HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

The Sm@rtClient view scales only in proportion, so a 4:3 remote image on a 16:9 panel always leaves an empty strip: fitted by height, it covers 75 percent of the width. Enlarge the view object and set its own scaling property, because the local Fit to screen choice does not govern the remote view. After that, accept the strip or rebuild the remote project at 16:9.

On this page
  1. Why the local screens fit but the remote view does not
  2. Fitting a 4:3 MP 277 image into a 16:9 client area
  3. What the view shows and what each symptom means
  4. Fixing the Sm@rtClient view
  5. Fit, crop or stretch: pick one on purpose
  6. Verify on the panel
  7. Questions asked

The remote image stays small because the Sm@rt Access client view scales only proportionally. A 4:3 MP 277 project shown on a 16:9 TP1200 Comfort can reach the top and bottom of the client area or its sides, never both, so a full 16:9 fill is impossible without distortion. The Fit to screen choice you made under Resize screen during the WinCC flexible to TIA Portal migration governs the local screens only; the Sm@rtClient view object carries its own scaling control. Enlarge that object, set its scaling, and the image grows to the largest proportional size the area allows. What remains is an empty strip that no client setting can remove: rebuild the remote project's aspect ratio to reclaim it, or give the strip a job as local navigation or status space.

Why the local screens fit but the remote view does not #

Two scaling paths run on the replaced panel, and they are independent. The Resize screen setting decides how the migrated project draws its own screens on the TP1200 Comfort; chosen as Fit to screen, it makes those local screens occupy the display. The Sm@rtClient view is different: it draws an image that the second panel's Sm@rtServer sends, and that image keeps the geometry of the remote project. Changing the local resize choice does not rewrite the geometry arriving from the remote panel, which is exactly why a project whose main screens all fit still opens a small remote view.

Before scaling work, confirm the panel image matches the project, because mismatched versions cause their own display faults; the article on matching an HMI panel image to its TIA Portal project version walks through that check. If the local screens themselves misbehave after a migration, the article on the WinCC 7.4 adapt picture setting for migrated screens covers how to make migrated screens fit a new resolution; the remote view is a separate problem with a separate fix.

Remote access itself is configured in the project tree under the panel's Runtime settings, in the Services area, where the Remote connection settings and the two remote access passwords live. Scaling problems are not connection problems: if the view opens and shows the remote image, the link is fine and the remaining work is geometry.

Fitting a 4:3 MP 277 image into a 16:9 client area #

Inputs for this migration case:

  • Source aspect ratio 4:3, the screen geometry of the MP 277 project, retained after the transfer to TIA Portal.
  • Destination aspect ratio 16:9, the Sm@rtClient view stretched across the TP1200 Comfort widescreen display.
  • The rule from the Sm@rtClient Scaling property: width and height are multiplied by one common factor, so the image's own ratio never changes.

Arithmetic, carried in ratio units (width divided by height):

  1. Source ratio: 4 / 3 = 1.333.
  2. Destination ratio: 16 / 9 = 1.778.
  3. The limiting dimension is height: fitted by height, the image spans the full client height, and its width is 1.333 heights, against an available width of 1.778 heights.
  4. Width used: 1.333 / 1.778 = 36 / 48 = 0.75 of the client area's width.

Result: the image touches top and bottom and covers 75 percent of the width, leaving 25 percent of the width empty on one side or split across both sides, no matter how you size the view object or set its scaling.

Decision: no client setting removes that strip. To reclaim it, rebuild the remote project's screens at 16:9, or place local navigation and status objects in the strip. Stretching the width by the missing factor, 1 / 0.75 = 1.333, would fill the area, but it deforms every control on the remote image, which is not a fix an operator station should carry.

What the view shows and what each symptom means #

What you see Cause Action
Complete image, empty columns at the sides Proportional fit by height; the source ratio is narrower than the destination Expected; redesign the source or use the strip locally
Complete image, empty bands above and below Proportional fit by width; the source ratio is taller than the destination Expected; same choice
Image occupies only part of its configured object Undersized view object or unset scaling Run the fix list below
Squares look wide, circles look oval Non-proportional stretch Remove it; restore proportional scaling
Edges or controls missing The image is cropped, not fitted Restore proportional fit and verify the full source image

A quick field check for distortion: find a known square button or circular indicator in the remote image. If it stays square or round, the scaling is proportional and the leftover space is the ratio difference. If it deforms, the view is being stretched and touch targets have drifted from the graphics.

Fixing the Sm@rtClient view #

  1. In TIA Portal, open the screen on the TP1200 Comfort that carries the Sm@rtClient view.
  2. Select the Sm@rtClient view object itself, not the surrounding screen or a background graphic, and enlarge its boundary to the largest rectangle your screen design allows. A larger object raises the ceiling on the proportional image; it cannot change the ratio.
  3. Set the view's Scaling property so the remote image can be zoomed while keeping its proportions.
  4. To zoom beyond the fitted size, use the view's Scale by zoom. It works only when the device layout is suppressed, through the Suppress Device Layout selection, because otherwise the client reserves the panel's own layout frame and the zoom stays locked.
  5. Download the project, run it, and reconnect to the second panel through Sm@rt Access.
  6. Confirm the image now touches the height boundary, or the width boundary when the source ratio is taller, and stops there.

Enlarging the object and setting the scaling is the whole client-side fix. Once the image touches its limiting boundary, further uniform enlargement would push content past the opposite boundary, so that boundary is the end point, not a sign that something is still wrong.

Fit, crop or stretch: pick one on purpose #

Whenever the source and destination ratios differ, three display policies exist, and only one is fit for a running machine. Proportional fit keeps every remote control visible and correctly shaped; make it the default for any screen an operator touches. Cropping fills the area but can push alarm fields, status objects or navigation controls outside the view; never crop a screen that carries alarms or a stop control, because a control the operator cannot see is a control he cannot press. Non-proportional stretch shows everything but changes control shapes and spacing, so the touch targets stop matching the visual design the operators learned.

The decisions, per case:

  • MP 277 4:3 project on a TP1200 Comfort 16:9 view: proportional fit, empty strip on the width axis; redesign the remote project at 16:9 if the strip is unacceptable.
  • Image smaller than its object: fix the object size and the Scaling property as in the list above.
  • Deformed buttons or oval indicators: remove the stretch and return to proportional scaling.

Verify on the panel #

  • Completeness: every remote edge, alarm field, status object and navigation control is visible; a missing edge means cropping or an undersized view object.
  • Geometry: a known square control stays square and a circular indicator stays circular.
  • Maximum proportional size: the image touches exactly one boundary of the client area; touching neither means the object dimensions or the scaling are still unset.
  • Independence: switch between a local screen and the Sm@rt Access screen; the local screens follow the migrated Resize screen choice while the remote view follows its own scaling, and each should now behave as configured.

Questions asked

Can I stretch the Sm@rt Access image from 4:3 to 16:9 to fill the screen?

Only by scaling width and height by different factors, which the view does not do and which you should not want: filling a 16:9 area from a 4:3 image needs 1.333 times more horizontal than vertical enlargement, so buttons become ovals and touch targets no longer sit where the graphics show them. If a full 16:9 image is a requirement, rebuild the remote project's screens at 16:9 rather than distorting the view.

Why does the Scale by zoom on the Sm@rtClient view do nothing?

The Scale by zoom works only when the client is not reserving the remote panel's own layout frame, which is what the Suppress Device Layout selection does. With the device layout active, the view keeps that frame and the zoom stays locked at its fitted size. Suppress the device layout in the view's configuration, set the zoom factor, then reconnect; the image should enlarge while keeping its proportions.

Does the Fit to screen setting ever affect the Sm@rt Access view?

No. Resize screen with Fit to screen is a local setting: it decides how the migrated project's own screens are drawn on the TP1200 Comfort display. The Sm@rt Access view draws an image sent by the remote panel at that panel's geometry, and it follows only the scaling configured on the Sm@rtClient view object. A local screen that fills the display therefore proves nothing about the remote view.

Keep reading

  • Troubleshooting

    Why SIMOTION device proxy initialization fails after MP277 migration

    Initialization fails when three prerequisites are missing at once: the SIMOTION D CPU must run firmware V4.3, the CPU object in HW Config must be changed to that version, and the project that initializes the proxy must be in SCOUT V4.4 format. Convert and recompile, re-synchronize the WinCC flexible part, install the engineering software in the reported order, and create the HMI connection in Network view so its driver is SIMOTION.

    HMI and touchscreens

  • Troubleshooting

    Fixing Data Table Too Small Errors After a PanelView Plus Conversion

    When a converted PanelView Plus application reports a data table too small or missing for every imported tag, the fault is the runtime communication path, not the PLC data files. Set up the runtime shortcut manually after import and give the gateway card and its alias unique IP addresses; in one documented upgrade that single change made the online tag folders appear immediately.

    HMI and touchscreens

  • How-to

    Replacing a Fleet of PanelView 550 Terminals on DH-485

    There is no direct swap: the PanelView 550 is Silver Series, so each terminal is a migration. The PanelView Plus 6 600 keeps the 550 cutout but needs a third-party DH-485 adapter; a Plus 6 700 takes the 2711P-RN6 but modifies the cutout. Audit all 25 catalog numbers, convert one application in FactoryTalk View Studio ME, pilot one machine, then buy the fleet.

    HMI and touchscreens

Where to Find the Vijeo Web Gate Client 6.3 Installer