TP177B backtransfer and the missing PDZ file

HMI and touchscreens Published 5 min read

Short answer

You cannot turn a TP177B's running program into an editable project unless the original download was made with Back transfer enabled in WinCC flexible. A backtransfer decides it: a PDZ file with real content means the source can be recovered and edited, while a 0-byte file or an error means it was never stored and you need the original project or a rebuild.

On this page
  1. The three conditions for a TP177B backtransfer
  2. Run the backtransfer and read the result
  3. What each finding means
  4. Worked example: a 0-byte file on a live machine
  5. Two legitimate paths when no backtransfer data exists
  6. Protect the panel before you edit
  7. Questions asked

You cannot edit a TP177B program by uploading it from the panel. The TP177B is engineered with WinCC flexible, and the only supported route from a running panel back to an editable project is backtransfer. Backtransfer works only if the original download was made with the Back transfer option enabled in WinCC flexible, and the proof is what the attempt leaves on the configuration computer: a PDZ file with real content means the source data was stored in the panel and can be recovered; a 0-byte file or an error means it never was, and no supported tool will turn the runtime into source. Below are the check, the outcome for each case, and the decision.

The three conditions for a TP177B backtransfer #

Backtransfer succeeds only when all three conditions hold:

  • Panel support. The TP177B is among the panels able to return source data to the engineering tool.
  • Source stored at commissioning. In WinCC flexible, the Back transfer check mark must be set when the project is compiled and downloaded; that is the step that writes the compressed source into the panel. A download made without it produces a runtime that is final.
  • Channel open at the panel. Control Panel > Transfer > Back Transfer must be switched on so the runtime releases the transfer interface.

On the engineering side you need WinCC flexible installed and a transfer connection on the channel the panel is configured for. This is the mechanism behind why an uploaded HMI copy is not an editable project: the download direction carries runtime data only, unless the source was explicitly packed along at commissioning.

Run the backtransfer and read the result #

  1. Install WinCC flexible on the configuration computer, in the version the panel was built with or a newer release, and select the TP177B variant printed on the nameplate.
  2. Connect on the panel's transfer channel and confirm the panel answers.
  3. At the panel, enable Back Transfer under Transfer in the Control Panel, exactly as the path above shows. The runtime leaves its screens in transfer mode, so do this while the machine is stopped.
  4. Start the backtransfer command in WinCC flexible and watch what lands on the configuration computer.

Two results are possible:

  • A *.pdz file with real content appears and WinCC flexible unpacks it. The project opens with editable screens and tag tables. Save it at once and put a copy in the source archive.
  • A 0-byte *.pdz file or an error. The commissioned download carried no backtransfer data, and no supported upload-to-edit path exists from a runtime alone.

The identical missing-file failure on the keypad variant of the same panel family is walked through in the OP 177B backtransfer PDZ fix. The same error on a different panel model is covered in the OP277 PDZ error walkthrough. The logic is identical on every model: no stored source, no recovery.

What each finding means #

Finding Meaning Decision
Backtransfer returns a PDZ file with real content and the project opens The commissioning download stored the source Edit it, archive the recovered project, set Back transfer again at the next download
Backtransfer returns a 0-byte PDZ file or an error No backtransfer data was ever stored Stop the recovery attempt; obtain the original project or rebuild
Only a runtime file on the SD card A reloadable image, valid for restoring this panel Keep it as a restore copy; it never opens as a project
An original project archive from the supplier Editable source exists elsewhere Compare it with the running panel before changing anything

The card file is worth keeping even when it cannot be edited; moving a project between card and panel is covered in how to transfer an HMI project with a USB drive or SD card.

Worked example: a 0-byte file on a live machine #

Hypothetical but typical: a TP177B PN/DP runs a machine, and the only copy of the program lives in the panel and on its card. You install WinCC flexible, enable Back Transfer at the panel and run backtransfer. The file browser on the configuration computer shows the new file at 0 KB, and 0 bytes in means 0 bytes of project to unpack, so there is nothing to open. The integrator's original download was made with the Back transfer box unticked, and no setting changed today can create data that was never written. Decision: stop, request the project archive from the integrator, and rebuild if it no longer exists. Had the same run returned a file of a few hundred kilobytes, WinCC flexible would have unpacked it and you would be editing screens.

Two legitimate paths when no backtransfer data exists #

  • Obtain the original. Ask the machine builder or integrator for the complete WinCC flexible project, not a runtime image. An editable archive opens directly in the engineering tool. Compare its screens and tag tables with the running panel before trusting it, because archives drift behind panels that were patched on the machine.
  • Rebuild. Create a new project for the TP177B, reconnect the PLC driver, rebuild the tag tables from the electrical drawings and reproduce the screens from the running panel. Budget it as a commissioning task with its own bench test; the general method is in how to recover an HMI program when the source file is lost.

There is no third path: nothing supported converts this panel's runtime image into engineering data, and the missing PDZ file is the documented sign that none was stored.

Protect the panel before you edit #

Whichever path applies, preserve what runs today:

  • Make a full backup with ProSave, the documented tool for TP177B backup, restore, download and operating-system update.
  • Keep the card's runtime copy as a second restore route.

One safety note: backtransfer, download and OS update all pull the panel out of runtime, so schedule every one of them for a planned stop, with a restorable backup in hand first.

Questions asked

Does switching on Back Transfer at the panel make an old project recoverable?

No. The panel-side setting only opens the transfer channel while the panel is in transfer mode. The source itself is written into the panel by the original WinCC flexible download, and only if that download was made with the Back transfer option enabled. Turning the setting on later gives an upload somewhere to go, but there is nothing to carry if the data was never stored.

Can ProSave recover the TP177B source?

No. A ProSave backup is a faithful image of the runtime: restoring it brings the panel back exactly as it was, screens and all, but nothing inside opens as editable screens or tag tables. Use ProSave to protect the machine before an edit or an operating-system update, and treat backtransfer or the original project archive as the only routes to editable source.

The panel came with an SD card holding the program. Is that the source?

No. A card written by a download or a panel-to-panel copy holds a loadable runtime image. Loading it puts the same program back onto a blank panel, which makes it a good restore copy, but no engineering tool opens it as a project. Editable screens and tags come only from backtransfer data or the original project archive.

How do I make sure the next recovery is possible?

Set the Back transfer option in WinCC flexible before the next download, then prove it: run a backtransfer once, confirm that the PDZ file appearing on the configuration computer has real content and opens as a project, and store that project as the source archive. Do both transfers while the machine is stopped, since the panel leaves runtime each time.

Keep reading

  • Troubleshooting

    TP177B color PN/DP OS update fails: version set and image fix

    The transfer is refused because the project, the engineering version and the panel image are not a compatible set. Install Hotfix 7 for WinCC flexible 2005 SP1, which supplies the TP177B image and downgrades the panel to it, or keep the panel's newer version with at least WinCC flexible 2008 SP1; then convert the project from TP177B mono to TP177B color PN/DP and transfer over MPI.

    HMI and touchscreens

  • Explainer

    Why KTP400 Basic Color PN is missing in WinCC flexible

    The KTP400 Basic Color PN (6AV6647-0AK11-3AX0) is not configurable in WinCC flexible 2008 in any service pack; the missing catalog entry is a support boundary, not a fault in your installation. Engineering starts in TIA Portal V11 SP2. A STEP 7 V5.6 controller project is either migrated into TIA Portal or kept separate behind a PLC proxy.

    HMI and touchscreens

  • Troubleshooting

    WinCC Flexible Migration Fails at 9% on Missing SQL Database

    A migration that stops at 9% with an SQL database message means TIA Portal could not open a database the WinCC flexible source project depends on. Read the Migration log, restore access to that exact database or remove the obsolete external connection in WinCC flexible 2008, then start Migrate project from the project level and rerun.

    HMI and touchscreens