How-to
How to Back Up a Smart 700 IE HMI With ProSave
Short answer
Back the Smart 700 IE up with ProSave, the standalone utility in the WinCC flexible 2008 SP4 package: select Smart 700 IE as the device type, set the interface and the panel's Ethernet address, prove the path with a ping, then run Backup into a dated folder. The .psb result restores a panel; it is not the editable project, so keep the WinCC flexible source beside it.

On this page
You do not need to read one Chinese menu to protect this panel. Back it up with ProSave, the standalone service utility that comes with the WinCC flexible 2008 SP4 package: select Smart 700 IE as the device type, point the interface at the PC's Ethernet adapter and the address at the panel's configured IP, prove the path with a ping, then run the Backup operation into a dated folder. The result is a .psb device backup that restores a compatible panel to its saved state. It is not the editable project — that stays archived beside it.
What the backup file is and is not #
ProSave has one job: move HMI data between a panel and a file on the PC. Backup reads from the panel, Restore writes to it, and the procedure is documented under Siemens support entry 18796010 for exactly this panel family. Installed from the same WinCC flexible 2008 SP4 setup as the engineering shell, it opens as its own program and never touches your project.
The file it writes is a device backup. Restored to a compatible HMI, it returns that panel to the state that was saved — what you need when a unit fails or is swapped. It is not engineering source: you cannot open it to change screens, tags or alarms, because a psb backup is not an editable WinCC flexible project. It is not an upload either; ProSave backup versus WinCC flexible backtransfer are different operations with different results.
What to prepare #
- The PC you already used for the install — ProSave was set up with the engineering package on it. The project itself does not need to be open or even present.
- The nameplate identity: Smart 700 IE, order number 6AV6 648-0BC11-3AX0. You will select exactly this device type.
- The panel's IP address and subnet mask, read from the panel's network settings or the machine documentation. Never copy them from the PC and never guess.
- An Ethernet path from the PC to the panel's Ethernet port, direct or through a switch; the software, cable and configuration reference for this panel collects the connection settings for the model.
- A destination folder named for machine and date, for example
D:\HMI_Backups\Smart700IE_2025-01-15.
Setting device, interface and address in a Chinese dialog #
ProSave from a Chinese package can open with Chinese labels, and that is fine: every value you must read or type is Latin script anyway — the model name in the device list, the dotted-quad address, the word Ethernet. Identify the three settings by what they contain, not by translating the labels.
- Start ProSave from its own program entry; it is a separate program, not a menu inside the engineering shell.
- Device type: open the list and pick Smart 700 IE. Model strings are not translated, so the entry reads the same in a Chinese dialog. If the model is not in the list at all, stop: when a panel model is missing from the ProSave device list the panel cannot be addressed, and the installation has to be corrected first.
- Interface: the setting that decides how ProSave reaches the panel. Choose the PC's Ethernet adapter that is cabled to the panel, not a wireless or virtual adapter.
- Address: type the panel's IP address exactly as read in preparation — the panel's, never the PC's own.
- Confirm the settings, then prove the path with the ping test from the worked example below before trusting the connection.
Do not spend the afternoon hunting for a language switch: the menu language is fixed by the edition that was installed, and the sibling Smart package has the same limitation — WinCC flexible Smart V3.2 has no English interface. ProSave needs so few settings that the labels stop mattering once you know which field holds what.
Running the backup #
- Choose a window where the operator can spare the screen for a few minutes, and keep the panel powered and cabled for the whole operation.
- In ProSave, select the Backup operation. Read the button twice: Restore writes to the panel and would overwrite it, and a project transfer installs software. Backup is the only operation you want.
- Point the operation at the dated folder and start it.
- Wait for the completion message. If an error appears, write it down exactly — codes and numerals stay legible even in a Chinese message — and correct the cause it names before rerunning.
- If the transfer is interrupted, start it again from the beginning; there is nothing to resume.
Verifying and storing the result #
- Open the destination folder and confirm the backup file exists with a nonzero size. A completion message without a file is a failed backup.
- Record the panel model, the nameplate order number, the panel address, the date and the source panel in the file record, so a second technician can identify it without you.
- Copy the file to a second controlled location and keep both copies unchanged.
- Store the editable WinCC flexible project beside the backup record, each labeled for its job — source for changes, backup for recovery.
- Where recovery time matters, restore the file once to a compatible spare panel under a maintenance procedure. Existence alone does not prove restorability.
When ProSave will not connect #
- Ping gets no reply: the fault is addressing or cabling, not ProSave. Check the subnet arithmetic from the worked example, the link LEDs at both ends, and that the panel is powered.
- Ping answers but ProSave fails: the device type is wrong or the interface field points at another adapter. Reselect both.
- The model is missing from the device list: the installed ProSave version does not know it. Correct the installation before anything else.
- An error during transfer: note the code, keep the panel powered, fix what the code names, then run the backup again.
Worked example: a PC at 192.168.1.50 backing up a Smart 700 IE #
The inputs:
- Panel: Smart 700 IE, order number 6AV6 648-0BC11-3AX0, from the nameplate — the unit in front of you.
- Panel address: 192.168.1.10 with subnet mask 255.255.255.0 — example values standing in for the address read from the panel's network settings.
- PC address: 192.168.1.50 with the same mask — an example value set on the PC's cabled Ethernet adapter.
- One cable or one switch between the two.
The rule: two IPv4 devices talk directly only when their addresses, with the subnet mask applied, produce the same network address. The standard proof that the path works is an ICMP echo request — a ping — answered by the far end.
The arithmetic:
- PC: 192.168.1.50 AND 255.255.255.0 = 192.168.1.0
- Panel: 192.168.1.10 AND 255.255.255.0 = 192.168.1.0
- 192.168.1.0 = 192.168.1.0, so both sit in one subnet and no router is involved.
The test: from the PC, run ping 192.168.1.10. Four replies with none lost prove the path.
The result: ProSave is set to the cabled adapter and to the panel's address, and Backup runs into the dated folder from the preparation list.
The decision: equal network addresses plus a ping reply — start the backup. Unequal network addresses — say the panel sat at 192.168.2.10, which masks to 192.168.2.0 against the PC's 192.168.1.0 — and ProSave cannot reach the panel: move the PC adapter into the panel's subnet first, repeat the ping, and open ProSave only once it answers.
Questions asked
How do I restore the backup onto a replacement panel later?
Open ProSave, select Smart 700 IE as the device type, connect to the spare panel's address with the same interface setting, and run the Restore operation with the saved file. The backup data are transferred to the HMI and return it to the state that was saved, which is exactly how a replacement unit is brought into service.
Can the panel back itself up to a USB stick or SD card?
That route belongs to the newer units. The operating instructions for Smart 700 IE V4 and V5 list a USB storage device or a micro SD card as a backup and restore route from the panel itself, but it is documented for those versions only. For a 6AV6 648-0BC11-3AX0, the documented route is ProSave from a PC.
Does the backup PC need WinCC flexible installed?
No. Siemens documents ProSave as the convenient option for a centralized backup on a computer that does not have WinCC flexible installed, so a maintenance laptop with ProSave set up is enough. The backup is read from the panel over the network; no engineering project has to be present on the PC.
Can one PC back up several Smart 700 IE panels?
Yes. ProSave addresses one panel at a time, so point the address field at each unit in turn and give every backup its own dated folder. Write the nameplate order number and the panel address into the file record so a later restore goes to the right unit.