IMDTouchKnowledge BaseShop main store

Troubleshooting

When a panel model is missing from the ProSave device list

HMI and touchscreens Published 6 min read

Short answer

A missing device type and a failed connection are two separate faults. The installed ProSave v9.0.3.0 has no profile for the SMART 700ie — the listed SMART 700 entry is a different panel — so identify the panel by nameplate order number, obtain the supported service package from Siemens or its distributor for your region, then connect and run a complete backup.

On this page
  1. Separate the two faults before you touch anything
  2. Read the panel identity before you call anyone
  3. Why the SMART 700 entry cannot stand in
  4. Connect and run the complete backup
  5. What the backup gives you — and what it does not
  6. The decision, case by case
  7. Questions asked

You have two faults stacked, and only the first one blocks the backup today. ProSave v9.0.3.0, as delivered with WinCC flexible 2008 SP3, carries no device profile for the SMART 700ie. The SMART 700 entry in the list is a different panel, and selecting it does not make this installation support yours — that is why no connection follows and no backup can start. The fix runs in this order: read the exact panel identity off the nameplate, obtain the service-software package Siemens or its distributor supports for that order number in your sales region, install it, then connect over Ethernet and run a complete backup. Get the package through that channel only; an unofficial copy is unsupported and outside the license.

Separate the two faults before you touch anything #

A missing device type and a failed connection are different diagnostic results, and each one stops the backup for its own reason. The device type selected on the General tab tells ProSave which transfer functions and image handling are documented for that hardware; without a profile for the exact model, the tool has no supported way to address it. With the right profile, the PC still has to reach the panel through a configured interface, so addressing and transfer settings stay a fault class of their own.

  • Device list has no entry for your exact model → software-support fault. Nothing selected inside this installation fixes it.
  • Entry exists, connection attempt fails → communications fault. Profile choice cannot fix it; interface settings can.
  • Both at once → close the profile fault first, then the connection; a correct profile with no path is still a dead backup.

Record the connection message exactly as shown. A missing entry and a refused connection are separate clues, and neither one alone means the panel is defective.

Read the panel identity before you call anyone #

The name on the bezel is not a compatibility identifier. SMART 700 and SMART 700ie are different panels, and the suffix carries hardware differences a profile has to know about. Photograph the nameplate and copy the full order number exactly as printed, every suffix included — shortening the name to SMART 700 is the step that creates this problem in the first place. If the panel still boots, its system information pages add the installed software version, which the support desk asks for next. For a panel with no readable nameplate at all, the same routine applies as in identifying an unbranded legacy touch panel before replacing it.

Why the SMART 700 entry cannot stand in #

The device list is built from the profiles shipped with that exact release, and ProSave v9.0.3.0 from WinCC flexible 2008 SP3 does not include one for the SMART 700ie. No selection inside the installation changes that: the near-named profile alters the product label, not the documented transfer behavior. The restore side carries the same dependency in reverse, which the C7-623 restore notes on exact ProSave device support spell out for another panel family.

The SMART panels were released for specific regional markets, and the matching service software is supplied through those same regional channels. So the decision is administrative, not technical. Contact Siemens or an authorized distributor with the order number, the installed versions and the operation you need, and ask for the supported combination for your region. If the panel sits outside that channel, the vendor answer defines what can legitimately be installed — not a download from an unofficial archive, which stays unsupported and outside the license no matter how well it appears to work. Vetting the engineering tool against the panel hardware before it earns bench time is the general habit; the guide to which HMI software works with which HMI panel hardware applies it across manufacturers.

Connect and run the complete backup #

Once the supported package is installed and the device list shows your exact model, the backup is a documented, mechanical flow: select the HMI device type on the General tab, then let a complete backup write the copy to the PC.

  1. Set the panel address. In the panel Control Panel, select Network and Internet, then Network settings, and enter the address — for example 192.168.0.20 with mask 255.255.255.0.
  2. Put the PC on the same subnet — for example 192.168.0.10 with the same mask. The check is a boolean AND: 192.168.0.10 AND 255.255.255.0 gives 192.168.0.0, and 192.168.0.20 under the same mask also gives 192.168.0.0. Identical network parts, same subnet, so the addresses can talk. A ping to the panel address should answer; on Basic and Comfort panels that Ethernet port is labeled X1.
  3. Put the panel into transfer mode, the state in which it accepts a service connection. That takes the operator screens out of service, so pick a window when the machine can spare the panel.
  4. In ProSave, select your exact model as the device type on the General tab, choose the interface that matches the cable, and run the complete backup to a folder on the PC. The operation reads from the panel and writes to the PC; it does not download anything to the device.
  5. Check completion before you trust the file: the log must show no unresolved communication or target errors, and a file must sit at the recorded destination.

Those addresses are a worked example, not a rule — any private subnet producing the same AND result does the job. The flow on a documented profile is what backing up a TP 1500 Comfort panel to a PC shows step by step; for the SMART family path through WinCC flexible, the walkthrough of backing up a SMART 700IE panel with WinCC flexible follows it end to end.

What the backup gives you — and what it does not #

A complete backup is a restore artifact, not an editable project. The documented contents cover the device image, operating system included, together with the panel runtime data. That makes it the right deliverable when a failed panel must be brought back or its image preserved before a swap. It is the wrong deliverable when the goal is editing: a backup on these devices does not return editable screens, tags or alarms, and no upload recovers project source that the panel never stored. Decide the deliverable before you begin:

  • Bring the same panel back after a failure → complete backup, restored by the documented process.
  • Edit screens, tags or alarms → locate the original WinCC flexible project, or plan a rebuild from the running application as the last resort.
  • Keep recipes, logs or user records → confirm what the documented backup contents cover for your model, and export anything that must stand alone with the panel export function.

The split between a service backup and an editable source decides every legacy recovery; OP15 project recovery with ComText, ProTool or ProSave works the same fork for a text panel.

The decision, case by case #

  • Your case — SMART 700ie on the nameplate, only SMART 700 in the list: stop selecting profiles. The installed release does not support the panel, so no connection or backup is legitimate from this installation. Get the package Siemens confirms for the order number and region, install it, and only then reconnect.
  • Package installed, device type present, connection still refused: the profile fault is closed; what remains is addressing, the subnet check, transfer mode or the cable. Work the five steps above and read the message the tool prints.
  • Goal is an editable project: no backup provides it on these devices. Find the original project file or schedule a rebuild.
  • Vendor confirms no supported software for your region: the panel cannot be serviced legitimately from your seat. Hand the order number to the distributor, and if the machine needs a serviceable operator station, the fallback is replacing the SMART terminal with one of the industrial panel PCs that runs your chosen HMI runtime.

Questions asked

Can I select SMART 700 and back up a SMART 700ie with that profile?

No. The device type on the General tab defines the transfer functions and the device image handling documented for that hardware, and SMART 700 is a different panel. A backup made under a stand-in profile is not a restorable artifact for your panel. Select only the device type that matches the nameplate order number.

How do I confirm a finished backup is actually usable?

Check three things before you call the job done. The tool log must show completion with no unresolved communication or target errors. The backup file must exist at the destination you recorded, readable from a second copy kept on separate storage. And the file must carry the panel identification, the software versions and the date, so another technician can reproduce the restore environment later.

What do I tell Siemens or the distributor when I request the software?

Have three things ready: the full order number from the panel nameplate, exactly as printed; the versions already installed, for example WinCC flexible 2008 SP3 with ProSave v9.0.3.0; and the operation you need, which here is a complete device backup. Ask for the supported service-software combination for your panel and your sales region, and let their answer define what you install.

Can the backup be restored to a different panel model later?

No. A ProSave backup restores to the same device type it was made from; a different model gets its own project and its own backup. That constraint is the reason the exact device profile matters before you start: an artifact you cannot restore to your hardware is not a recovery path.

Keep reading

  • How-to

    How One Spare HMI Panel Covers Seven Machines

    Yes. Keep one backup archive per machine on a USB stick or memory card, and restore the needed archive to the single spare panel at the panel itself. This works without WinCC flexible only if the backup transfer option was enabled when each project was downloaded; otherwise you need a PC with ProSave, and archives restore only to the same panel model.

    HMI and touchscreens

  • Troubleshooting

    Backing up a TP 1500 Comfort panel to a PC

    Take the image to the PC over Ethernet with TIA Portal's Backup from online device or with ProSave, or over a USB-A to mini-B cable from the PC to the panel. A USB-stick backup that has been copied to a PC and written back is not a supported archive path: the restore can report success and still leave Runtime waiting at Connecting to host.

    HMI and touchscreens

  • Selection guide

    Industrial HMI device types and how to choose between them

    An HMI device is the hardware that presents the operator interface: touchscreen panel, button panel, panel PC, panel-mount display, mobile device, web client or virtual HMI. Three questions pick the type — where the operator stands, what the location does to hardware, and who else needs the same view. Score each candidate 0 to 2 on those three; the highest total is the station's device.

    HMI and touchscreens

Why the PanelView passthrough checkbox is missing