Explainer
Why a TP170B Mono backup cannot move to a newer panel
Short answer
A TP170B Mono runtime backup restores only to another TP170B Mono and cannot be retargeted to a successor panel. Moving the application to a replacement is an engineering job: open the editable project, the file with the .hmi extension, in WinCC flexible and change the device type to a target that version supports. Establish which file you hold before ordering hardware.
On this page
- A backup and a project are different files
- Why a restore accepts only the same panel type
- Identify the panel and the file first
- The conversion route runs through WinCC flexible
- What the converted project must be checked against
- The decision for each case
- Worked example: counting what the files can recover
- Commissioning: prove the route before retiring the panel
- Questions asked
There is no direct replacement that accepts a TP170B Mono backup. A backup taken from that panel restores only to another panel of the same type, and no transfer setting converts it for a different device. Moving the application to a newer panel is an engineering job: it needs the editable project — the file with the .hmi extension — opened in WinCC flexible, where the device type is changed to a target that version supports and every conversion message is worked through. Before any hardware is ordered, establish which of those two files you actually hold; that single fact decides the entire replacement.
A backup and a project are different files #
The panel stores compiled runtime data, not source code. A backup captures that deployed content as a recovery image, and the vendor's backup and restore documentation ties every such image to the same panel type: it brings an identical unit back, and nothing else. The .hmi project is the other file: the editable engineering source, holding screens, tags, connections and the configured device itself. Only an engineering tool opens it, and only an engineering tool can repoint it at different hardware. Restore utilities, transfer dialogs and card slots all move compiled data between panels; none of them converts anything.
When someone says the program was uploaded from the old HMI, ask what was actually produced. A file copied off the panel is a recovery artifact until the engineering tool proves otherwise, and the test takes a minute: open a working copy in the engineering software. If screens, tags, connections and a device configuration appear, it is a project. If only the backup utility accepts the file, it is not.
Why a restore accepts only the same panel type #
The runtime image is built for one device. Its display properties, operator controls, communication interfaces and runtime functions are compiled against that device, and the restore path checks the target against the source type before it writes anything. A backup carries no field for a different destination panel, so there is nothing for a transfer tool to redirect; selecting a newer model in a transfer utility does not convert the application, it simply fails. That is deliberate. Restore exists to recover a failed unit of the same type quickly and exactly, and an operation that silently rewrote the application for other hardware would not be a recovery tool.
Identify the panel and the file first #
Two identifications come before any purchase order.
The hardware: read the complete order number from the nameplate, digit for digit. This panel circulates under two writings — a shortened form, 6AV545-0BB15-2AX0, and the fuller 6AV6 545 form — and a supplier searching on the short form will find nothing. Give out only what the nameplate shows.
The software: find out whether an editable project exists at all. Search the machine documentation, the electrical drawings and the engineering computers. A replacement panel without recovered source is just new hardware on a door, which is the failure behind why a replacement HMI panel needs the recovered legacy project. While the old panel still runs, record what it shows: screens, alarm texts, tag behavior and the controller connection settings.
The conversion route runs through WinCC flexible #
With the .hmi file in hand, the route is documented. Open a copy of the project in WinCC flexible 2008 SP3, the level the Siemens migration guide uses, and run the "Change device type…" function, then pick a target the installed version still offers. For this generation the documented step is TP170B to TP177B; the Siemens migration guide for the Basic Panels covers the further move to the current KTP Basic line. Which engineering tool programs which panel is a lookup, not a guess — the subject of which HMI software works with which HMI panel hardware.
The conversion recompiles the application for the new device and reports what could not be carried over. Expect manual work on whatever the target does not support; the messages are the work list, not decoration. Every mono-panel migration of that era follows this same source-versus-backup logic, and the OP27 Mono to KP700 engineering migration guide walks one such conversion end to end.
What the converted project must be checked against #
A converted project that compiles is not yet a working replacement. Check four dependencies before the target panel is ordered:
| Dependency | What to compare | Failure if skipped |
|---|---|---|
| Display and operation | Screen size and resolution, object placement, touch targets, navigation | Clipped objects, controls that cannot be reached |
| Controller communication | Connection driver, physical interface (MPI or PROFIBUS on this generation), node address, bus settings | A running HMI showing dead or wrong process data |
| Application functions | The conversion messages against the target's supported function list | Functions silently missing after download |
| Installation | Cut-out and mounting dimensions, supply voltage, connector types | A panel that works logically and does not fit the door |
The communication row deserves extra respect: the interface that reaches the PLC from the old panel has to exist on the new one, or the job includes a network change, not just an HMI change.
The decision for each case #
- You hold the editable project: convert it to an orderable target, fix every conversion message, test, download. The old backup becomes the fallback, nothing more.
- You hold backups only: no conversion exists. A restore works only to a same-type TP170B Mono spare, so either source one of those or accept re-engineering; there is no third option.
- The panel runs and the files are unknown: take a backup immediately, then hunt for the project source while the panel is alive. A successful backup proves recovery data exists; it proves nothing about source.
- Nothing is recoverable: document the running application and rebuild it for a supported panel, with the discipline described in reading an old HMI program before panel replacement. The running panel is the best documentation you will get.
- You would rather leave small panels behind: the same source can be retargeted to a PC runtime device on industrial panel PCs instead of another proprietary terminal.
Worked example: counting what the files can recover #
Illustrative inputs: a plant has four TP170B Mono panels running three different configurations. The engineering archive holds one editable project; the maintenance laptop holds two backup files.
Backups restore only to the same type, so at most two of the four panels have a recovery file: 4 panels − 2 backups = 2 panels with nothing to restore from. Those two get backed up this week, while they still run.
On the conversion side, one project covers one of the three configurations, so 3 configurations − 1 documented = 2 configurations that exist only as compiled runtime data on their panels. Those two can never be converted to a successor; their route is a same-type spare or a rebuild. The decision: convert the documented configuration to the successor now, obtain same-type spares only to keep the undocumented two alive, and budget the rebuild for them.
Commissioning: prove the route before retiring the panel #
Keep the old panel powered and in service until the new route is proven on the bench. Convert a copy, never the last original, and download to the target with the machine in a safe state — an HMI screen carries buttons that write real commands to the PLC, and a freshly converted project is exactly the kind of thing that fires one by accident. Then verify against the controller: the startup screen renders unclipped, live values track the process, alarms behave, and each write does what the old panel did. A completed transfer proves the data arrived; only this test proves the replacement.
Questions asked
Can I rename the backup file to .hmi and open it as a project?
No. The extension is a label, not a format; renaming changes neither the file's internal structure nor its contents, and the engineering tool still refuses it. A backup stays a recovery image for the same panel type no matter what it is called, and the restore utility expects the file under its original name.
How do I confirm my WinCC flexible installation can perform the conversion?
Open the device catalog of the installed version and check two entries: the source panel and the intended target. If either entry is missing, that installation cannot run this conversion. Then check the project version: WinCC flexible opens projects saved by its own version or older, so a project last saved in a newer release needs that newer release installed.
Does a memory-card backup behave differently from a backup made with the utility?
No. Every backup route follows the same-type rule. A SIMATIC HMI memory card from one operator panel restores into any operator panel of the same type, carrying the operating system, the project and the data together. That is why a same-type spare stays valuable even after the panel type is discontinued: it is the only hardware a restore will ever accept.
What should I ask the supplier for when the panel is discontinued?
Ask for two separate things, because they solve different problems. First, whether same-type units are still obtainable, since only those accept a restore. Second, the documented successor for the engineering conversion, together with the current migration guide for that step. A direct-replacement label settles neither question, because the restore route and the conversion route have different answers and only your files decide which one you can use.