Why a PSR backup cannot open in WinCC flexible 2005

HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

A .psr file is a ProSave restore image, not an editable project, and WinCC flexible 2005 accepts only a ProTool .pdb as conversion input. The OP7 has no route that returns one, so installing ProTool changes nothing. Search the archives for the .pdb; if none exists, rebuild the application as a new OP77B project, taking behavior from the running OP7 and tags from the PLC program.

On this page
  1. A restore image is not a project
  2. Why ProTool cannot upload the missing project
  3. What WinCC flexible 2005 accepts, and what the OP77B needs
  4. Search every archive before you rebuild
  5. Rebuilding the application as a new OP77B project
  6. Cutover with the OP7 as the rollback
  7. The decision for your case
  8. Questions asked

WinCC flexible 2005 refuses the .psr file because that file is a ProSave backup — a restore image for the panel it was taken from — while the only ProTool-era format the engineering tool opens for conversion is a .pdb project database. No cable, no ProTool installation and no renaming changes that: the OP7 holds a compiled runtime image and has no function that hands an editable project back. You have two routes. If a .pdb surfaces in the archives, convert it. If none exists, build a new WinCC flexible project for the OP77B, using the running OP7 as the behavioral specification and the PLC program as the tag source, and keep the .psr as the old panel's recovery file.

A restore image is not a project #

A .pdb is the ProTool project database: screens, tags, messages, texts and the editor metadata needed to change any of them. A .psr is what ProSave reads back from the panel: the compiled image the panel executes, packaged so ProSave can write it onto a panel again. Compilation is a one-way step. It removes or transforms the information an editor needs, so the image can reproduce the machine's screens at runtime but cannot be opened as source.

The extension follows the content, not the other way round. Renaming a .psr to .pdb changes nothing, because the engineering tool reads the file's internal structure and rejects it as a project source. The rejection you saw is a format mismatch, not a corrupted file. The same boundary applies to every panel family — an uploaded copy is a restore image as well, as why an uploaded HMI copy is not an editable project explains.

Why ProTool cannot upload the missing project #

The OP7's documented functions are receive and restore. ProTool compiles a project and transfers it down; ProSave talks to the panel over a serial RS232 cable (from the 6XV1440-2K.. family) and stores a .psr. Source back transfer — returning an editable project from the panel — is not a function the OP7 provides. Installing ProTool therefore gets you an editor with nothing to open: you could only author a brand-new OP7 project and download it, which is the same rebuild you are facing anyway, aimed at the panel you are replacing. Every read path from an OP7 ends in the same restore-only file, so no version of ProSave and no different cable changes the outcome.

What WinCC flexible 2005 accepts, and what the OP77B needs #

When you point the Open dialog of WinCC flexible 2005 at a ProTool-era source, the accepted input is a .pdb; a .psr is not on the list because it is not a project. The conversion produces a native WinCC flexible project, and because the OP7 itself is not a target device in WinCC flexible — its successor there is the OP77B — even the .pdb route ends in a device change: you change the project's target device to the OP77B and recompile. Expect conversion messages for functions the newer system handles differently, and clear every one before transfer. The full sequence is covered in converting a ProTool project to a new touch panel.

Search every archive before you rebuild #

The search typically takes hours; a rebuild takes days, so exhaust the source first. Work through the old engineering PC and its project directories, removable media, the machine documentation or handover package, and any controlled backup system. Search by machine or line identifier as well as by the .pdb extension, because project filenames rarely match equipment names. Open each candidate from a working copy, never from the only archived one, and compare its screen names, texts, tag addresses and machine functions against the running OP7. A .pdb that matches is the migration input. A .pdb that describes a different revision is worse than none: do not convert the wrong revision — keep it as a reference and rebuild instead.

Rebuilding the application as a new OP77B project #

Treat the OP7 application as a functional specification. Before you disturb communications, record every reachable screen, navigation path, displayed value, editable setpoint, alarm text, unit, decimal place and access restriction, across all operator levels and the fault and maintenance states that get forgotten. Count what you record — for example 14 screens, 96 tags and 31 messages — and use the count to prove the rebuild is complete.

The PLC program is the authoritative tag source. For every object, read from the PLC application the address, data type, read or write direction, scaling, limits, and the condition that enables the control. A screen label states an operator intention; the connected operand states what the machine actually does. The object-by-object method in rebuilding a lost HMI project from PLC tags and logic applies directly, and converting an OP7 ProSave backup to an OP77B WinCC flexible project walks the same record-then-build sequence for this exact panel pair.

Then build: create the project with the OP77B as target device, configure communications to match the installed controller and cabling — take protocol and node settings from the controller's hardware configuration and the existing network, since the .psr cannot be read for them — define tags from the verified records, rebuild the screens with the observed formats and limits, and recreate messages with their verified trigger bits.

The scaling check that catches wrong tags #

Say the OP7 shows a dryer temperature of 123.4 °C, and the integer word behind that display reads 1234 in the online PLC program. The transfer factor is the displayed value divided by the raw counts: 123.4 °C ÷ 1234 counts = 0.1 °C per count. Recompute forward: 1234 counts × 0.1 °C per count = 123.4 °C, which matches, so the OP77B tag gets the same address with factor 0.1 and one decimal place. Run the check in the write direction too: an operator entry of 80.0 °C must reach the PLC as 80.0 °C ÷ 0.1 °C per count = 800 counts. If the division does not land on a clean factor, you are reading the wrong word, the wrong data type, or a value with an offset — resolve it before building the tag, because a wrong factor passes every cosmetic check and corrupts every setpoint the operator types.

Cutover with the OP7 as the rollback #

Keep the OP7, its .psr and its cable untouched until the OP77B passes acceptance. Bench-test first, because every command you exercise reaches the real PLC: compile the OP77B project and require zero unresolved references; establish communications and require live values with no stale-quality indications; compare representative values at several normal operating points against the documented OP7 behavior and the online PLC; then test each operator command in a safe machine state and require the intended bit or value to change exactly once, with nothing adjacent moving. If the OP77B must sit on the same MPI bus while the OP7 is still connected, give the panels different node addresses first — an OP7 and OP77B MPI network conflict resolution shows the symptom and the setting to change.

The decision for your case #

  • A matching .pdb exists: convert it in WinCC flexible 2005, change the target device to the OP77B, clear every conversion message, bench-test, cut over. No rebuild needed.
  • Only the .psr exists: no engineering tool turns a .psr into a project, and no upload from the OP7 yields a .pdb. Keep the .psr as the OP7's recovery file and rebuild the application as a new OP77B project from the recorded panel behavior and the PLC program.
  • The file's origin is unclear: identify which tool wrote it — ProTool, ProSave or an archive utility — before trusting the extension, then apply the branch above that fits.

Questions asked

Can the .psr backup be restored into the OP77B?

No. A ProSave backup restores only to the panel type it was taken from, so the file serves the OP7 alone. The OP77B receives its runtime image from WinCC flexible, compiled from a project, and has no function that accepts a .psr. Keep the file with the machine documentation as the rollback path for the old panel.

Do I need a ProTool license for the conversion?

Not for the conversion. WinCC flexible 2005 opens and converts a .pdb with its own integrated converter, and ProTool does not have to be installed on that PC. What you need is the .pdb file itself. ProTool only matters if you want to edit a project that stays on the OP7, which your migration does not.

Will a newer WinCC version open the .psr file?

No. ProSave and backup images stay restore-only in every generation, so a newer engineering tool does not change what the file contains. The migration route into newer software still starts from the ProTool project, normally converted through WinCC flexible first, so the .pdb requirement does not go away with an upgrade.

Is a second ProSave backup of the OP7 worth making?

Yes, for safety, not for editability. A fresh .psr over the serial cable protects you if the old panel fails before cutover, and a test restore in a planned window proves your existing file is valid. Label both backups with the panel serial number and date, and treat them as recovery files only: neither can be opened as a project.

Keep reading

  • Explainer

    Why a PSB Backup Cannot Run in WinCC Flexible PC Runtime

    No. A .psb file is a ProSave device image that restores only to the panel model it came from, and Siemens documents that it cannot be loaded or edited in the engineering tool. To run the application on a PC, open the source .hmi project, change the device type to the PC runtime, recompile and license it.

    HMI and touchscreens

  • How-to

    How to Back Up a Smart 700 IE HMI With ProSave

    Back the Smart 700 IE up with ProSave, the standalone utility in the WinCC flexible 2008 SP4 package: select Smart 700 IE as the device type, set the interface and the panel's Ethernet address, prove the path with a ping, then run Backup into a dated folder. The .psb result restores a panel; it is not the editable project, so keep the WinCC flexible source beside it.

    HMI and touchscreens

  • Explainer

    Why a TP170B Mono backup cannot move to a newer panel

    A TP170B Mono runtime backup restores only to another TP170B Mono and cannot be retargeted to a successor panel. Moving the application to a replacement is an engineering job: open the editable project, the file with the .hmi extension, in WinCC flexible and change the device type to a target that version supports. Establish which file you hold before ordering hardware.

    HMI and touchscreens

Why a C7-626 panel has no ProSave backup or upload route