Troubleshooting
Why a TIA Portal Project Still Requests WinCC After HMI Delete
Short answer
Deleting every HMI device on a WinCC-equipped TIA Portal station and saving that exact revision normally lets the project open on a station without WinCC. If the prompt persists, the transferred revision is stale or residual objects remain; copy only the PLC station into a new project and verify that copy opens.

On this page
A TIA Portal project that asks for WinCC on a station without it usually carries either a stale saved revision or residual HMI content. The fix that works in the field: open the project on a station with WinCC installed, delete every HMI device from the project view, save and close, then transfer that exact revision and test it. If the prompt still appears after a fresh delete-and-save cycle, stop editing the original and copy only the PLC station into a new project.
Confirm what is actually blocking the open #
The reported symptom is the open attempt refusing because the project contains HMI or WinCC content. That message tells you the project data still includes HMI objects; it does not tell you which object or setting remains, so do not assume deleting the visible panels always clears it. Two failure paths exist:
- The station without WinCC received an older archived or saved revision, one that still contains the deleted HMI devices.
- The project retains undocumented WinCC residue even after every HMI device was removed.
The first path is far more common, and a repeated delete-and-save attempt succeeded in the reported case after an initial failure. The second path needs the fallback in the last section.
Remove every HMI device and save the exact revision #
Work on the station where WinCC is installed:
- Open the project in the project view.
- Select all HMI devices in the project tree.
- Delete the selected devices.
- Save and close the project.
- Note the revision you just saved, because the next step depends on transferring that one.
Then transfer the project to the station without WinCC and test the open. If you move the project by archive and retrieve, verify the archived file is the revision you saved after deletion. The verification procedure for a panel image or runtime is the same discipline as matching an HMI panel image to its TIA Portal project version: check the exact version pair before you conclude anything about the project data. An uploaded copy retrieved from a device is not an editable project, so retrieving from hardware will not help here; that limit is covered in why an uploaded HMI copy is not an editable project.
Verify the revision pair before blaming the project #
Example case, using the environment from the reported fault. Inputs:
- Station A: TIA Portal V13 SP1 Update 1 with WinCC installed. It owns the delete-and-save step.
- Station B: TIA Portal V12 SP1 Update 4 without WinCC. It must open the result.
- Revision 1: the project as saved before any deletion; it still contains the HMI devices.
- Revision 2: the project saved on station A after deleting every HMI device.
The rule: station B can only open project data whose saved revision contains no HMI objects, and a project saved in a newer TIA Portal version is not backward-compatible into an older one, so the transfer to station B must be a V12-compatible revision, not a V13-native save. Walk the check:
- Transfer revision 1 to station B: it still carries the HMI, so the open refuses. This is the failure you see when the wrong revision goes over.
- Retrieve revision 2 on station B, confirmed as the post-deletion save and in a V12-readable format: the open succeeds.
Decision: if revision 2, correctly transferred and version-matched, still refuses on station B, the project retains WinCC residue that deletion does not reach, and you move to the PLC copy. If revision 1 is what reached station B, the project was never the problem; the transfer was.
Copy the PLC into a clean project if traces remain #
When a verified post-deletion revision still requests WinCC, stop trying to hunt undocumented residue. On the WinCC-equipped station, select the PLC in the project tree and copy it. Open a second TIA Portal instance, create a new project, and paste the PLC into the new project tree. Save the new project and test the open on the station without WinCC.
This fallback deliberately moves the PLC and nothing else, so it leaves behind whatever HMI or WinCC data remained. Exporting everything to ASCII has no completed, verified procedure behind it, so treat it as unproven. Also keep this separation in mind: compatibility mode in the newer installation is a version-conversion concern, not a WinCC-removal concern, and mixing the two steps makes the result impossible to attribute.
Decision #
- Fresh delete-and-save revision opens on the non-WinCC station: done; keep that revision as the one you distribute.
- Fresh revision still prompts for WinCC: copy the PLC into a new project on the WinCC-equipped station and verify that copy opens; retire the original project tree.
- Only the pre-deletion revision was ever transferred: the deletion worked; repeat the transfer with the revision saved after deletion.
One safety note: when you paste a PLC into a new project, its configuration and program travel with it, but any HMI tags or screens referenced only from the deleted HMI do not, so bring the machine back up with the HMI offline first and confirm no interlock or alarm logic depended on the removed HMI objects.
Questions asked
How do I remove WinCC from a TIA Portal project?
Open the project on a station where WinCC is installed, delete every HMI device from the project view, then save and close. Transfer that exact saved revision to the station without WinCC and confirm it opens before doing anything else.
Why does TIA Portal still request WinCC after I delete the HMI device?
In most cases the station without WinCC received an earlier archived or saved revision, one that still contains the HMI. Check which revision you transferred and repeat the delete-and-save cycle once. If a fresh revision still prompts for WinCC, copy the PLC station into a newly created project and test that project instead.
Can I copy a PLC station from one TIA Portal project to another?
Yes. Open a second TIA Portal instance, create a new project, right-click the new project tree and paste the station. Save the new project and verify it opens on the installation without WinCC.
Do I need to upgrade the older TIA Portal station to fix this?
No. The WinCC dependency is a project content problem, not a version problem. Keep version conversion separate from removing the HMI: remove the HMI in the version that has WinCC, then handle any version compatibility as its own step with the release notes for that version pair.