Troubleshooting
Why a psb backup is not an editable WinCC flexible project
Short answer
A .psb file is a panel backup made for the restore function, not a project, so the open-project command in WinCC flexible rejects it with the not-a-recognizable-format error every time. Restore the backup with ProSave or the panel's own backup/restore to a panel of the same type. To edit anything, you need the original WinCC flexible project or a retransfer file stored on the panel.

On this page
The dialog is not lying to you. Error on open project with .psb is not a recognizable format in WinCC flexible 2008 SP2 is the project-open function correctly rejecting a file that was never a project: a .psb file is a panel backup, a backup restores only to a panel of the same type, and it is not editable. Your MP 277 8-inch backup belongs in the restore function — ProSave on the PC or the panel's own backup/restore — run over the transfer cable, not from the memory card. If you need to edit screens, tags or connections, only two artifacts can get you there: the original WinCC flexible project from the engineering archive, or a retransfer file stored on the panel when the project was transferred. The sections below show which route applies to your machine and how to run the restore without ending up with a panel that will not start.
What a .psb backup actually holds #
A WinCC flexible project is the source: screens, tags, connection settings, scripts — the file the engineering tool saves and reopens. A panel backup is the deployed state: the runtime application as it sits on the MP 277, captured so it can be restored. Same panel, two different files, two different readers. The open command in WinCC flexible reads only the first kind; the restore function in ProSave or on the panel reads only the second.
That split is why nothing you do to the file converts it. Copying it again, renaming the extension, taking the backup a second time — each produces another restore artifact, never source. The vendor's backup/restore FAQ for Windows-based panels states the rule plainly: a backup restores only to a panel of the same type, backups are not editable, and a retransfer file is the editable artifact.
Two neighboring traps fall under the same rule. A .psb cannot run in a PC runtime either, which is the subject of why a PSB backup cannot run in WinCC flexible PC runtime, and a copy uploaded from a panel is not source either, as why an uploaded HMI copy is not an editable project explains.
Why the project-open command rejects the file #
The open-project function reads only files the engineering tool saved as projects. A .psb comes from the backup side — a ProSave backup or the panel's own backup — and its structure belongs to the restore function and to one panel type. The rejection is the file being recognized as exactly what it is: not a version problem and not a corrupt file. The same bytes the open command rejects will restore a same-type panel without complaint.
Read the two messages from the reported case separately. Error on open project is the open command giving up because the input is a backup. .psb is not a recognizable format says the same thing from the file side. The extension alone does not prove a backup is complete, but this error says nothing about corruption either; the file is simply being fed to the wrong function.
Reading the error: an MP 277 8-inch backup opened in WinCC flexible 2008 SP2 #
Inputs, as reported:
- Panel: MP 277 8-inch; the backup was taken from its runtime.
- File: one
.psbbackup produced by a panel backup operation. - Tool: WinCC flexible 2008 SP2 on the engineering PC.
- Error shown:
Error on open project, then.psb is not a recognizable format. - Missing: the original project, and the panel was never given stored retransfer source.
Rule in words: a file opens in WinCC flexible only if the engineering tool saved it as a project; a .psb answers only to the restore function, and only on a panel of the same type as the source.
The three conditions, evaluated one by one:
- Was the file produced by a backup operation? Yes — a panel backup, not a saved project. The open command rejects it on every PC, at every version, every time.
- Is there a same-type restore target? Yes — an MP 277 8-inch panel in transfer mode accepts this restore.
- Does an original project or a retransfer file exist? No — the project is gone and the panel holds no stored source, as in the reported case.
Result: condition 1 blocks the edit route for this file permanently, while condition 2 keeps the restore route open. The open failure is the file doing its job, not evidence of damage.
Decision: restore the .psb to a same-type MP 277 and keep the machine running. The edit route opens only when condition 3 changes — an original project or a retransfer file actually turns up. Until one does, no tool version or workaround turns this backup into editable screens.
Restoring the backup the supported way #
- Copy the
.psbto the engineering PC and leave the original untouched; restore from the duplicate. - Put the machine in a safe maintenance state first: a restore overwrites the panel's runtime, and the MP 277 is out of the process until the restore completes.
- Connect the configuration computer to the panel over MPI, PROFIBUS or Ethernet; for a serial link, set the parameters under
Project > Transfer > Transfer Settings...before you start. - Run the restore from the backup/restore facility — ProSave on the PC or the panel's own backup/restore — and select the
.psbinside that facility, never through the open command. - Restore to a panel of the same type: an MP 277 8-inch backup goes back onto an MP 277 8-inch panel, not a similar-looking one.
One documented trap to avoid: the vendor support note on MP 277 and Mobile Panel 277 panels that stop running or fail to start after a restore ties that failure to restores performed from the memory card, and states that the backup/restore route through WinCC flexible or ProSave is not affected by this behavior. Run the restore over the cable and leave the card out of it; whether an HMI memory card holds a restorable panel backup covers what the card can and cannot carry. The ProSave flow is the same one that recovers a KTP400 Basic .psb backup with ProSave — different panel, identical restore logic — and the step-by-step MP277 PSB backup and restore guide walks it end to end for this panel family.
The only two files that give you editable screens #
If the restore gets the machine running but you still need to change screens, tags or connections, two artifacts and only two can do it:
- The original project, the file the engineering tool saved when the HMI was built. Search the engineering archive, the commissioning media and the integrator handover before assuming it is gone; if it truly is, how to recover an HMI program when the source file is lost sets out what can and cannot be rebuilt.
- A retransfer file, the transfer function's read-back, where the engineering tool pulls the project, source included, off the panel. It exists only if the project was put on the panel in a form that kept the source retrievable at transfer time. A panel that simply runs an application proves nothing: a plain runtime transfer leaves nothing to pull back. The practical check on your MP 277 is to put the panel into transfer mode, call the retransfer function from the engineering tool, and read what comes back — if it returns nothing editable, the panel holds no source, and repeating the attempt will not change that.
On older OP-series panels the same split appears as ProSave backup versus WinCC flexible backtransfer, and the MP277 restore failures: PSB file versus original project recovery page works through the same distinction for this panel family.
Checks after the restore #
A finished transfer is not a recovered HMI. Verify, in this order:
- Restore result: the facility reports completion with no transfer or compatibility error.
- Startup: the panel reaches its expected startup screen and stays there. A restart loop or a stop at a load error is the documented memory-card-restore failure mode, so treat a repeat as a fault, not a quirk.
- Communications: displayed process values match the controller values, after accounting for configured scaling and display formatting.
- Operator functions: navigation opens the intended screens and controls act on the intended tags, exercised under controlled conditions.
- Source status: record whether an editable project or a retransfer file was found. If not, archive a second copy of the
.psb, because it is the only recovery artifact you have.
Plan the endgame while the restored panel still runs. A backup cannot migrate an application: moving to any newer target is built from source, so the recovered or rebuilt project is the deliverable that matters. If the MP 277 hardware itself is the aging item, the like-for-like fallback is an industrial panel PC running the HMI runtime at the machine instead of the proprietary terminal — but that migration begins with a project, not with this backup.
Questions asked
Can a .psb backup be converted into a WinCC flexible project?
No. WinCC flexible and ProSave offer no conversion: a .psb holds the panel's runtime state for the restore function, not project source. The only editable inputs are the original project file from the engineering archive or a retransfer file stored on the panel. If neither exists, the backup can restore operation to a same-type panel, but the screens stay uneditable.
Can I restore an MP 277 backup to a different panel type or screen size?
No. The vendor rule is that a backup restores only to a panel of the same type it came from, and a matching screen size alone is not identification. An MP 277 8-inch backup belongs on an MP 277 8-inch panel. Moving the application to a different target needs the editable project, which is then compiled and transferred to the new panel.
Does the not-a-recognizable-format error mean the backup is corrupt?
Usually not. That message comes from the project-open function, which can never read a backup. Test the file where it belongs: run a restore from a duplicate copy to a same-type panel. If the restore completes and the panel reaches its startup screen, the backup is usable. If the restore itself fails on a transfer error, the file is damaged or incomplete.
Will a newer WinCC flexible version open the backup?
No. The failure is a file-purpose mismatch, not a version problem. Every WinCC flexible release reads projects with the open command and hands backups to the restore path, so upgrading the engineering tool will not turn a .psb into an editable project. Versions matter for project files, and a version conversion still needs the original source, which a backup never contains.

