Why WinCC Flexible 2008 Closes a Project After an Interrupted Save
Short answer
A save killed in Task Manager leaves the project file internally inconsistent, so WinCC Flexible 2008 reports the unloadable data and closes the project when you acknowledge the error. A control project on the same PC and the failed copy on a second PC separate file damage from an installation fault. Recover from the newest pre-hang backup and accept it only after a save-close-open cycle passes.
On this page
- Why does WinCC Flexible 2008 close the project after you click OK on the error?
- How do you tell a damaged project from a damaged installation?
- Which backup should you open first?
- Should you run the WinCC Flexible repair option?
- Can you copy the screens out of the damaged project?
- Is a Windows restore point a way back?
- How do you recover the project and prove the recovery?
- Questions asked
When WinCC Flexible 2008 is killed in Task Manager during a hung save, the project on disk can be left internally inconsistent: part of the write completed and part did not. On the next open the editor loads what it can, reports the data it cannot read, and closes the project the moment you acknowledge the error. That sequence — save interrupted, error on every open, project closes after OK, same error on a second computer — identifies damage in the saved project copy, not a broken installation. This article gives the two-comparison test that separates the two, the backups worth opening, and a recovery that ends with a verified save-close-open cycle.
Why does WinCC Flexible 2008 close the project after you click OK on the error? #
Because the project on disk is no longer a complete, internally consistent set: the interrupted save wrote only part of its update, and the editor closes the project after the error because it cannot load the data that was left half-written.
A save updates many related objects and references inside the project store. When the process is ended mid-write — Task Manager's End Task on a hung save, a power cut, a hard reset — the stored project holds part of the new state and part of the old. On the next open the editor validates while loading, finds data it cannot resolve, shows the error dialog, and ends the project session when you acknowledge it. That immediate close is also why the screens cannot be copied out: the session that would expose them never survives past the dialog. Stop reopening the only copy, because every attempt that reaches the save path can overwrite more of what survived.
How do you tell a damaged project from a damaged installation? #
Run two comparisons: open a different project on the same computer, then open the failed project on a second computer running the same WinCC Flexible 2008; which of the two fails identifies the faulty component.
Change one variable at a time:
- Protect the failed copy. Run every test on duplicates; the original stays untouched as the record of the last state.
- Test 1, the control project: on the original computer, open a known-good project. If none exists, create a disposable one, save it, close it, and reopen it. A completed save-close-open cycle proves the installation can run the test.
- Test 2, the failed copy: transfer a duplicate to a second computer running the same WinCC Flexible 2008 and open it there.
| What you observe | What it means | Decision |
|---|---|---|
| The control project passes on the original computer; only the interrupted project fails | The fault follows the project data | Recover from backup; leave the installation alone |
| The control project also fails on the original computer | The local installation is suspect | Run the repair option, then repeat the control test |
| The failed copy gives the same error on the second computer | The project copy itself is damaged | Recover from backup on either computer; repair will not rewrite the file |
| The failed copy opens on the second computer | The first installation is suspect | Save a fresh copy there, then test and repair the first computer |
Worked example. Two computers, both running the same WinCC Flexible 2008. Test 1 on computer 1: the control project saves, closes and reopens — pass. Test 2 on computer 2: the failed copy shows the same error and closes after OK — fail. One passing control and one failing copy, two machines out of two, means the fault follows the file. Decision: skip the repair and go to backup recovery, because no installation work on either machine recreates data that was never written.
Which backup should you open first? #
Open the newest backup that already existed before the hung save, and treat any copy made after the failed save as a duplicate of the damage, not a recovery point.
List the available backups in chronological order; their dates establish sequence, not integrity. Expected on the newest candidate: it opens without the error that closes the failed copy and stays open past the dialog stage. If it fails, move to the next older independent backup, and never re-save a copy that fails while you are testing it. Opening is necessary but not sufficient: a copy can load while missing screens or holding outdated objects, so a candidate counts only after content inspection plus a second save-close-open cycle. The article on recovery and backup when an HMI project fails to open orders the same checks for other editors.
Should you run the WinCC Flexible repair option? #
Only when the control project fails on the original computer: the repair replaces missing or damaged application components, and it cannot rebuild project objects that the interrupted save never wrote.
Judge the repair by its effect on the control project, never by assumption — after it runs, the known-good or disposable project must complete a save-close-open cycle on the original computer. If instead the editor closes before any project loads at all, the installation itself is failing at startup, and the fix for an editor that closes right after the splash screen comes before any project test means anything.
Can you copy the screens out of the damaged project? #
Only if the project stays open after you acknowledge the error; when the editor closes it immediately, as it does after this kind of save, there is no session to copy from, and repeated attempts risk overwriting more of the original.
Run the test once, on a duplicate: acknowledge the error and watch the session. If the project stays open, copy the required screens into a new project and test every transferred object — that is selective salvage, not proof the source is healthy. If it closes, stop: the session needed to expose the objects never exists.
Is a Windows restore point a way back? #
No: a restore point rolls back Windows and installed software without supplying a known-good project copy, and it can change the very installation you need for the recovery, so it comes only after every backup and both installation tests have failed.
A restore point can undo updates and settings while the damaged project file stays exactly as it is. Before any rollback, copy every project and every backup outside the rollback scope, or the rollback can take the evidence and the recovery files with it.
How do you recover the project and prove the recovery? #
Recover from the newest backup that opens, rebuild only the work lost since it, and accept the result only after a save-close-open cycle passes on a copy that leaves the source backup untouched.
- Keep the failed project unchanged and run everything below on copies.
- Open the newest independent pre-hang backup. If it errors, take the next older one; never overwrite or re-save a copy that fails.
- Inspect the screens and objects edited in the last engineering session: everything dated before the backup should be present, and only the changes made after the backup and before the hang are missing.
- Recreate that missing work on the copy.
- Save the result under a new name as the recovery copy; the backup that opened stays intact as the rollback point.
- Close the editor normally, reopen the recovery copy, and repeat the inspection.
- Create a fresh backup of the recovery copy only after every check below passes.
What proves the recovery:
- The recovery copy opens without the error that closed the failed project.
- The editor stays open, with the recovered screens accessible and editable.
- The contents match the last state you can verify, including the screens touched in the final session.
- A full save-close-open cycle passes on the recovery copy itself.
When no backup opens at all, the remaining path is reconstruction, and the options for recovering an HMI program when the source file is lost are what is left.
Questions asked
Can a newer WinCC Flexible version or TIA Portal open the damaged project?
Not as a repair. Opening it there runs a migration that reads the same inconsistent data, so the load error usually follows the file, and the conversion can alter the only copy. Keep the failed original untouched, run any migration attempt on a duplicate, and confirm the target version supports your source release first.
Does the HMI panel keep running after the engineering project is damaged?
Yes. The panel runs a separate compiled runtime produced by the last transfer, so the machine keeps operating the version it already holds. Leave the panel alone until the recovered project passes verification: the damaged source cannot generate a replacement runtime, and a new transfer needs a healthy project.
How do you prevent a repeat of this failure?
Keep the working project on a local drive, not a network share or removable media, and save before long compile or transfer steps. Copy the whole project folder to separate media at the end of every engineering session; that habit keeps the newest recovery point at most one working session old.
Where should recovery backups be stored?
On storage the engineering PC cannot take down: a second physical drive, a network share, or both. A failing system disk, a rollback, or the same interrupted write that damaged the project can then not destroy the backups with it. Keep the failed project and the backup that opened as separate, clearly named copies until verification ends.