Why WinCC Flexible 2007 Cannot Open a 2008 Project

HMI and touchscreens Published 5 min read

Short answer

WinCC flexible is forward-only: a project saved in 2008 will not open in the 2007 tool, and no service pack or file trick changes that. The documented fix is Save As Version in WinCC flexible 2008, which writes a 2007-format Project.hmi with its Project_log.LDF; on Windows XP Professional SP3, installing 2008 is documented and removes the problem entirely.

On this page
  1. Why the 2007 tool refuses the file
  2. The documented path: Save As Version in 2008
  3. Why the two files travel together
  4. The XP SP3 machine you already have
  5. What will not work
  6. If 2007 is not the real goal
  7. The decision for each case
  8. Questions asked

WinCC flexible reads forward only, and that is the whole answer: a project last saved in WinCC flexible 2008 will not open in WinCC flexible 2007, no matter which service packs either side carries. The one documented route back is Save As Version in the 2008 tool, which writes a 2007-format copy of the project. Your second option is to move the tool forward instead of the project: Windows XP Professional SP3 is documented for WinCC flexible 2007 or higher, so the same XP machine you are using now can take the 2008 installation and open the file natively.

Why the 2007 tool refuses the file #

Every WinCC flexible project carries its format version internally, and the engineering tool checks that stamp before it loads anything else. The rule the tool applies is one-directional: a version opens projects saved by itself and by earlier versions, and refuses anything saved later. WinCC flexible 2008 changed the project format in ways 2007 has no code to parse, so the open stops at the stamp check and you get a load error.

This is why having both project files does not help here. The file-set check, meaning whether the project archive and its change-log database are present, is a separate concern from the version stamp. A complete, undamaged 2008 project still fails in 2007; the files are fine and the format is not.

The distinction matters for diagnosis. If the error names a newer version, it is the forward-only rule and the fix is a downgrade or a newer tool. If the error says nothing about versions and fails even between two identical installations, the file pair is incomplete or damaged, and the fix is a clean copy of the whole project folder.

The documented path: Save As Version in 2008 #

Only a WinCC flexible 2008 station can write the 2007-format file. The 2007 tool cannot reverse-read the format, so the downgrade happens where the project was last saved:

  1. Get the project back from whoever saved it in 2008, or get access to any station running WinCC flexible 2008. Work on a copy; never downgrade the only source.
  2. Open the project in 2008 and let it finish loading.
  3. On the Project menu, choose Save As Version.
  4. Select the WinCC flexible 2007 format, and give the downgraded copy its own name and its own folder so the 2008 original survives untouched.
  5. Confirm the new folder holds both Project.hmi and Project_log.LDF, and that both files are non-empty.
  6. Move the entire folder to the 2007 station.
  7. Open the copy in 2007, run a full compile, and open one screen, one tag and one alarm from each area of the project. A compile with zero errors and objects that resolve means the downgrade took.

Why the two files travel together #

A WinCC flexible project is not a single file. Project.hmi is the archive you open; Project_log.LDF is the change-log database that belongs to it. The tool needs both in the same folder to open the project, which is why a project received as only the .hmi file fails even between two machines running the same version.

The consequence for everyday work is simple: copy, compress and send the whole project folder, never a picked file. Renaming either file or moving one out of the folder produces the same cannot-open failure as a version mismatch, and no rename puts it right.

The XP SP3 machine you already have #

Your station runs Windows XP Professional SP3. The vendor's compatibility list pairs that platform with WinCC flexible 2007 or higher, and 2008 falls inside that line, so the machine that refuses the 2008 project today is a machine the 2008 tool supports.

That makes the decision straightforward. If you control the station, install WinCC flexible 2008 on it and open the project directly; the downgrade to 2007 becomes unnecessary. Keep 2007 only if another station or another engineer must edit in 2007, and give them the downgraded copy that Save As Version produced. Installing 2008 beside 2007 does not teach the 2007 installation to read 2008 files.

What will not work #

  • Renaming the file extension: the format version lives inside the archive, not in the file name, so a rename changes nothing the tool checks.
  • Editing the version stamp: altering the project header corrupts the archive and turns a clean version mismatch into a damaged project.
  • Collecting both files onto the 2007 station: the file pair was never the problem in this case, and a complete pair still fails the version check.
  • Asking TIA Portal to write a 2007 file: the migration into TIA Portal is one-way and produces no WinCC flexible project on the way back.

If 2007 is not the real goal #

If the point is simply to keep editing, the forward paths are better documented than the backward one. TIA Portal migrates WinCC flexible 2008 projects, with the migration option enabled when TIA Portal is installed, and the walkthrough in how to migrate a WinCC flexible project to TIA Portal covers that end to end. If the panel hardware is the constraint rather than the tool version, the article on running a WinCC flexible 2008 project in PC runtime shows how the same project runs on a PC instead of a panel, with no downgrade involved.

The decision for each case #

  • A project saved in WinCC flexible 2008, and you only have 2007: it will not open, by design. Plan around it instead of fighting it.
  • You can reach a 2008 station: run Save As Version to the 2007 format there, on a copy, and move the whole folder back with both files in it.
  • You control your Windows XP Professional SP3 station: install WinCC flexible 2008 on it, which the compatibility list supports, and open the project natively. This is the cleanest fix because nothing is converted.
  • Neither 2007 nor 2008 is the long-term home: migrate forward to TIA Portal. A 2007 source resaves in 2008 first, then migrates; the move from there is one-way, so keep the WinCC flexible original archived.

Questions asked

Can WinCC flexible 2007 and 2008 sit on the same computer?

Installing 2008 gives that computer the tool that reads the 2008 format; it does not teach the 2007 installation anything, so edits still happen in 2008. Windows XP Professional SP3 is documented for WinCC flexible 2007 or higher, which covers the 2008 installation. If other engineers must stay on 2007, hand them the copy that Save As Version produces and keep the 2008 original as the source.

I received only the .hmi file. Can I open it?

Not reliably. The tool needs Project_log.LDF, the change-log database, in the same folder as the archive before it will open the project, and a missing one fails even between two machines running the same version. Ask for the complete project folder again, sent as a single archive so the file pair cannot be separated in transit.

Does the downgrade to 2007 lose project content?

The 2008 tool rebuilds the project database when it writes the 2007-format copy, so verify rather than assume: open the downgraded copy in 2007, run a full compile and require zero errors, then open a screen, a tag and an alarm from each area of the project. If an object fails to resolve, that feature did not survive the step back to the 2007 format.

Keep reading

  • Troubleshooting

    Why ProTool Lite Cannot Open a TP270 Project It Does Not Support

    A TP270 project that will not open in ProTool is blocked by the editor edition: ProTool Lite does not support the TP270 target. Installing the full ProTool edition, reported working at version 6.0, opens the project before any PLC or transfer diagnosis is needed.

    HMI and touchscreens

  • Explainer

    Can You Migrate a WinCC 7.2 Project to WinCC Flexible

    No migration path converts a WinCC 7.2 project into WinCC flexible 2008; Siemens documents the two as architecturally incompatible, and the documented directions run the other way - WinCC flexible into TIA Portal, and WinCC 7.2 up to WinCC V7.5. Treat the MP 377 12-inch Touch application as a new WinCC flexible project: inventory every function, rebuild it item by item, and verify each one on the bench.

    HMI and touchscreens

  • How-to

    How to Migrate a ProTool HMI Project to a New Touch Panel

    A discontinued ProTool-era panel is replaceable without a rewrite only when the editable project file exists: migrate it under WinCC flexible 2008 with Service Pack 2, Advanced edition for ProTool Pro projects, then review every conversion message and adapt tags and screens for the chosen target. Without the .ptp file, budget the job as a rebuild.