Troubleshooting
Why a PanelView 1000 Banner Shows Only One Alarm at a Time
Short answer
The banner is doing what it is configured to do: set to the first unacknowledged alarm, it holds one message while the rest wait in the alarm list. Alarms missing from the list too point to the single integer that can hold only one alarm number — replace it with one latched bit per alarm.
On this page
Stop adjusting scan time. A PanelView 1000 banner that shows a single alarm while several are active is usually doing exactly what it was configured to do: set to display the first unacknowledged alarm, the banner holds one message until an operator acknowledges it, and every other alarm is still captured in the alarm list. Open that list before touching the PLC. Alarms present in the list but absent from the strip are a presentation choice, and the fix is the banner selection or a full-page list. Alarms missing from the list as well trace back to the data design, because one integer holding one alarm number can only ever represent one alarm, whatever the scan does. A third fault hides on the acknowledge path, where the decimal value the terminal writes back has to decode into the right bit.
Open the alarm list before changing the PLC #
Add a full-page alarm list to the application, or open the alarm history, and trip two alarms together. Two minutes here decides which of three faults you have:
- One message in the banner, several entries in the list. The alarms are captured. The banner's selection property is choosing which one to show, and everything downstream of the PLC is fine.
- One alarm everywhere, list included. The PLC never presented the second condition to the terminal: either one integer is being overwritten by the next alarm's write, or the condition does not stay active long enough to be polled.
- The acknowledged alarm will not clear, or the wrong one clears. The acknowledge value returning from the terminal is being decoded into the wrong bit.
A list that stays empty even for a single alarm is a different failure altogether, a dead alarm display rather than a selection problem, of the kind covered in why PanelView 600 Plus alarms stay blank.
Blaming scan time treats this as a timing fault before anyone has looked at the data. The same discipline as separating PLC scan time from real HMI communication faults applies here: establish what the PLC data actually contains, then decide whether timing plays any part at all.
How the banner chooses the one alarm it shows #
The banner is a strip with room for a fixed number of lines, and its selection property decides which active, unacknowledged alarm fills it. On these terminals the reported choices are the first unacknowledged alarm and the most recent alarm to arrive. Set to the first unacknowledged, the strip shows exactly one message — the oldest unacknowledged alarm — holds it until someone acknowledges it, then advances to the next. Two alarms tripping in the same second therefore look like one, and that is the configured behavior, not a fault.
The decision: if operators must see every active alarm at once, the strip is the wrong tool for that job. Keep the banner as the attention-getter and put a full alarm list on its own screen, keyed from the same alarm bits. On PanelView Plus terminals the neighboring configuration question is how the FactoryTalk View ME alarm banner behaves after an acknowledge.
One integer per alarm cannot hold two alarms #
In the arrangement where each alarm message is selected by the value written into a shared integer, the word holds exactly one alarm identity at any instant. When one rung writes the first alarm's number and a later rung writes the second's, the integer ends at the second value and the terminal's poll returns only that; the first alarm never existed as far as the display is concerned. Slowing the scan cannot fix this, because the limit is capacity, not timing: a scan of any length still leaves one value in one integer.
The repair is structural. Give each alarm its own bit in a retained word, latch the condition into that bit, and clear it explicitly from the acknowledge or reset logic. Two simultaneous alarms then coexist as two set bits the terminal can poll at leisure, and acknowledging one leaves the other untouched. A condition that is true for only one scan needs the same latch: the terminal reads on its own schedule, asynchronous to the PLC scan, so a one-scan pulse can fall between polls and disappear from the list as well as the banner.
Worked example: acknowledging alarm bits 0, 3 and 15 on one 16-bit word #
Inputs:
- Alarm storage: one 16-bit integer in the PLC-5/20 data table, one alarm per bit — the design the fix above ends with, and the arrangement described in a field report on this terminal family.
- Acknowledge path: when an operator acknowledges an alarm, the terminal writes a decimal value back to the PLC identifying that alarm's bit (reported terminal behavior).
- Interpretation: the word is handled as a signed integer on this path; the same field report describes bit 15 acting as a sign identifier.
- Test alarms placed on bit 0, bit 3 and bit 15.
Rule in words: the decimal weight of bit n is 2 raised to the nth power, and a signed 16-bit word covers -32768 through 32767.
Arithmetic:
- Bit 0 weighs 2^0 = 1; bit 3 weighs 2^3 = 8; bit 7 weighs 2^7 = 128; bit 14 weighs 2^14 = 16384.
- Bit 15 weighs 2^15 = 32768, one count past the signed maximum of 32767, so the word stores 32768 - 65536 = -32768.
- Two alarms active on bits 3 and 7: the word reads 8 + 128 = 136, inside the signed range. Acknowledging alarm 3 returns 8, clearing bit 3 leaves 136 - 8 = 128, and alarm 7 stays active and listed.
Every acknowledge weight is therefore a power of two equal to 1 or greater; decimal 0 is not among them, because no power of two equals zero.
Decision:
- Acknowledge the bit 0 alarm and read the value that returns: it must be 1. The field report shows what a returning 0 does in practice — the decoded word came back all zeros and nothing set, on a path using the DCD instruction. Treat a returning 0 as a broken mapping, the bit number sent where the weight belongs, and correct it before trusting any alarm in the lower bits.
- Acknowledge the bit 15 alarm: expect 32768, seen as -32768 through a signed read, and expect any sign or range check in the decode to misroute it. The decision that follows: run alarms on bits 0 through 14, which is 15 alarms per word, and open a second word past that — also the workaround the field report settled on.
Test the whole path, one alarm at a time #
With the machine in a safe state — outputs inhibited or the process simulated — prove each stage before moving to the next:
- Trip one alarm and follow it end to end: rung true, bit set in the word, message in the banner, entry in the list.
- Hold that alarm active and trip a second. In the repaired design both bits set and both entries list; in the old single-integer design you will watch the value replace itself and the first alarm vanish.
- Acknowledge the first alarm and record the decimal value that returns and the word after decode. The second alarm must stay active and stay listed.
- Repeat at the boundaries: bit 0 must acknowledge with weight 1, bit 15 with 32768 read as -32768 signed.
- Only after the list behaves correctly, change the banner's selection property if the strip still shows operators less than they need.
That sequence assigns every symptom in this article to exactly one place: correct list plus single-message banner is configuration, missing list entries are the PLC data design, and a wrong or empty acknowledge is the decode path.
Questions asked
Why does the PanelView 1000 banner show only one alarm when several trip together?
Because it is configured to. A banner set to the first unacknowledged alarm displays that one message and holds it until an operator acknowledges it; the other alarms are captured and sit in the full alarm list. If operators need to see all active alarms at once, keep the banner as an attention-getter and add a full-page list keyed from the same bits.
Will a longer PLC scan time bring the missing alarms back?
No. One integer holding one alarm number is a capacity limit, not a timing problem: the second alarm's write replaces the first no matter how the scan is timed, and a poll can only ever return the value present at that instant. The fix is one latched bit per alarm, not a slower scan.
What decimal value should the terminal return when an alarm is acknowledged?
A single power of two identifying the bit: bit 3 returns 8, bit 7 returns 128, bit 0 returns 1. Decimal 0 is not a valid weight, because no power of two equals zero, which is why a zero coming back for bit 0 decodes to an all-zero word and sets nothing.
Is bit 15 safe to use for an alarm?
Not where the word is read as a signed integer. Bit 15 weighs 32768, which a signed 16-bit word shows as -32768, so sign and range checks in the decode misroute it. Use bits 0 through 14 for 15 alarms per word and add a second word when you need more.