IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a PC Adapter cannot download WinCC Flexible to a TP177

HMI and touchscreens Published 7 min read By IMDTouch engineering team

Short answer

A PC Adapter that goes online with an S7-300 is working; it is a programming adapter, not a panel download cable. WinCC flexible reaches a TP177 over the bus only by S7 routing through the PLC, with the adapter plugged into a bus connector that has a PG socket and the panel's address, baud rate and interface type matched on the panel, the adapter and the transfer dialog. A TP177B can instead transfer directly over USB or Ethernet.

On this page
  1. The adapter is healthy; the transfer path is missing
  2. Direct transfer or S7 routing
  3. The wiring that routing needs
  4. Settings that must agree in three places
  5. Matching a TP177 and a PC Adapter on a 1.5 Mbps PROFIBUS bus
  6. When the transfer still fails
  7. The decision for each case
  8. Questions asked

A PC Adapter that goes online with an S7-300 is doing its real job: it is the programming adapter for S7 PLCs over MPI or PROFIBUS, not a panel download cable. Point WinCC flexible at a TP177 with it and the transfer stops at the first attempt with the message that no connection could be established. The panel is not reached directly. The transfer goes through the PLC's subnet by S7 routing, with the adapter plugged into a PROFIBUS bus connector that carries a PG socket, and with the panel's address, baud rate and interface type matched on the panel, on the adapter and in the transfer dialog. If your unit is a TP177B, USB or Ethernet gives you a direct transfer without the adapter.

The adapter is healthy; the transfer path is missing #

Going online with the S7-300 through the adapter proves four things at once: the adapter works, its driver is installed, the cable is good and the bus is alive. Nothing on that list is the problem.

The problem is what the transfer is allowed to do. A transfer writes the panel's project memory through the panel's transfer channel, and over MPI or PROFIBUS the released path with this adapter is S7 routing: the panel appears as a station on the PLC's subnet, the transfer dialog addresses it there, and the PLC's network carries the data. A direct download from this adapter to the panel is not among the released methods, so the no-connection message means exactly one thing: the panel never answered on the path you gave it. The manufacturer's PC Adapter manual covers installing the software and commissioning the hardware, and it promises programming access, not panel transfers.

Direct transfer or S7 routing #

WinCC flexible reaches the panel by two honest routes:

  • Direct, over a path the panel is released for. A TP177B transfers over USB with a standard A-to-Mini-B cable, or over Ethernet with a fixed address set on the panel. A TP177A has neither port, so for it no direct path from a PC Adapter exists at all.
  • S7 routing, over the bus the panel already shares with the PLC. The adapter taps the segment through a bus connector with a PG socket and the transfer travels the subnet to the panel's station address. The method is the one you use to transfer a WinCC flexible project to an MP277 via S7 routing; only the panel's address and bus values change.

The rule behind both: every panel has released transfer paths and nothing else works, which is the same reason a KTP600 Basic DP needs a PC Adapter USB A2 for transfer on its own generation of hardware.

The wiring that routing needs #

Check the segment before opening any dialog:

  • A PROFIBUS cable runs from the S7-300's DP port to the TP177 through bus connectors. If the machine already links the two, that cable is your transfer path and nothing new gets pulled.
  • At least one bus connector on the segment has a PG socket. The adapter's bus end plugs into that socket; the socket is a parallel tap, so the connector at the PLC or any other node will serve.
  • Termination stays where it belongs: on at the first and last node of the segment, off at every connector in between. Plugging the adapter in at a middle connector changes nothing about that.
  • The adapter adds one tap, not one length: the ends of the segment do not move.

Settings that must agree in three places #

Install the PC Adapter software from the manufacturer's support entry 27062840 before plugging the adapter in; only then does it appear as an interface on the engineering PC. Then work through the three lists, because the transfer connects only when all three agree:

  • On the panel, in its transfer settings: the station address, the baud rate and the interface type of the MPI/PROFIBUS channel. These are the three values the panel side needs, and transfer mode stays enabled until the download ends.
  • On the adapter, in its own configuration: the bus profile and the rate it uses when tapping the segment.
  • In the WinCC flexible transfer dialog: the adapter as the PC interface, the panel's address, and the same rate.

DP segments on these machines commonly run 1.5 Mbps, while MPI networks default to 187.5 kbps, and a panel set to one rate on a bus running the other answers nothing.

Matching a TP177 and a PC Adapter on a 1.5 Mbps PROFIBUS bus #

The case: a TP177 sharing the machine's PROFIBUS segment with an S7-300, a PC Adapter with its software installed, and WinCC flexible 2008 SP3 on the engineering PC.

Inputs, each with its source:

  • Segment baud rate: 1.5 Mbps, the value the S7-300's DP port is configured for. Read it from the PLC's hardware configuration; it is the one value you cannot choose.
  • Panel transfer address: 1, an example station address, entered on the panel and reused in the transfer dialog.
  • The rate the panel may still carry from an earlier MPI setup: 187.5 kbps.
  • Taps on the segment: adapter, PLC and panel, three in total.

The rule in words: the transfer connects only when the panel channel, the adapter profile and the transfer dialog all carry one baud rate and one panel address, with the panel in transfer mode.

The arithmetic: 1.5 Mbps is 1,500 kbps, and 1,500 kbps ÷ 187.5 kbps = 8. The bus clocks eight times faster than a panel left on the old MPI rate listens for, so not one frame decodes and the dialog reports no connection. For termination, three taps on one segment mean two terminating connectors, at the physical ends; the middle connector keeps its switch off even with the adapter sitting in its PG socket.

The result: panel channel on PROFIBUS at the bus rate with address 1, adapter profile at the same rate, dialog on the adapter with the same address. The transfer connects and runs through.

The decision: a single differing value stops the transfer before it starts, so match all three first, every time. With the three matched and the adapter still reaching the PLC but not the panel, the fault sits on the panel side: transfer mode not enabled, or a different address on the panel than in the dialog. If the panel is a TP177B and the segment keeps fighting you, drop the bus and transfer over USB or Ethernet.

When the transfer still fails #

Report Cause Fix
No connection at the first attempt, adapter still goes online with the PLC One of the three settings differs from the bus Set panel, adapter and dialog to the rate and address the segment actually runs
Adapter missing from the interface list Software installed after plugging in, or not installed at all Install the package from support entry 27062840, then reconnect
Transfer starts and breaks partway Termination missing at an end node, or a long noisy run Terminate on at the two end nodes only, move the adapter tap, shorten the cable
Panel never leaves its runtime screen Transfer mode not enabled on the panel Enable transfer on the panel, then start the transfer in WinCC flexible
Everything matched on a TP177B, still nothing The bus path itself Transfer over USB or Ethernet instead

One line for the schedule: from the moment transfer mode starts until the new project loads, the panel shows no runtime screens, so run the download when the operator can work without it.

The decision for each case #

  • Adapter and a TP177A: no direct path exists. Tap the segment through a bus connector with a PG socket, match address, baud rate and interface type in the three places, enable transfer mode, and download by routing.
  • Adapter and a TP177B: take USB or Ethernet for the transfer and keep the adapter for PLC work. Routing still works when reaching the panel's ports is harder than the cable run.
  • No PG-socket connector on the segment: fit one first, ideally at an end node where termination already lives, before attempting anything from the engineering PC.
  • Adapter reaches the PLC but never the panel with everything matched: correct transfer mode or the address on the panel, and leave the bus alone.

Questions asked

Does the panel transfer change anything in the S7-300?

No. A panel transfer writes only the panel's project memory; the PLC's program, data and configuration stay as they are, even when the data travels through the PLC's subnet. When the transfer ends, the panel restarts on its own and loads the new project, so allow a minute for that restart before judging the result.

What station address should the TP177 get?

Any address that is free on that subnet. The PLC and the other nodes keep their own, so pick a number none of them uses, then enter that same number in the panel's transfer channel and in the transfer dialog. The worked case uses 1; choose another number if 1 is already taken on your segment.

Does the transfer need changes in the PLC's network configuration?

Only if the panel is not yet a station there. If the hardware and network configuration already shows the TP177 on the PROFIBUS or MPI subnet, nothing in the PLC changes and the dialog finds the panel by its address. If it is missing, add it to the subnet in the network configuration and download the hardware configuration before transferring.

Can the adapter stay plugged into the PG socket afterwards?

Yes. It sits as one more tap and does not alter termination, so leaving it in place changes nothing on the bus. Most engineers still unplug it after the job, because the PG socket then stays free for programming sessions and the segment carries one node fewer during production.

Keep reading

  • Troubleshooting

    Why a KTP1000 DP WinCC Flexible Download Says No Connection

    A compiled project proves the project, not the transfer path. When WinCC flexible reports that no connection could be established on a KTP1000 DP, set MPI/DP (3) as the transfer mode with the panel's node address, point the S7ONLINE access point at the adapter that is cabled, and give every participant the same MPI rate and a unique station address.

    HMI and touchscreens

  • How-to

    Transfer a WinCC flexible project to an MP277 via S7 routing

    Yes, the engineering PC reaches the CPU 315-2 PN/DP over Ethernet, the CPU forwards the WinCC flexible transfer onto its MPI subnet, and the MP277 receives it at its MPI node address. That takes the CPU's routing configuration compiled and loaded, the panel configured on the MPI subnet, transfer enabled on the panel's MPI/PROFIBUS channel, and the PC's online access bound to its Ethernet adapter. Routing never targets the panel's Ethernet channel.

    HMI and touchscreens

  • Explainer

    Why an HMI second Ethernet port does not route PC Runtime to the PLC

    A WinCC flexible transfer to the HMI's second Ethernet port proves only PC-to-HMI reachability. The two interfaces are separate networks; a PC Runtime reaches the controller through an explicitly configured network route or supported S7 routing, never automatic bridging inside the HMI.

    HMI and touchscreens

Connecting an S5 PLC to WinCC flexible PC runtime