Explainer
OP270 upload: ProSave backup versus WinCC flexible backtransfer
Short answer
A ProSave backup of an OP270 is a binary image that restores only to the same panel type and never opens as an editable project. The only route to editable source from the panel is WinCC flexible backtransfer, and it works only if Enable backtransfer was selected before the project was transferred. Without that stored data, the decision is to locate the archived project or rebuild.

On this page
Upload means two different operations on an OP270, and they produce two different things. A ProSave backup copies the panel as a binary image: it restores to the same panel type and it never opens as an editable project. WinCC flexible can retrieve an editable project from the panel only through backtransfer, and only when the option that stores the engineering data was active before the project was transferred. This article gives both procedures, the precondition that decides which one is open to you, and the decision when neither produces source.
Two operations that both get called upload #
ProSave and WinCC flexible retrieve different data from the same panel. ProSave reads the deployed runtime image and the panel data and writes a backup whose only job is restoration. WinCC flexible backtransfer reads engineering data — screens, tags, alarms and connections as editable objects — that was written onto the panel during the original download. A running application on the OP270 proves that runtime data exists on the panel; it proves nothing about engineering data, which is the trap explained in why an uploaded HMI copy is not an editable project. So decide the goal first: restoring a failed or replaced panel needs the image; changing anything on a running machine needs the project.
The precondition stored on the panel #
Backtransfer data is not extracted from the running application. It exists on the OP270 only if Enable backtransfer was selected in the transfer settings of the WinCC flexible project before the last download. With the option active, the transfer writes a compressed copy of the engineering data into the panel's application memory alongside the runtime. With it off, nothing was written, and no cable change, repeated ProSave run or file rename will create it afterwards. That dependency on a stored payload is the same one that blocks recovery in TP177B backtransfer and the missing PDZ file. For your panel the test is the upload attempt itself: it settles the question in minutes. Plan it for a window in which the operator station can pause, because the panel must enter Transfer mode for the session.
The transfer path both operations share #
Both tools reach the OP270 the same way: through the transfer channel configured on the panel, a matching cable or adapter at the computer, and the panel in Transfer mode. Where the software asks for a device type, select the OP270 — in ProSave's device list and again in WinCC flexible — so the tool addresses your panel rather than a stand-in. A mismatched path fails at the connection, before any data question, and it disguises itself as missing project data because the transfer never starts. If the OP270 does not appear in the device list at all, the installed tool is missing the matching support, a problem covered in when a panel model is missing from the ProSave device list. Before touching anything, record the panel's current transfer settings; a station running production should not be reconfigured to chase a connection.
Backing up the OP270 with ProSave #
Take this backup first whatever the final goal is, because the image is the rollback for every later step.
- Connect over the transfer path and select the OP270 as the device type.
- Run the backup and choose a destination you control, not a temporary folder.
- Put the panel into Transfer mode when prompted and let the backup run to the completion message.
- Confirm the file exists and is not empty, then store the original read-only with the panel type and the date recorded.
The result protects operation only: it restores to the same panel type and it is never a project. Treat a completed backup as a restoration artifact, not as proof that modifications are possible.
Recovering the project with backtransfer #
- Use the transfer path already proven by the ProSave run.
- Start the upload from WinCC flexible with the panel in Transfer mode.
- If the stored data is present, the upload completes and the retrieved data opens as a project; save it under a new name so the archive name stays free.
- Compile the recovered project unchanged. A clean compile, with every screen, tag, alarm and connection visible as an editable object, is the acceptance test for the baseline. Only then begin modifying.
If the panel reports that no retransfer data exists, stop: the source is not on the panel and the next section applies.
The decision when no source comes back #
| Result on the bench | What it establishes | The decision |
|---|---|---|
| ProSave backup completes | A restorable image exists | Archive it read-only; it protects restoration, not modification |
| Backtransfer completes and compiles | Engineering data was stored at the last download | Version the recovered project; it is the new source baseline |
| Backtransfer reports no data | The runtime holds no engineering source | Locate the archived project or rebuild the application |
| Neither tool connects | Nothing about data yet | Correct device type, channel, cable and Transfer mode first |
For the archive search, look where the project was engineered: workstations, removable media and controlled backups, expecting a file set that opens as screens and objects rather than an image. For a rebuild, document the running panel first — every screen, the navigation, alarms, recipes, tag addresses and the controller connection — then build the new project beside the working panel. Do not overwrite the OP270 runtime until the replacement is fully tested and a ProSave image of the current state is secured. Keep the recovered or rebuilt source under version control from then on; it is also what any later hardware change depends on, as why a replacement HMI panel needs the recovered legacy project sets out.
Questions asked
Can I turn on backtransfer for the OP270 now, after the project is already running?
Not without the source. The option is selected in the transfer settings of the WinCC flexible project, and the data is written during a download, so enabling it requires the very project you are trying to recover. Someone must transfer a project with the option active before the panel carries retrievable data. A running panel cannot generate that data from its own runtime.
What does ProSave actually write, and can WinCC flexible import that file?
ProSave writes an image file with the .psb extension, and only ProSave reads it. WinCC flexible has no import for the format, and renaming or repacking the file changes nothing. The only panel content that WinCC flexible can turn into a project is the backtransfer data written during a transfer.
How do I know in advance whether the OP270 holds backtransfer data?
You cannot tell from the running application; the upload attempt is the test. When no data was stored, WinCC flexible reports that there is nothing to upload and offers no project to save. When data is present, the upload runs to completion and the result opens as a project with screens, tags and connections visible as editable objects. Schedule the attempt for a window in which the station can pause.
Can a ProSave run prove the connection before the WinCC flexible upload?
Yes, and it is the fastest order of work. A completed ProSave backup proves the channel, cable, adapter and Transfer mode all match, and it leaves you the rollback image at the same time. Then start the WinCC flexible upload over the same path. If that session fails after ProSave succeeded, compare the device type and connection selected in WinCC flexible with the ones ProSave used.