Backing up a TP 1500 Comfort panel to a PC

HMI and touchscreens Published 8 min read

Short answer

Take the image to the PC over Ethernet with TIA Portal's Backup from online device or with ProSave, or over a USB-A to mini-B cable from the PC to the panel. A USB-stick backup that has been copied to a PC and written back is not a supported archive path: the restore can report success and still leave Runtime waiting at Connecting to host.

On this page
  1. Can I back up the panel to a USB stick and copy the file to a PC?
  2. Which cable connects the PC to the panel for the backup?
  3. How do I take the backup to the PC with TIA Portal or ProSave?
  4. Why does a restore report success and then stop at Connecting to host?
  5. How do I clear Connecting to host on the restored panel?
  6. How do I verify the backup and the restored panel?
  7. Questions asked

A TP 1500 Comfort image that has to live on a PC is taken from the panel with TIA Portal or ProSave, over Ethernet or a USB cable with a type-A plug at the PC and a mini-B plug at the panel. Carrying a USB-stick backup through the PC is not a supported archive path: written back to a stick, it can restore with a success message and still leave Runtime waiting at "Connecting to host". The sections below follow the order you meet the problem in, and each one ends in a decision: which connection, which tool, what to do with the stick, and how to prove the restored panel really talks to its PLC.

Can I back up the panel to a USB stick and copy the file to a PC? #

No. The stick is the backup's container, not a folder of files you can move: backup data written to a stick fails the restore as soon as its contents are copied to another medium, and routing it through a PC is exactly that copy.

A backup is a full image of the panel (project, runtime and device data) written to a storage medium, and a restore writes that image into another device of the same type. It is not an upload or a download: the file is not a project, it does not open on the PC, and it cannot be edited. Its only purpose is cloning or replacing a panel, which is exactly why you want one archived before a panel swap.

The panel's own Control Panel offers the backup to USB, and that route is fine as long as the stick itself stays the archive. Three constraints come with it:

  • Contents copied to a different stick fail the restore.
  • A second backup onto the same stick is refused or overwrites the first image, so one image per stick.
  • Contents deleted from the stick, stored on a PC and written back are not a supported archive; the restore can report success and fail later at "Connecting to host".

Decision: if the image must live on a PC, do not use the stick as transport at all. Take the backup directly to the PC over one of the next two routes.

Which cable connects the PC to the panel for the backup? #

Use Ethernet, or a USB cable with a type-A plug at the PC and a mini-B plug at the panel. Comfort panels have an Ethernet interface, so the everyday choice is a network cable plus the panel's IP address.

Read the panel's IP address and subnet mask in its Control Panel, give the PC a free address in the same subnet, and ping the panel. If the panel already talks to its PLC over PROFINET or TCP/IP, the same kind of Ethernet link carries the PC backup. The Siemens backup documentation gives a short list of supported PC connections per panel family; settle on one route per job. On older operator panels that route was a USB/PPI multi-master cable with the PC interface set to match, and a Comfort panel needs neither: you use Ethernet or the USB device cable.

The ping result splits the fault in two. A reply with a failing tool points at the panel's transfer settings; no reply points at addressing or the cable.

How do I take the backup to the PC with TIA Portal or ProSave? #

With TIA Portal, go online with the panel and run "Backup from online device": TIA Portal writes the complete device image to a folder you choose on the PC, with no USB stick involved.

In the online functions of the HMI device you select the panel, the connection and the destination folder, then start the backup. If the entry is missing, you are not actually online with the panel through the selected interface, so fix that before anything else. You do not need the TIA project for this, because the panel itself is the source. Where the source project does exist, keep it as well: a download rebuilds a panel from the project, a backup restores it without one, and the two cover different failures. If your real problem is a project file that will not open on the PC at all, that is recovery rather than backup, and when an HMI project fails to open: recovery and backup covers that path.

With ProSave, select the panel type, the connection type and, for Ethernet, the panel's IP address, then start the backup to a folder of your choice on the PC; ProSave does backup and restore only and needs no project. ProSave is a standalone utility from Siemens support, and release V13 is the one commonly used because it covers the whole Siemens panel range. It is the lowest-overhead route when the engineering project is not on the PC.

  1. Read the panel IP and subnet mask in the panel Control Panel, and enable the transfer channel the connection uses where the panel requires it.
  2. Set the PC adapter to a free address in the same subnet and ping the panel.
  3. Open the backup function in ProSave, select the panel type, the connection type (Ethernet or USB) and, for Ethernet, the panel IP.
  4. Choose a destination folder and start. Keep the panel powered and the cable undisturbed until the tool reports completion.
  5. Store the file under the panel designation and date, keep a second copy of the whole file, and do not edit, rename or unpack anything inside it.
  6. To restore into a replacement panel of the same type, connect it the same way, select restore, point at the file and run it. Remote access to the panel is blocked while the restore runs, and you set the network parameters after the restart.

One warning belongs here: never cut power or unplug mid-restore. The image is being written into the panel's internal storage, and an interrupted write can leave it with no loadable system.

Why does a restore report success and then stop at Connecting to host? #

Because the image went through a copy it was never built to survive: a stick backup deleted, rebuilt from PC files and restored can report success, reboot, and leave Runtime waiting for a PLC its connection cannot reach.

"Connecting to host" means Runtime started the restored project and is waiting for the PLC connection configured inside that project. The success message proves the write finished; it says nothing about the network the panel now sits in. That separates the fault into exactly two layers:

  • Restore made from a stick whose contents passed through a PC: treat that stick as unusable. Take a fresh backup straight to the PC with ProSave or TIA Portal, or download from the source project if it exists, and restore from that.
  • Restore made from a clean PC-written image: the image is fine and the stall is addressing, so work the next section.

How do I clear Connecting to host on the restored panel? #

Put the panel in the same subnet as the PLC the project's connection points at; in a healthy setup "Connecting to host" clears a few seconds after the addresses match, and live values appear.

Worked example with illustrative addresses. Say the restored project's HMI connection points at a PLC at 192.168.0.10, and the replacement panel boots with 192.168.1.23 and subnet mask 255.255.255.0:

  • Panel side: 192.168.1.23 AND 255.255.255.0 = 192.168.1.0
  • PLC side: 192.168.0.10 AND 255.255.255.0 = 192.168.0.0
  • 192.168.1.0 and 192.168.0.0 are different networks, and with no router in between the panel cannot reach the PLC, so Runtime waits indefinitely.
  • Set the panel to a free address in the PLC's subnet, for example 192.168.0.23 with the same mask: both sides now compute 192.168.0.0, the subnets match, and the connection comes up once cabling and the PLC address are right.

If the subnets already match and a ping from the PC to the PLC still fails, the fault is the cable, the switch port or the PLC interface, so check the link LEDs and the PLC's Ethernet settings.

Reading Meaning Action
Panel and PLC in different subnets Project connection unreachable Move the panel into the PLC's subnet and compare the PLC address in the project connection with the real one
Same subnet, ping to the PLC fails Cable, switch port or PLC interface Check link LEDs and the PLC Ethernet settings
Panel talks to the PLC over MPI or PROFIBUS Bus parameters differ from the live bus Match baud rate, panel station address and highest station address to the network in use
Clean PC image, addresses right, stall persists Image or device settings damaged Restore again from the PC image, otherwise download from the source project

How do I verify the backup and the restored panel? #

Work the checks in order and stop at the first failure: the file exists with size, the restore completes, Runtime starts a project, the network parameters match the plant, and live values appear.

  • The backup file on the PC is present and non-zero and the tool reported success. A zero-size or missing file means the backup failed, so retake it.
  • The restore completes and the panel restarts on its own. A stall during transfer is a connection fault, so check cable and addressing, then retry.
  • The project's start screen appears, not a Transfer or Loader screen. A Loader screen means the image did not install.
  • Panel IP, subnet mask and the PLC address in the project connection match the plant plan; on MPI or PROFIBUS, the bus parameters match the network in use.
  • "Connecting to host" clears and live tag values show on screen.

The same habit applies to bigger archives: verifying HMI project data is inside your platform backup catches the backup that silently missed the part you actually needed. And when a failing, discontinued terminal makes the next swap the last one, the alternative to another like-for-like panel is industrial panel PCs running the vendor's PC runtime, a migration you plan from the source project while it still exists.

Questions asked

Can I open or edit the backup file on the PC?

No. A backup is a device image: its only supported use is a restore into the same panel type, and no engineering tool opens it for editing. That is why the source project is archived as a separate artifact. It is the only editable copy of the application, and losing it leaves the image as the sole recovery path.

Can I restore the image into a smaller panel, for example a 12-inch model?

Not from the image. A restore targets the same device type, so a change of size or generation is a replacement built from the source project, downloaded and adapted to the new panel's resolution. If you are downsizing and hold only the image, search first for the source project on the engineering PC or in old project archives.

Does the panel's automatic backup to its memory card replace the PC archive?

No. When the automatic backup service function is enabled, a Comfort panel writes all the data required for operation to its SIMATIC HMI memory card by itself. That card is treated as removable only with the device switched off, and it stays a device-attached copy. It never produces the file you need on a PC.

ProSave cannot see the panel although ping works, so what is wrong?

Ping proves addressing, nothing more. Check that the transfer channel for the connection is enabled in the panel's Control Panel, and on the PC that the interface assignment the tool uses points at the physical adapter you are actually cabled to. A tool that still fails after both checks is usually set to the wrong panel type or connection type in its own selection.

Keep reading

  • How-to

    How to Upload a Program From an Old Touchscreen HMI

    An editable upload from an old Siemens touchscreen HMI is possible only if Enable back transfer was checked when the project was first downloaded; it was off by default, so most panels refuse. Without it, ProSave recovers at best a binary backup that restores to the same panel type and cannot be edited. Identify the exact model from the label, and ask the original supplier for the project before anything else.

    HMI and touchscreens

  • How-to

    How One Spare HMI Panel Covers Seven Machines

    Yes. Keep one backup archive per machine on a USB stick or memory card, and restore the needed archive to the single spare panel at the panel itself. This works without WinCC flexible only if the backup transfer option was enabled when each project was downloaded; otherwise you need a PC with ProSave, and archives restore only to the same panel model.

    HMI and touchscreens

  • Troubleshooting

    Fixing HMIRTM.EXE Runtime Crashes on a Comfort Panel

    The HMIRTM.EXE serious error is the HMI runtime crashing on the panel itself, most often because internal storage filled with accumulated logs. Back up to a USB stick from the panel operating system, delete the logs, and stop the runtime before changing the IP address; the failed ping is a network fault that sits below the project layer.

    HMI and touchscreens