MP377 frozen startup screen: recovery after an interrupted transfer

HMI and touchscreens Published 7 min read

Short answer

When power drops during an MP377 project transfer, storage can end up incomplete and the panel hangs at the startup screen without loading its network or transfer services, so ping, ProSave and WinCC flexible all fail. The documented recovery is an operating system update with Reset to factory settings over the panel's recovery connection; a failed ping does not prove the loader is dead, and no project download will land until the OS is rewritten.

On this page
  1. Why a cut transfer freezes the panel before its network starts
  2. Checks to run before any recovery attempt
  3. What ping, ProSave and a failed restore actually prove
  4. The recovery branch: OS update with Reset to factory settings
  5. Working this case: no ping, no ProSave, no restore on 6AV6644-0AA01-2AX0
  6. Bringing the panel back after the reload
  7. When the panel goes to repair
  8. Questions asked

An MP377 frozen on its startup screen after power failed during a project transfer is not proven dead, and another project download will not fix it. The interrupted write left the panel's storage inconsistent, so the services that apply the network address and accept transfers never load — which is exactly why ping, ProSave, WinCC flexible and a backup restore all stay silent. The documented recovery is an operating system update run with the option Reset to factory settings, started from the engineering tool with the image for the panel's exact order number. A failed ping proves nothing about the loader, because the loader sits below the layer that configures the address you are pinging. Run the checks below in order; the worked case shows how the decision falls.

Why a cut transfer freezes the panel before its network starts #

A project transfer writes application data — screens, tags and runtime configuration — to the panel's storage; an OS update writes the system software underneath it. Power that fails while either write is running can leave persistent storage incomplete, so on the next start the runtime, the network configuration and the transfer service fail to load, and the display stops at the startup screen. That frozen picture tells you the boot did not finish; it does not tell you which layer failed.

Every recovery tool you have talks to a service inside the layer that did not load, except the OS update, which begins from its own handshake. A panel that boots far enough to check its data reports a damaged image instead of freezing; that is the corrupted-image branch described in Why an MP 377 shows image is corrupted after a power loss, and it is not this fault.

Checks to run before any recovery attempt #

  1. Measure the supply at the panel's own terminals while it starts, not only at the power supply output. Expected result: the voltage holds inside the nameplate range for the whole startup. Voltage dropped across wiring or a loose terminal stalls boots that look like software faults; correct that first, or every recovery attempt tests the wrong thing. The measurement is live, so use insulated probes and touch nothing but the terminal block with them.
  2. Power-cycle once, under control, and record the behavior. A reboot loop sends you back to power quality and hardware; a panel that holds the same frozen screen, as this one does, goes to the recovery branch.
  3. Check the physical link: link LEDs at both the panel port and the PC, over a direct cable or an isolated switch. No LED means cable, connector or port — fix that before any software step.
  4. Confirm which network adapter the recovery tool will use: the one physically cabled to the panel, not the plant or office network. A wrong adapter selection defeats the attempt even with a good cable and the right image.
  5. Stop uncontrolled power cycling from here on. Repeated on-off attempts are not a repair method, and each one tests nothing.

What ping, ProSave and a failed restore actually prove #

Ping needs the runtime's IP configuration applied; ProSave and the WinCC flexible transfer need the panel's transfer service; a restore needs a working transfer session before it can begin. All three depend on the OS layer that never loaded, so their silence is the expected result and adds no evidence about the loader. The reverse case — a panel that answers ping while the download still fails — is a different fault with its own path, covered in Why an HMI Is Detected but Project Download Fails.

Observation What it rules in or out Next step
No ping at the former address The layer that applies the address is down; NIC and loader remain untested Verify link and adapter, then take the OS-update branch
ProSave: no response The transfer service is not running OS update with the factory-reset option
WinCC flexible transfer will not start Same blocked service; a repeated download cannot land Do not retry the download
Backup restore does not start Restore also needs a working session Recover the OS first, restore afterwards
Link LEDs dark at either end Cable, port or panel connector Fix the physical link before any software step

The recovery branch: OS update with Reset to factory settings #

The documented route is the Siemens procedure for SIMATIC HMI operating system updates (support entry 19701610, which includes the WinCC flexible variant): start an OS update, select Reset to factory settings, and let the progress run — it is shown both in the tool and on the panel.

  1. Identify the panel exactly from its label: here the order number is 6AV6644-0AA01-2AX0, an MP 377 12-inch Touch. Never pick an image by screen size; visually similar panels take different system software.
  2. Match the image to that variant and to the WinCC flexible version installed on the engineering computer, using the OS-update document for your release. Image, target and engineering tool are three separate checks.
  3. Obtain the image only through Siemens support for that order number or through your installed engineering software's resources. A file described merely as MP377 firmware identifies nothing.
  4. Accept that the operation is destructive: it rewrites the system software to a usable baseline and keeps nothing of the loaded application. Project source and ProSave backups stay on the engineering computer.
  5. Connect over the verified direct link, select the exact panel type, the matching image and Reset to factory settings in the tool, then start the update.
  6. Use SD-card or USB recovery only if the documentation for this exact model specifies it, with its required media preparation; copying an image onto removable media does not create a bootable recovery medium.

Working this case: no ping, no ProSave, no restore on 6AV6644-0AA01-2AX0 #

The inputs, each from the failed unit or the attempts already made on it:

  • Power failed during a project transfer — the triggering event.
  • Panel: MP 377 12-inch Touch, order number 6AV6644-0AA01-2AX0 from the label.
  • Frozen startup screen; the runtime never appears.
  • ProSave over Ethernet: no response. WinCC flexible transfer: no response. Backup restore: transfer does not start. Ping to the assigned address: no response.
  • Supply at the terminals inside the nameplate range throughout startup — the first check passed, and the panel holding its screen instead of rebooting agrees with that reading.

The rule, in words: a service that answers proves the OS layer above the loader is alive, and each silent test removes one candidate layer. Nothing among these tests reaches the loader itself; only the OS-update handshake does.

The arithmetic:

  • Communication tests run: 4 (ping, ProSave, WinCC flexible transfer, backup restore).
  • Tests that answered: 0 of 4.
  • Layers confirmed alive by those results: none — the runtime application, the network configuration and the transfer service all sit in the OS layer that did not load.
  • Layers still untested: the loader, and the OS image held in storage.

Result: 0 of 4 answering leaves no path for a project download or a restore to land on, so both stay closed. The recovery to run is the OS update with the factory-reset option, using the matching image over the verified direct link.

Decision, with its threshold: start the OS update. If the handshake appears and progress runs in the tool and on the panel, the loader is alive — let the update finish, then reload the project as the next section shows. If no handshake appears at all over the verified link, with the confirmed image and the correct adapter, the fault lies below the software, in storage or on the board, and the panel goes to repair or replacement.

Bringing the panel back after the reload #

  1. Let the update run to its end without touching power; interrupting this write repeats the original fault.
  2. The panel now starts on factory defaults, so set its interface address again before anything tries to reach it.
  3. Open the transfer connection in WinCC flexible under Project > Transfer > Transfer settings, put the panel in transfer mode, and download the project from the engineering source — or restore the earlier ProSave backup, which now has a working session to land on.
  4. Prove the result the way any commissioning does: tags update, a controlled restart brings the runtime back, and a second transfer succeeds.

When the panel goes to repair #

If the OS update never shows a handshake over a verified direct link with the confirmed image, or starts but fails at the same point every time, the fault is in storage or on the board and no software route reaches it — the panel goes to the vendor's repair service. When a repair stops being worth it on a panel of this generation, the operator station can move to industrial panel PCs running a PC-based HMI runtime at the machine.

Questions asked

Where do I get the OS image for order number 6AV6644-0AA01-2AX0?

Have three things ready before you search: the order number from the label, the hardware identification printed beside it, and the version of WinCC flexible installed on the engineering computer. The OS-update document for your release names the matching package, and Siemens support for that order number is the distribution route to use. A file shared without that provenance is not something to write into a panel.

Will Reset to factory settings erase the project on the panel?

Yes. The option rewrites the operating system to its factory baseline and keeps nothing of the loaded application, so treat the panel's contents as lost from the moment you confirm. Nothing needs to stay lost, though: the project source and any ProSave backups live on the engineering computer, and you reload or restore them as soon as the panel accepts transfers again.

How is this different from an MP 377 that reports a corrupted image after a power loss?

That panel boots far enough to check its data and report the damage, so parts of its system software and diagnostics are alive and its own recovery procedure applies. A panel frozen before its network starts never gets that far, which is why the corrupted-image procedures do not apply here and the factory-reset OS update is the branch to take.

The OS update will not connect either. What now?

Re-verify the two details that silently defeat it: the network adapter the recovery tool is set to use, and the physical link on a direct cable to the panel. If the handshake still never appears, with the confirmed image for your exact variant, the fault is below the software, in storage or on the board, and the panel goes to repair rather than through more recovery attempts.

Keep reading

  • Troubleshooting

    TP177B color PN/DP OS update fails: version set and image fix

    The transfer is refused because the project, the engineering version and the panel image are not a compatible set. Install Hotfix 7 for WinCC flexible 2005 SP1, which supplies the TP177B image and downgrades the panel to it, or keep the panel's newer version with at least WinCC flexible 2008 SP1; then convert the project from TP177B mono to TP177B color PN/DP and transfer over MPI.

    HMI and touchscreens

  • Troubleshooting

    Why HMI Variable Values Reset After a Project Transfer

    HMI values reset after a transfer because the transfer's Initialize settings requested it, the variables were never marked retentive, or the editor's newer version forced a firmware update that initializes all variable memory. Clear [Variable Value] and [Backup Memory] under Initialize, mark operator values retentive, and retrieve the program plus current values with Shift + X before you transfer. Only the firmware-update path wipes retentive values; capture them first, because no setting protects them through it.

    HMI and touchscreens

  • Troubleshooting

    How to identify an MP377 panel in WinCC Flexible 2008 runtime

    On an MP377 running XP Embedded you can read the Windows computer name at startup with WScript.Shell and ExpandEnvironmentString. On CE Embedded there is no shell access, so give each panel a distinct Project ID or UserVersion area pointer and hold restrictive behavior until that value is valid.

    HMI and touchscreens

Recovering a PanelView 300 Micro Stuck at the v04.41 Splash