IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a LOGO! 0BA7 HMI Connection Fails Despite Matching TSAPs

HMI and touchscreens Published 7 min read

Short answer

Keep local TSAP 20.00 and remote TSAP 10.00 on the LOGO! 0BA7 server connection and tick the accept-all check box in the connection you actually download: the reported fix was client admission, not new TSAP values, with the EasyBuilder Pro driver pointed at the master at 192.168.1.100. A one-bit read on an isolated bench proves it.

On this page
  1. Why does the LOGO! 0BA7 refuse the HMI when both TSAPs look right?
  2. How do local and remote TSAPs pair across the two ends?
  3. Where do you set the server connection and the accept-all flag?
  4. Which address should the EasyBuilder Pro driver target?
  5. How do you prove the repaired connection with one bit?
  6. When is a fixed peer the better choice than accept-all?
  7. Questions asked

A LOGO! 0BA7 that exchanges I/O with its slave and still refuses every read from an EasyBuilder Pro panel is refusing the connection at its server entry, not at the switch. The programming downloads and the master-to-slave link never touch that entry, so they prove the IP path and nothing about the data session. Keep the server connection at local TSAP 20.00 with remote TSAP 10.00, tick the check box that accepts all connection requests in the connection you actually download, and point the driver at the master at 192.168.1.100. In the reported case with exactly these addresses, the repair was that admission flag in the downloaded connection, not new TSAP values.

Why does the LOGO! 0BA7 refuse the HMI when both TSAPs look right? #

Tick the accept-all check box on the LOGO!'s server connection and keep local TSAP 20.00 with remote TSAP 10.00: a fixed-peer entry admits only a partner presenting exactly the configured remote endpoint, and the panel's source TSAP is the side you cannot read or set. A server entry with the box clear is a filter, not a label: the LOGO! answers only a partner that presents the exact remote endpoint typed into that entry, and the panel's driver assembles its own source endpoint internally, where you cannot inspect it.

With the box ticked, the LOGO! responds to requests from all clients, and the only endpoint that still has to be right is the one the panel asks for. The flag counts in the connection downloaded into the controller; the same project open offline with the same ticked box proves nothing. The panel side alone could never have fixed it, because the driver's documented settings configure the panel's end while the admission decision lives in the LOGO!. Drivers also fail differently: the Rockwell case against the RCE variant of this controller is its own fault, covered in why a TP 177micro cannot connect to a LOGO! 0BA7 RCE.

How do local and remote TSAPs pair across the two ends? #

Each end of an ISO-on-TCP connection owns a two-byte TSAP, and the pair must mirror: the value the LOGO! lists as local is the value the panel must request, while the value it lists as remote is what the panel must present as its own source. ISO-on-TCP is the RFC 1006 transport that carries S7 communication over TCP, and it requires both partners to be identified by such a pair. The notation writes the two bytes as decimals, so 20.00 is the byte pair 0x14 0x00 and 10.00 is 0x0A 0x00. Copying the controller's local value into the panel's local field mirrors it the wrong way: on the panel, that number belongs in the field for the controller's TSAP, wherever the driver exposes one.

Field in the LOGO! server entry Value in this setup What it must equal on the panel side
Local TSAP 20.00 The TSAP the driver requests for the controller
Remote TSAP 10.00 The source TSAP the driver presents, with a fixed peer
Accept-all check box Ticked Nothing: it removes the source-endpoint filter

The same mirror rule explains an S7-1200 that fails against a LOGO! even with matching values on paper, worked through in the guide to S7-1200 TSAP configuration when a LOGO! connection fails despite matching TSAPs.

Where do you set the server connection and the accept-all flag? #

Open the Ethernet connections dialog from Tools → Ethernet connections, add an entry of type Server Connection, keep the local TSAP the tool assigns, set the remote TSAP to 10.00, and tick Accept all connections requests before you download. The order matters, because each step closes one of the faults this symptom hides:

  1. Open the project that matches the controller and enter Tools → Ethernet connections; the master-to-slave exchange already occupies one entry, and the HMI needs a second.
  2. Open that entry, the first is named Connection1, and confirm its type reads Server Connection.
  3. Leave the local TSAP at the value the tool assigns; for a server entry it is not editable.
  4. Tick Accept all connections requests, which makes the server answer requests from all clients.
  5. Download the project to the controller; the flag exists in the controller only after that transfer.
  6. In EasyBuilder Pro, point the device at the master's address and, where the driver exposes a controller TSAP, enter the server entry's local value.

A ping or a successful program download runs none of these steps: programming transfers use a different service than the runtime data session, which is why both worked while the panel stayed blind.

Which address should the EasyBuilder Pro driver target? #

Point the EasyBuilder Pro device at the master at 192.168.1.100, because that is where the server entry lives; the slave at 192.168.1.101 exchanges I/O with its master over the master-to-slave link and admits no panel until it gets a server entry of its own. The reported setup, used here as the worked example:

Device Address Subnet mask Role in the diagnosis
LOGO! master 192.168.1.100 255.255.255.0 Hosts the server entry the panel must reach
LOGO! slave 192.168.1.101 255.255.255.0 Talks to the master only; opens no panel path
HMI panel 192.168.1.150 255.255.255.0 Originates the runtime connection

The subnet check that rules the path in or out:

  • Panel network: 192.168.1.150 AND 255.255.255.0 = 192.168.1.0
  • Master network: 192.168.1.100 AND 255.255.255.0 = 192.168.1.0
  • Equal results mean one subnet: frames go straight from panel to master, the empty gateway field is correct, and no router is consulted. A panel moved to 192.168.2.150 would AND to 192.168.2.0, miss the master's subnet, and need a gateway.

Adding a gateway entry cannot repair a refused session between two devices that already share a subnet, and the working downloads already demonstrated that path.

How do you prove the repaired connection with one bit? #

Bind a display-only object to a single bit the program drives, watch that bit in the controller's online monitor, change it once without touching machine outputs, and let the panel's communication status plus the following state change split a session fault from an addressing fault.

  • Run the test on an isolated bench with the machine's outputs disconnected: a communications check must never move a machine.
  • Pick the bit from the addresses the driver documents; a terminal input you can close by hand or a bit the program toggles both work. Keep indirect addressing and display expressions off the test object.
  • Note the bit's state in the online monitor, then change it once.
  • Read the outcome: a dead session with the driver reporting offline sends you back to the server entry and its flag; a live session with a frozen bit sends you to the address syntax and the memory areas the driver can reach; a bit that follows the change sends you back to the original object's binding and expressions.
  • If the test needs a write, target a VM bit rather than a physical input, for the reason in why an HMI button should write a LOGO VM bit not I1.

For the wider split between driver, tag and screen, the sequence in Is It the Driver, the Tag or the Screen? Diagnosing HMI Values applies unchanged.

When is a fixed peer the better choice than accept-all? #

Keep a fixed peer when you control both ends and the partner presents a stable source TSAP — PC Access, SIMATIC NET or another S7 CPU — and use accept-all where the client's source TSAP is invisible, which is the honest description of most panel drivers. Both settings pass traffic once the pairing genuinely matches; the difference is who does the checking. With a peer you administer, enter its source TSAP as the entry's remote value and keep the filter: it costs nothing and it refuses strangers. With a panel driver that builds its source TSAP internally, the filter can only guess, so accept-all is the correct steady setting for the HMI entry, not a diagnostic shortcut. The case where both sides expose their endpoints is worked through in the guide to resolving LOGO! 0BA7 TSAP issues with PC Access and SIMATIC NET. Neither setting excuses a wrong requested TSAP: the mirror rule above still decides whether the request lands on the server entry at all.

The decisions, case by case: a panel driver goes to the master's address with accept-all ticked and its requested TSAP equal to the server entry's local value; a wrong requested TSAP is repaired in the driver, never by the flag; a second HMI or an OPC client needs no second entry once accept-all is on, but each live session consumes one of the controller's connection slots; and a peer that shows you its source TSAP keeps the fixed-peer filter.

Questions asked

Does the accept-all check box let any device write to the LOGO! 0BA7?

Yes, within routing reach: the setting makes the server answer every client that can send a request to its communication port, so admission control moves from the LOGO! to the network. Keep that port off any forwarded or internet-facing path, keep the machine network its own segment, and switch back to a fixed peer only when the client exposes a stable source TSAP you can enter.

How many connections can a LOGO! 0BA7 hold at once?

Practitioners report the 0BA7 holds eight connections at once, and every simultaneous session takes one: the master-to-slave exchange, every panel, every OPC client. Before adding an HMI, count the sessions the cell already runs; a configuration that looks right but refuses new sessions has usually hit that ceiling.

Can the HMI read the slave LOGO! directly instead of the master?

Only after the slave gets its own server entry, with the same accept-all treatment and a download; the working master-to-slave exchange does not open the slave to other clients. The cleaner route is to leave the HMI on the master and have the master's program copy the slave data it already reads into its own memory, so one connection serves the whole cell.

Can you change the server connection's local TSAP from its default?

No: for a server entry the tool assigns the local TSAP and does not accept edits, which is why chasing a different value wastes an afternoon. What matters is that the client requests exactly the assigned value, so read it from the downloaded project, not from a screenshot, and enter that value wherever the driver asks for the controller's TSAP.

Keep reading

  • How-to

    Configuring Dual LAN HMI Ports for Two PLC Networks

    Yes. A dual-LAN HMI terminal with two independently configurable interfaces reads a PLC on each network when LAN1 and LAN2 carry non-overlapping subnets and sit on physically separate segments. A remote client on the LAN1 side reaches the terminal itself over VNC, cMTViewer, OPC UA or Modbus TCP, but not the devices behind LAN2.

    HMI and touchscreens

  • Troubleshooting

    When VNC works but HMI project upload fails over Ethernet

    A VNC session proves only an IP path to the panel's viewer service; it says nothing about the engineering transfer service the upload tool needs. Read the panel's real address, put the PC in that subnet, test LAN1 and LAN2 separately, then check adapter selection and the panel-side transfer enable. Copy the project to USB before any firmware recovery.

    HMI and touchscreens

  • Troubleshooting

    Connecting a Delta DVP 15MC PLC to a Weintek HMI

    The DVP 15MC exposes its data to an HMI as a Modbus TCP server on the standard port 502. In EasyBuilder Pro, use a 15MC-specific driver if your editor's driver list has one, otherwise the generic Modbus TCP driver with the controller's register-to-Modbus mapping table. A 64-bit QWORD spans four holding registers, so prove one read-only tag before building screens.

    HMI and touchscreens