TP177B color PN/DP OS update fails: version set and image fix
Short answer
The transfer is refused because the project, the engineering version and the panel image are not a compatible set. Install Hotfix 7 for WinCC flexible 2005 SP1, which supplies the TP177B image and downgrades the panel to it, or keep the panel's newer version with at least WinCC flexible 2008 SP1; then convert the project from TP177B mono to TP177B color PN/DP and transfer over MPI.
On this page
- Why the file alarm appears before any image selection
- Match the engineering version to the image the panel must keep
- Version check for a panel at V01.01.02.0_1.67 against image V1_0_1_7
- Convert the project from the mono device to the color device
- Align the transfer channel at both ends
- Load the OS image, then the project
- Questions asked
The transfer is refused because the project, the engineering version and the panel image are not a compatible set — and the alarm The System Cannot Find The File Specified in the Output Alarm Summary means WinCC flexible has no image for this panel on the engineering PC at all. Two repairs work: install Hotfix 7 for WinCC flexible 2005 SP1, which puts the TP177B image into the images folder and downgrades the panel to the version that image carries, or keep the panel's newer version by moving to at least WinCC flexible 2008 SP1. Either way, the project then has to be device-converted from TP177B mono to TP177B color PN/DP before it transfers over MPI.
Why the file alarm appears before any image selection #
The alarm fires the moment Project > Transfer > OS Update is selected, before WinCC flexible asks for an img file. That order identifies the fault: the engineering software looks up its installed image catalog for the selected device type first, and the lookup comes back empty. Nothing has reached the cable yet, so communication settings cannot fix it.
For WinCC flexible 2005 SP1 that catalog is the folder Program files\Siemens\WinCC flexible\images, and the TP177B family entry is identified as Mobile_OP_TP177B. Hotfix 7 is what installs it; the base installation alone leaves the folder without this panel's image. Do not substitute an image from another device family — the image package has to match the selected operator panel.
Keep the two fault domains apart:
The System Cannot Find The File Specified, immediately on selecting the command: a local image lookup that failed. Fix the software installation.- A timeout or unreachable-device result after the image selection: the lookup passed and the channel is engaged. Chase the adapter, cabling, address and transfer mode instead.
Match the engineering version to the image the panel must keep #
Decide by the image that has to stay on the panel, not by whatever starts a transfer. This version-set check belongs in the software audit done before a replacement panel is ordered; the general procedure is in checking HMI engineering software before a panel replacement.
| Goal | Engineering version | What happens to the panel |
|---|---|---|
| Stay in the 2005 project environment | WinCC flexible 2005 SP1 with Hotfix 7 | Loaded with the hotfix's image, a lower version than it shipped with |
Keep the installed version V01.01.02.0_1.67 |
At least WinCC flexible 2008 SP1 | No image change; do not load the hotfix image just to make the transfer start |
| Move the project to 2008 | WinCC flexible 2008, at least SP1 for this panel | Opening the project migrates it automatically to the installed version |
For one replacement panel on an existing 2005 SP1 project, take the hotfix path: the lower image is the one that project was engineered for. Move to 2008 SP1 when the panel's shipped version must be kept or the migration was planned anyway.
Version check for a panel at V01.01.02.0_1.67 against image V1_0_1_7 #
Inputs:
- Panel's displayed version:
V01.01.02.0_1.67, read from the replacement panel's own properties display. - Image version listed in the Hotfix 7 readme:
V1_0_1_7. - Installed engineering software: WinCC flexible 2005 SP1, before the hotfix.
The rule in words: an image version is an ordered set of numeric fields. Compare field by field from the left; the first field that differs tells you which version is higher. An OS update installs whichever image you select, so choosing the lower one is a downgrade.
The arithmetic:
V01.01.02.0gives the fields 01 | 01 | 02 | 00V1_0_1_7gives the fields 01 | 00 | 01 | 07- Field 1: 01 = 01, a tie. Field 2: 01 > 00 — the panel's installed version is the newer one.
Result: loading the hotfix image takes the panel from 01.01.02.0 down to 01.00.01.07. That downgrade is the expected result of pairing this panel with Hotfix 7, not a malfunction.
Decision:
- If the panel must keep its installed version, stop before touching it: install at least WinCC flexible 2008 SP1 and migrate the project instead.
- If the project stays on 2005 SP1, accept the downgrade, load the hotfix image, and confirm the restarted panel reports the hotfix image's version before the project download.
Convert the project from the mono device to the color device #
An OS update changes the panel's runtime; it does not change the project's configured target. The original project targets TP177B mono and the replacement is a TP177B color PN/DP, so the engineering system has to convert the project.
- Copy the original project and work on the copy — a project saved by a later version is a new revision, and the recover-first habit is laid out in HMI replacement: recover the project before converting.
- On the 2008 path, open the copy, let WinCC flexible migrate it automatically to the installed version, and save it as the migrated revision.
- Run the device change in WinCC flexible and select TP177B color PN/DP as the new target; the project is converted to the color device.
- Work through everything the conversion reports as unavailable on the new target, then inspect the screens: fonts, colors, object placement, alarm views, recipes and communication connections. Layout built for a mono display is not automatically right in color.
- Compile the converted project. A clean compile is the gate to any transfer.
Align the transfer channel at both ends #
The PC side is set under Project > Transfer > Communication Settings. Those entries are only a request — the panel has to be placed in transfer mode with the same channel and the same address, and the PC interface must be the one wired to that network.
| Item | Engineering setting | Panel-side check |
|---|---|---|
| Device type | TP177B color PN/DP | The hardware is that model |
| Channel | MPI | MPI transfer enabled in the panel's transfer settings |
| Device address | 5 | Panel set to the same address; no other station on the segment uses it |
The settings above are the ones from the failing case, with MPI and address 5; set both ends to whatever the panel's own configuration shows. A local file error fires before any of this matters, a timeout fires after it — only the second is a channel problem.
Load the OS image, then the project #
Take the station out of service first: the panel can neither display nor control anything while the image loads. Keep power and the transfer link undisturbed from the start of the load until the restart.
- Put the panel into transfer mode for an OS update.
- In WinCC flexible, confirm the device type, channel and address from the communication settings.
- Select
Project > Transfer > OS Updateand pick theMobile_OP_TP177Bimage that belongs to the installed engineering version. - Start the transfer and leave the panel untouched until it restarts.
- Read the version the restarted panel reports — it must belong to the image just loaded — then download the compiled project.
Verify end to end: a completed download proves file transport only. Check that tags update from the controller, alarms trigger and acknowledge, and every converted screen behaves. If the transfer now starts but fails with a different alarm, the fault has moved into the transfer stage; one such case on another operator panel is covered in MP277 OS update fails with not enough memory on the destination device.
Questions asked
Does installing Hotfix 7 change the WinCC flexible 2005 SP1 license?
No. The authorization already held for WinCC flexible 2005 SP1 stays exactly as it is; the hotfix needs no separate or different license, and neither does the panel image it installs. Install the hotfix over the existing 2005 SP1 installation and keep the current authorization untouched.
Is ProTool needed for the OS update?
No. The TP177B image comes from the WinCC flexible installation, not from ProTool, so ProTool plays no part in an OS update. If the ProTool shortcut starts searching for missing files, that ProTool installation is damaged or absent. Reinstall ProTool after WinCC flexible only when older ProTool projects still have to be opened.
Where should the image file come from?
Only from the engineering software's own hotfix or service pack, or from the manufacturer's official image downloads for HMI operator panels. Do not take an img file from an unofficial file-sharing source. If the images folder stays empty after the correct hotfix, reinstall the hotfix rather than hunting for a loose file.
Does the OS update erase the project already on the panel?
Treat it as yes. The image load replaces the runtime system and takes the stored project and panel-resident data such as recipes and logs with it. Record the displayed version and back up anything still retrievable before starting, and expect to download the converted project afterwards as a matter of course.
The OS update worked but the project transfer still reports a version difference. What now?
Recompile the converted project in the same engineering version that supplied the image, then transfer again; the download matches the project's target against the panel, so a project prepared under a different version is refused. If both sides agree and the refusal persists, confirm the device type selected in the communication settings is the color PN/DP and not the old mono panel.