IMDTouchKnowledge BaseShop main store

Troubleshooting

Why SIMOTION device proxy initialization fails after MP277 migration

HMI and touchscreens Published 7 min read

Short answer

Initialization fails when three prerequisites are missing at once: the SIMOTION D CPU must run firmware V4.3, the CPU object in HW Config must be changed to that version, and the project that initializes the proxy must be in SCOUT V4.4 format. Convert and recompile, re-synchronize the WinCC flexible part, install the engineering software in the reported order, and create the HMI connection in Network view so its driver is SIMOTION.

On this page
  1. Why initialization stops at 39 percent
  2. The three prerequisites the device proxy checks
  3. Update the controller and the project
  4. Install the engineering software in this order
  5. Initialize the proxy and connect the TP900
  6. Version check on a D435-2DP before initialization
  7. If the CCDBUtils database message appears
  8. The decision for each case
  9. Questions asked

Migrating an MP277 8-inch Touch to a TP900 Comfort on a SIMOTION D line can pass every compile and still fail at the device proxy: after the HMI project is copied from STEP 7 and migrated into TIA Portal V13, initialization reports PLC_Device Proxy fails, stops at 39 percent, and gives no reason. The percentage is not a fault code to decode. It is where initialization stalls when its prerequisites are not all met: the CPU firmware, the CPU object in HW Config, and the SCOUT project format. Bring the controller and its project object to V4.3, convert the project to SCOUT V4.4 format, install the engineering tools in the reported order, and create the HMI connection in Network view so its driver is SIMOTION.

Why initialization stops at 39 percent #

The case reports the reason as unknown, and no vendor document assigns a meaning to the percentage, so treat it as the point where the proxy write stalls rather than a code to look up. Initialization works from the converted SIMOTION project and its data, and the three checks in the next section are the conditions the delivery release and the proxy requirements name; when any one of them is short, the write stops partway.

Keep this apart from a migration that never finishes: if the HMI project itself will not convert or open in TIA Portal, that is a different fault with its own cause. A WinCC flexible migration that fails at 9 percent on a missing SQL database is one such example with its own fix.

The three prerequisites the device proxy checks #

Initialization passes only when all three of these hold at the same time:

  • CPU firmware at V4.3. A V4.2 CPU cannot initialize the proxy; the reported line was brought to V4.3 before anything else was touched.
  • The CPU object in HW Config at V4.3 as well. Updating the physical CPU alone is not enough: until the object in the project is changed and the project recompiled, the project still describes the old device and cannot serve the initialization.
  • The source project in SCOUT V4.4 format. The project selected for initialization must be the converted, saved and compiled V4.4 project, not the archive as it came off the machine.

The engineering environment is the remaining documented requirement: TIA Portal as of V13 with SIMOTION SCOUT TIA installed, which is what allows a Comfort Panel to be used in SIMOTION SCOUT. Missing any one of the three items above is what produces the mid-write stop.

Update the controller and the project #

  1. Archive a copy of the working project and run the conversion and initialization against the copy. A migration that destroys the editable source leaves you with the recovery problem described in recovering an HMI program when the source file is lost.
  2. Install the Firmware Support Package from the vendor's support portal (support entry 33119786) so the device tool can create the V4.3 update data.
  3. Load firmware V4.3 onto the CPU. The load reboots the SIMOTION D and takes the connected S120 motion control offline, so bring the machine to a safe stopped state and schedule the reboot before you begin.
  4. In HW Config, drag the V4.3 catalog entry for the installed CPU onto the rack, or right-click the rack and use change device. Select the entry that matches the CPU's order number.
  5. Open the library, go to the TP/TO tab, and select the V4.3 version with the same settings the V4.2 selection used.
  6. Update the S120 drive objects in the same pass; the reported sequence moved them from V4.3 to V4.7.
  7. Save and compile the SIMOTION project.
  8. Open the integrated WinCC flexible project. The CPU change has made its symbols and addresses stale, so WinCC flexible starts a synchronization that pulls the new symbol and address information from the CPU version; compile it and clear any errors before migrating.
  9. De-integrate the HMI part with copy from STEP 7, then open that copy in TIA Portal V13 to migrate it.

Install the engineering software in this order #

The reported stack for this workflow is SIMOTION V4.4.0.6, and the order matters because it clears the mixed SCOUT and SCOUT TIA installations:

  1. Uninstall SCOUT V4.4.0.2.
  2. Install SCOUT V4.4.0.6.
  3. Uninstall SIMOTION SCOUT TIA V4.4.0.2.
  4. Install STEP 7 V13 SP1.
  5. Install WinCC V13 SP1.
  6. Install TIA Portal Update 4.
  7. Install SIMOTION SCOUT TIA V4.4.0.6.

With that stack in place, TIA Portal V13 SP1 and SCOUT TIA V4.4.0.6 are the versions that open both halves of the migrated project.

Initialize the proxy and connect the TP900 #

In TIA Portal, add the device proxy and select the converted SCOUT V4.4 project. The Initialize Device Proxy window detects the SIMOTION D on the Ethernet network: select the target, confirm its IP address, and initialization writes the proxy data from the SCOUT project to the device.

When initialization completes, the job is done. There is no proxy data generation command, and not finding one in the menus is not a fault.

The migrated project usually already shows an HMI connection to the SIMOTION device. If that connection was drawn manually, it is the wrong one: delete it, open Network view, select Connections, click the HMI and drop the connection line onto the SIMOTION device. TIA Portal creates the HMI configuration with driver SIMOTION; synchronize the symbols and compile.

If the initialization window lists no device at all, the fault is in the Ethernet path rather than the proxy: the engineering PC and the SIMOTION D must be able to reach each other on the subnet before initialization can find the target. That reachability pattern, a device that answers only once TIA Portal has added the engineering PC's IP address, is described in why an S7-1200 is reachable only after TIA Portal adds a PC IP address.

Version check on a D435-2DP before initialization #

Inputs, as the reported case starts:

  • Installed CPU firmware: V4.2, read from the CPU at the start of the case.
  • CPU object in HW Config: V4.2, untouched because only the panel was being replaced.
  • SCOUT project format: V4.2, the archive as it came off the machine.

Rule: initialization runs only when the device firmware, the CPU object in the project and the project format are simultaneously at their required versions, which here are firmware V4.3, CPU object V4.3 and project format V4.4. The check set passes only with three passes.

Arithmetic:

  • Firmware at V4.3? V4.2 is below it: fail.
  • CPU object at V4.3? V4.2 against a V4.3 device: fail.
  • Project format at V4.4? V4.2: fail.
  • Checks passed: 0 of 3, so initialization cannot complete and stops partway, which is the reported 39 percent.

After the update sequence, with firmware loaded to V4.3, the CPU object changed to the V4.3 catalog entry and the project converted, saved and compiled as V4.4, the same three checks read V4.3, V4.3 and V4.4: 3 of 3, and initialization completes.

Decision: do not retry while any check fails, because a retry stops in the same place. Fix the failing item, recompile, and initialize from the SCOUT project.

If the CCDBUtils database message appears #

Some stops come with An error occurred while connecting database: Please ensure that CCDBUtils service is installed. Open the Windows Services list and confirm the CCDBUtils service is installed and running; start it if it is stopped. Treat the message as its own fault rather than the cause of the initialization failure: it is not one of the three version prerequisites, so clearing it alone will not make initialization pass while a firmware or project version is short. Fix the service, re-run the three checks, then initialize.

The decision for each case #

  • Initialization stops partway with PLC_Device Proxy fails: bring the CPU and the HW Config object to V4.3, convert the project to SCOUT V4.4, compile both, and initialize from the SCOUT project.
  • The initialization window lists no device: fix addressing and the Ethernet path between the engineering PC and the SIMOTION D, then reinitialize.
  • No proxy data generation appears after initialization: nothing is missing; create the HMI connection in Network view with driver SIMOTION, synchronize the symbols and compile.
  • The database message about the CCDBUtils service appears: install or start that service, then re-run the version checks.
  • The TP900 is running: it now operates the SIMOTION CPU as the MP277 did, including run and stop commands, and the procedure for running and stopping a SIMOTION CPU from a Comfort panel HMI carries over unchanged.

Questions asked

How do I load firmware V4.3 onto the SIMOTION D CPU without the device tool?

Download the V4.3 firmware archive for the installed order number from the vendor's support portal, extract it to the root of an empty SIMOTION CF card, and put the card in the CPU: the new firmware loads at boot. The device tool route creates its update data only after the Firmware Support Package is installed.

Can a SIMOTION D CPU running firmware V4.4 initialize the device proxy?

Yes. The delivery release for SIMOTION SCOUT V4.4 states the device proxy supports SIMOTION CPUs with kernel or firmware version V4.4 as well as V4.3. What cannot initialize the proxy is V4.2, which is why the reported migration brought the CPU and its project object to V4.3 before initializing.

Which hardware catalog entry do I select, D435 or D235?

The entry that matches the CPU actually installed, checked against the order number on the device. The reported case is described as a D435-2DP at the start and as a D235 later, and the two take different V4.3 catalog entries; dragging the wrong entry onto the rack leaves the station configuration inconsistent with the hardware, so verify the order number first.

Keep reading

  • Troubleshooting

    Why the HMI image updater login fails with invalid_request

    A browser sign-in to the portal that works proves nothing about the HMI Panel Image Updater, because the updater signs in in the background and cannot answer any prompt — an MFA challenge, a choice between linked accounts, or a passkey reminder. Run one fresh, complete browser sign-in and finish whatever it shows; if a prompt keeps returning, or none appears and invalid_request stays, skip further reinstalls and install the panel image from the offline package.

    HMI and touchscreens

  • Troubleshooting

    Downloading a TIA Portal project to multiple HMI panels

    A TIA Portal download targets one HMI device, so the only one-action way to load several panels is one HMI device per panel in the same project, all panels in Transfer mode, then select the devices and download once. With a single device, repeat the download per address or ship a Pack & Go package, and a panel the engineering PC cannot reach loads through S7 routing on the CPU.

    HMI and touchscreens

  • Troubleshooting

    Upload a PanelView 600 Program When DF1 AutoConfigure Fails

    When RSLinx AutoConfigure fails on a PanelView 600, configure the DF1 driver manually at the terminal's power-up defaults - 9600 baud, CRC error checking, no parity, 8 data bits, 1 stop bit, no handshaking - then upload with PanelBuilder32. The unreadable display does not block serial recovery, and the memory card is not a guaranteed source copy.

    HMI and touchscreens