CM 1243-5 cannot carry the transfer, which adapter does what, and the settings that decide success.

The DP in the panel's name is its only transfer channel #

Two different jobs share a panel's network interface, and it pays to keep them apart. The runtime connection carries process data between the HMI and the controller - on your line-up, the DP link from the CM 1243-5 to the panel. The transfer channel is what the engineering software uses to load the project, and on the KTP600 Basic Color DP it is that same physical PROFIBUS interface. The suffix is the whole story: this variant has no Ethernet port, so there is nothing on the panel for your PC's Ethernet cable to reach, whichever device that cable runs through.

When you configure the HMI in the project, its transfer settings therefore offer exactly one option that exists on the hardware: PROFIBUS. Instructions written for the PROFINET variants of the same panel family do not apply to the unit on your bench.

Why the transfer cannot ride the CPU's Ethernet connection #

The Ethernet cable to the 1214C gives TIA Portal engineering access to the CPU - that is how the PLC program downloads, and it is all that leg does. It proves itself one way: the software must reach the CPU before anything else, the point covered in why HMI programming software needs a ping reply to download. If TIA Portal cannot go online with the CPU at all, fix that first; an S7-1200 that shows link lights but TIA Portal cannot connect is a separate fault with its own checks. A working CPU connection says nothing about the DP segment behind the CM.

The CM 1243-5 is a DP master. Its datasheet gives up to 16 DP slaves, and its documented communication service is cyclic exchange of process data between master and slave, handled by the operating system. That is a runtime role. A DP master is not an engineering gateway: none of its documented services forwards a project download from the CPU's PROFINET side out to a slave.

S7 Routing is the one mechanism that does forward engineering traffic between networks, and the vendor publishes a dedicated FAQ for transferring HMI projects that way in WinCC (TIA Portal). Read the conditions and you find the catch: routing works only when every node in the path supports it, interface by interface, panel included. The S7-1200 documentation describes S7 routing between CP interfaces; the interfaces in your path are the CPU's PROFINET port and a DP-master CM whose documented job is process data. For a DP-only Basic Panel behind a CM 1243-5, the vendor's connection-cable FAQ, document 19109408, points to the PC Adapter USB A2 - not to a routed path.

So the direct answer to "can I go through the module from Ethernet?" is no in this line-up. Plan the adapter, and do not hold commissioning on a routed transfer.

The adapter the vendor lists, and the one you already have #

Read the order number before you plug anything in, because the two adapters in this story share a connector family and nothing else.

The PC Adapter USB A2, 6GK1 571-0BA00-0XA0, presents an MPI/DP interface to the PC over USB, and the vendor's connection-cable FAQ lists it for the KTP600 Basic Color DP, with the KTP1000 Basic Color DP beside it. Its driver comes from the manufacturer; once installed, the adapter appears in TIA Portal's online-access settings as a selectable interface. That is the adapter to get for this panel.

The USB/PPI Multi-Master Cable, 6ES7 901-3DB30-0XA0, is a different product for a different family: it links a PC to S7-200 networks over PPI, and the connection faults it does produce belong to that world, as covered in troubleshooting a USB/PPI Multi-Master cable connection to an S7-200. It is not the adapter the vendor lists for this panel, so time spent forcing it into this transfer is time lost. If you try it once anyway and nothing appears, you have learned nothing about the panel. Get the A2.

The settings that decide the transfer #

Four settings have to agree before the panel appears as a target: transfer channel, baud rate, station addresses and wiring. Image compatibility is a separate question, handled last.

On the panel, open the transfer settings from its start screen: enable the PROFIBUS channel, write down the station address and transfer baud rate it shows, then press Transfer - the panel now waits for the engineering side. A panel that is merely running its project is not in transfer mode; a live process-data connection proves nothing about transfer readiness.

On the PC, open the adapter's interface in TIA Portal's online-access settings and set it to PROFIBUS, with the baud rate exactly equal to the panel's transfer rate and a PC station address nothing else on the segment uses. Start the HMI download, select that adapter interface instead of the CPU's Ethernet, and the panel shows up under its station address - confirm the device identity before you load anything.

For the physical link, plug the adapter straight onto the panel's DP socket with the operating bus disconnected: the temporary segment is one connector long, so bus termination does not come into play. Do that only with the machine in a safe stopped state - the moment the panel leaves the bus, your operator has no screen, and the download restarts the panel anyway. If you must connect with the bus live, attach the adapter without disturbing the termination at the physical ends, and verify the segment the way how to check PROFIBUS termination when an HMI reads no data describes.

Last, the image: if TIA Portal V16 reports that the panel's image does not fit the project, the download offers an operating-system update. Read that prompt before accepting it, and settle the version question as described in matching an HMI panel image to its TIA Portal project version. An image mismatch and a communication fault are different animals; fix the path first.

Working the transfer path: 1214C, CM 1243-5 and a KTP600 Basic Color DP #

Inputs, each with its source:

  • Engineering link: an S7-1200 1214C DC/DC/DC connected to the PC by Ethernet - the setup in front of you.
  • DP segment: a CM 1243-5 master, which takes 24 VDC power from the CPU per the S7-1200 manual, with the panel as its configured DP slave.
  • Panel: the KTP600 Basic Color DP; its station address and transfer baud rate are read from its own transfer screen, never assumed.
  • Adapter: the PC Adapter USB A2 named above, USB to MPI/DP per the vendor's connection-cable FAQ.
  • Tool: TIA Portal V16 with the compiled HMI project.

The rule, in words: a transfer succeeds when one physical segment reaches the panel and the four settings agree on it - channel, baud rate, unique addresses, seated connectors. The Ethernet leg carries none of the project.

The arithmetic:

  • Ethernet ports on this panel variant: 0. Project bytes that can reach the panel through the CPU's Ethernet port: 0 of the total.
  • Stations on the temporary point-to-point segment: 1 adapter + 1 panel = 2. Distinct addresses required: 2. With the adapter set to an address the panel is not using: duplicates = 2 - 2 = 0. Pass.
  • Baud rates in play: one value, copied from the panel's transfer screen into the adapter's interface setting - one value, two ends, exact match required.
  • Slave count during the session: the adapter is an engineering node, not a configured slave, so the master's configuration of 1 slave stays at 1.

Result: the working path runs from the PC, over USB, through the adapter, onto the panel's PROFIBUS socket - panel in transfer mode, one baud rate, two distinct addresses, no termination hardware on a one-connector segment. Run the download over the adapter interface and confirm the target's identity before you load.

Decision: if the panel does not appear as a target, stop recompiling - the fault is in the four settings, checked in this order: transfer channel on the panel, baud equality, address uniqueness, connector seating. If the Ethernet download dialog offers only the CPU, that is the expected result for this line-up, not a fault to chase. When the download completes, refit the bus connector, take the panel out of transfer mode, and confirm process data is back before handing the machine over.

Questions asked

Does the operating-system update use the same connection as the project transfer?

Yes. The image update travels over the same transfer channel, so one adapter session carries both. Accept the offered update with the machine stopped: the panel installs the image and restarts before the project lands, and a project compiled for a newer image will not run until that update is in place.

What does the PLC do while the panel is unplugged for the transfer?

The CM 1243-5 sees its DP slave disappear and the CPU logs a slave or bus failure for as long as the panel is off the segment; the fault clears once the panel is back in runtime. That message is expected during the session, not a wiring fault. Note it, finish the transfer, then confirm it is gone before handover.

Can another PROFIBUS interface replace the PC Adapter USB A2?

Yes, provided TIA Portal V16 supports it for PROFIBUS engineering access, for example a PROFIBUS communication processor fitted in a desktop PC. Any such interface must speak the same engineering protocol the transfer uses. The PC Adapter USB A2 remains the current USB adapter the vendor's FAQ names for this panel, and the practical choice for a laptop.

How do I avoid the adapter on the next machine build?

Specify the PROFINET variant of the same Basic Panel family. It downloads over the Ethernet link you already use for the CPU, with no adapter and no bus interruption for the transfer. The DP variant you have keeps its adapter-only path for life, so keep one adapter in the commissioning kit.

Keep reading

  • Selection guide

    Do You Need SCADA Software for a Modbus HMI Project

    No. Modbus only proves a possible data link, so pick the runtime target first: a touch panel programmed by its own editor for machine-side parameter control, or a licensed PC SCADA runtime when the screens must run on a computer. The documented demonstration mode of a Vijeo Citect-class runtime stops after about 15 minutes with live devices, which settles a bench test but not continuous operation.

    HMI and touchscreens

  • Troubleshooting

    Configure a PROFIBUS to EtherNet/IP gateway for HMI and PLC

    Selecting PROFIBUS-DP Slave and EtherNet/IP Scanner in SYCON.net assigns only the gateway's own roles on each network. The link still needs the MP277 configured as PROFIBUS DP master from the gateway's GSD description, and the SLC 5/05 configured as the documented target of that scanner connection. Verify each side's status separately before mapping data; PC recognition of the gateway proves none of it.

    HMI and touchscreens

  • Troubleshooting

    Fixing a Vijeo Designer USB transfer filesystem path error

    The [HMIS] filesystem path error means the software resolved the wrong transfer destination, and the connection-abort line is only its consequence. Because the failure sits on one workstation, compare that PC's target selection, transfer method and installed version against a working one before touching the Runtime installer, and keep the two-to-three-times-slower USB-key route as a fallback.