Why a TP700 Comfort CSV log needs a computer to print

HMI and touchscreens Published 6 min read

Short answer

A TP700 Comfort writes its datalog as a CSV table of values on the SD card, but the runtime has no application that opens that archive and lays it out as pages, so the panel cannot print the file itself. Print it from a computer that imports the CSV with the delimiter and column types the file actually uses. Direct panel-to-printer output is a separate documented configuration limited to function-tested printers.

On this page
  1. The archive holds values, not pages
  2. What direct printing on a Comfort Panel requires
  3. Where the HP P1106 stands
  4. The computer route, step by step
  5. Import faults that fake a bad archive
  6. Worked example: the 8 h shift log from a TP700 Comfort
  7. The decision for each case
  8. Questions asked

A TP700 Comfort will log a CSV archive to its SD card all shift, but it cannot print that file, and plugging in an HP P1106 does not change that. The archive stores values separated by delimiters and line endings, not page layout, and the panel runtime ships with no application that opens the file, arranges it into columns and paginates it. A print job has to be built somewhere that can do those three things, and that place is a computer: copy the CSV off the card, import it with the delimiter and column types the file actually uses, and print it to the P1106 with the printer's driver installed on that computer. Direct panel-to-printer output exists only as a separately documented configuration, and a printer belongs on that path only if the function-tested list names it.

The archive holds values, not pages #

CSV is a text table: delimiters separate the fields and line endings separate the records. Every completed logging cycle proves the panel can write that table to storage, and nothing more. Printing needs three steps the write path does not have: reading the file back as a document, arranging it into a page layout, and driving a printer with the result. The Comfort Panel runtime has no spreadsheet, no editor aimed at the archive folder and no print dialog over a file listing. When a Comfort Panel prints, the job comes from a function configured in the engineering project — a hardcopy, a report — rendered from live or configured data at print time, never from opening the CSV on the SD card.

What direct printing on a Comfort Panel requires #

Treat the printing documentation as the standard here, because it is what compatibility means in practice. Siemens documents function-tested printers for SIMATIC Comfort Panels, and a printer either appears there with its driver or it is not a direct-print printer. The commissioning guide for released printers on SIMATIC HMI operator panels covers the sequence: download the driver, install it, parameterize it on the panel. A printer-driver add-on package supplies drivers for the specified HMI devices, and on the project side a print function must be configured before the panel produces any job at all.

Miss one leg — released printer, installed driver, configured function — and a panel that sees the printer still prints nothing; why a Comfort Panel will not print to a Brother label printer on USB works through exactly that failure. What the configured functions can output is its own subject, and printing images and PDFs from a Unified Comfort panel shows the scope on the Unified side. When the driver never reaches the panel through the engineering toolchain, that is a separate fault, covered in why the printer driver is missing in ProSave for a TP1500 Comfort.

Where the HP P1106 stands #

The printer's USB socket tells you the connector, not the compatibility. Whether an HP P1106 may hang directly off a Comfort Panel is decided by the function-tested list and its driver, and no released-printer document we can point to names this model — until the current list shows it, it does not belong on the panel. The engineering decision is therefore simple: treat it as a computer-attached printer, where its driver from HP renders the page and the printer prints it. That gives up nothing for your task, because the thing you need on paper — the archive — was never printable from the panel, whatever the printer.

The computer route, step by step #

  1. Close the archive cleanly. End the logging run or follow the panel's documented procedure for removing storage, so the last record is fully written before the card comes out.
  2. Copy, do not move. Put the CSV on the computer and leave the card's file untouched as the original; all formatting happens on the copy. If you would rather pull the file over the network than carry the card, read why HMI SFTP cannot see the SD card data log files before concluding the transfer is broken.
  3. Read the raw text first. Open the copy in a text editor and note the actual field separator, the decimal sign and the timestamp layout; the import dialog gets set to what the file contains, not to the spreadsheet's regional default.
  4. Import with explicit types. Choose the delimiter you just read, and import timestamps and any ID columns as text so automatic conversion cannot reorder or reformat them.
  5. Lay out the report. Add a title, the time range and the units from the project configuration, then set orientation and column widths until the preview shows every value unclipped.
  6. Print on the P1106's own ground. Install the printer's driver from HP on that computer, confirm the leg with a one-page test print, then send the report.

Import faults that fake a bad archive #

Read the file before blaming the printer or the logging: a clean-looking page can still carry altered timestamps, rounded values or missing records.

Symptom in the imported sheet What actually happened Fix before printing
Every field lands in one column The application did not recognize the delimiter Set the separator the raw text shows and re-import
Timestamps or IDs change form Automatic conversion applied regional formats Import those columns as text
Values gain or lose digits Decimal notation differs between file and locale Match the file's decimal sign in the import settings
Fewer rows than the run should hold Parsing or a filter dropped records Count rows against logging time divided by logging interval

Worked example: the 8 h shift log from a TP700 Comfort #

Inputs, with their sources. Your station is a TP700 Comfort writing a CSV archive to its SD card, with an HP P1106 intended for the printout — that is the case in front of you. For the log configuration, take example values and swap in your project's own: one record every minute across an 8 h shift, with a single header row.

The rule, in words: a correct import accounts for every record the logging run should contain. Expected records equal logging time divided by logging interval, and the sheet must show that many data rows plus the header.

The arithmetic:

  • Logging time: 8 h × 60 min/h = 480 min
  • Expected data rows: 480 min ÷ 1 min per record = 480 records
  • Rows the sheet must show, header included: 480 + 1 = 481 rows

Result: a complete import displays 481 rows. Decision: at that count, print the report to the P1106 from the computer; at anything less, the import dropped records — correct the delimiter or timestamp parsing and re-import before wasting paper. The path decision is the one this whole question turns on: verification, layout and print job all live on the computer, because the panel cannot render its own archive and the P1106 is not shown as a released panel printer.

The decision for each case #

  • You need the archived records on paper. Computer route, full stop. The panel records, the computer imports, lays out and prints, and the P1106 hangs off the computer.
  • The panel must print unattended at the machine. That is a different project: a printer from the function-tested list, its driver installed per the commissioning guide, and a report configured in the engineering project. It prints what that report produces, never the CSV file itself.
  • You only need the current values on paper. A configured hardcopy or report on a released printer does that from live data; the archive stays what it is — the record you print from a computer when the full history is wanted.

Questions asked

Which documents decide whether a printer works directly on a Comfort Panel?

Siemens' printing entry for SIMATIC Comfort Panels, ID 58205602, points to the function-tested printers. The commissioning guide for released printers on SIMATIC HMI operator panels is attachment 11376409 and covers downloading, installing and parameterizing the drivers. The driver collection for specified HMI devices is documented as the Add-on package printer driver V1.4. A report about a similar printer substitutes for none of these.

Would a network printer be easier than USB?

Not on a Unified Comfort Panel: its Printers settings manage USB printers, network printers are not supported, and adding a printer requires the associated PostScript file. On the classic TP700 Comfort, the function-tested printer list decides the permitted interface. Either way, that is the printer question, not the archive question, and no interface makes the panel open its own CSV as a document.

Does the ExportDataRecords system function offer a way around this?

No. ExportDataRecords exports one or all data records of a recipe to a CSV or TXT file, one file per recipe, from the function list of the engineering tool. It produces the same kind of data file your datalog already is, so it adds nothing the panel could print that the archive does not already give you.

Will a print server or a USB-to-network adapter change the answer?

No. The blocker is not the transport but the missing step between archive and page: something must read the CSV, lay it out and drive the printer's driver, and only a computer in this chain does that. An adapter that lets the panel reach the printer still leaves the panel with nothing to send except what a configured print function produces.

Keep reading

  • Troubleshooting

    Why HMI Data Logs Export Bool True as -1

    A Comfort Panel USB data log shows -1 for a true Boolean because the export serializes the all-ones bit pattern as a signed value. Assign the literals 1 and 0 conditionally into a separate numeric tag and log that tag; a direct copy into an Int or UInt keeps the -1. Verify the change in the raw CSV with a text editor.

    HMI and touchscreens

  • Selection guide

    HMI panel as local data logger for a PLCnext controller

    An HMI panel with an integrated datalogger, CSV file output and an FTP service can log PLCnext data locally with no separate PC or historian. The decision turns on two numbers: the log volume per day against the panel's free storage, and the controller's protocol server against the panel's driver list, where Modbus TCP is the lowest-friction choice.

    HMI and touchscreens

  • Explainer

    Where HMI Panel Simulation Saves Historical Data

    Yes. In the panel simulation, every data log whose storage location is set to Storage Card SD writes its archive files into a stand-in folder on the root partition of the engineering PC's drive C:. The files remain after the session ends, and the next simulation overwrites them, so the folder is scratch space for testing, not productive logging.

    HMI and touchscreens

Why GP-Pro EX CSV export writes to the simulation folder