HMI and touchscreens Published 6 min read

Short answer

The driver is missing because ProSave filters transferable options by the selected device type: a driver offered under TP700 Comfort but not TP1500 Comfort applies to the first target only. Keep the TP1500 Comfort selected, check the package release notes against the panel image and software versions, transfer through the ProSave Options tab, and use a printer the vendor lists as tested.

On this page
  1. The stage that fails first
  2. Why the selected target decides the list
  3. The XML archive is not the driver
  4. The transfer path that keeps the real panel selected
  5. Acceptance checks after the transfer
  6. Decision by case
  7. Questions asked

ProSave offers transferable options only for the device type selected, and the printer driver you found is not released for the TP1500 Comfort. Seeing it under TP700 Comfort is the proof: the package applies to that target, so selecting your real panel removes it from the list. This is a package-applicability stop, not a broken USB port, a cabling fault or a defective printer, and it happens before anything is transferred. The fix is to keep the TP1500 Comfort selected, confirm the package scope against the panel image and the engineering software, install a driver that names your panel, and print to a printer the vendor has tested. Do not select the other panel to force the transfer through.

The stage that fails first #

Panel printing runs through three stages: the driver package must apply to the selected target, the option must transfer to the panel, and the project's print function must produce output the printer understands. This report stops at the first stage. Nothing has been transferred, so there is no installation or print test to reason from, and cable, media and page-layout checks are premature.

Read your observation against this list:

  • The driver is absent with TP1500 Comfort selected: the target filter removed it. The next check is the package scope, not the USB port.
  • The same driver appears with TP700 Comfort selected: the package is released for that target, and this visibility is the applicability statement you were missing.
  • The driver transferred and the printer stayed silent: the fault has moved past package discovery. Troubleshoot the print path, not ProSave.
  • The TP1500 Comfort itself is missing from the ProSave device list: the engineering station's installed support packages are the fault, covered in when a panel model is missing from the ProSave device list.

Record which observation you actually have. A driver that never appears in the list and a transfer that starts and then fails are different faults with different fixes.

Why the selected target decides the list #

The documented workflow transfers printer drivers to Comfort Panels through ProSave: open the Options tab and take the desired printer driver from the Available options list, then follow the ProSave instructions. That list is assembled for the device type selected at that moment, because each driver package is released for named panels and software versions. Applicability is decided before anything moves.

Selecting TP700 Comfort therefore changes the list ProSave builds, not the panel on your bench. It is an evaluation context, not an installation trick. The same logic disposes of the USB argument: the connector supplies power and a communications interface, while the printer's command language must be generated by software released for the panel's firmware.

Worked example from the two list results: with TP700 Comfort selected, Available options offers 1 printer driver; with TP1500 Comfort selected it offers 0 for the same function. The difference, 1 − 0 = 1, is exactly one package whose release ends at the TP700 Comfort target. Decision from that arithmetic: the package is closed to your panel, and no cable or retry changes the count — only a package released for the TP1500 Comfort does.

The XML archive is not the driver #

Siemens publishes the current list of printers recommended for its HMI devices online, and the documentation delivered with STEP 7 Professional V13.0 already points readers to it. Downloading that list yields an archive of XML files. XML is a structured text format: the files carry the list's data, and the extension says nothing about installability.

Do not copy them to the panel and do not expect ProSave to accept them. A printer driver reaches a Comfort Panel as an option selected from Available options and transferred by ProSave, not as files placed on the panel's storage. Read the description accompanying the download: if it states no installation procedure, the archive is reference data for the recommended-printer list, and the driver you need comes from the package whose release notes name your panel.

The transfer path that keeps the real panel selected #

  1. Record the configuration before changing anything: the panel model from its identification data, the installed panel image version, the engineering software version, the ProSave version, and the printer's exact model. Read each value from the device or software information display, never from the project name.
  2. Select TP1500 Comfort in ProSave and keep it selected for the whole operation.
  3. Open the Options tab and read Available options for that target. If the driver you need is listed, select it and follow the ProSave instructions to transfer.
  4. If it is not listed, open the package's release notes or download description and find the supported-panels statement and the software prerequisites. A package that names only the TP700 Comfort stops there; the arithmetic above already decided it.
  5. Obtain the package that names the TP1500 Comfort through Siemens' support and download channels, or change to a printer the recommended list covers. For a machine in production, commit to the listed printer and stop qualifying unlisted hardware on the line.
  6. Transfer with the machine in a safe state: the panel is out of operation while options install, and an interrupted installation is a new fault.
  7. If the documentation leaves applicability open, send Siemens support the configuration record and both list results, and ask for the supported printing path for the actual panel — not for a way to push the existing package through.

Acceptance checks after the transfer #

A completed transfer proves discovery, not printing. Separate the checks:

  • Option status: the transfer finishes without an unresolved error and the option shows as installed on the panel.
  • Printer self-test: run the printer's documented local self-test to prove the print engine, media and consumables. This validates the printer alone, not the panel's path.
  • Controlled print: trigger one configured print function with known content; the page appears once and is legible.
  • Application print: run the actual report or screen hard copy the operators use, and confirm layout, characters and paper.

If the option is installed and output is still missing, the driver question is settled and the fault sits in the runtime print path — the territory covered in why a Comfort Panel will not print to a Brother label printer over USB. A greyed-out print button in the panel's viewer is a viewer setting, covered where the Comfort Panel viewer print option is disabled by the viewer, not the driver.

Decision by case #

  • The driver is offered with TP1500 Comfort selected: transfer it from Available options and run the acceptance checks. Nothing else is wrong.
  • The driver appears only under TP700 Comfort: the package does not apply to your panel. Do not transfer under the wrong device type; get the package released for the TP1500 Comfort or change the printer.
  • The printer is absent from the recommended list: printing is not proven impossible, but the combination is undocumented. Qualify it on a bench with the printer manufacturer's interface documentation, or choose a listed printer — on a production machine, choose the listed one.
  • The driver is installed and the printer is silent: the fault is downstream of ProSave; troubleshoot the configured print path.

Questions asked

Can I select the TP700 Comfort in ProSave just to push the driver across?

No. The list is filtered because the package is not released for the TP1500 Comfort, and a transfer that only runs under another device type is not a supported installation. ProSave offers no confirmation that such an option works on hardware it does not name, so the panel can end up with an option it cannot use. Take the package that names your panel, or change the printer.

Is the zip of XML files from the printer FAQ the driver I need?

Not as a transferable option. XML is a structured text format, and a printer driver reaches a Comfort Panel through the ProSave Options tab, not by copying files onto it. Read the description that comes with the archive: if it states no installation procedure, treat the files as data for the recommended-printer list, and take the driver from the package whose release notes name your panel.

The printer works from a PC over USB. Why does the panel need its own driver?

The PC runs a Windows driver that turns the print job into the printer's command language. The Comfort Panel has no Windows and must generate those commands from an option released for its own firmware and device type. A working USB cable proves only the electrical interface, which is why the vendor publishes a tested panel-printer list instead of declaring USB printers compatible in general.

Does the missing driver mean a TP1500 Comfort cannot print at all?

No. It means that one package does not apply to the target. Other released printer drivers for the TP1500 Comfort still transfer normally through the options workflow, and the recommended-printer list names combinations that work with them. If your printer has no released driver for the panel, choose a listed printer or qualify the combination yourself on a bench.

Keep reading

  • Troubleshooting

    Why a Comfort Panel will not print to a Brother label printer on USB

    The panel prints only through drivers in its image, and the compatibility list names the Brother P-Touch QL 650 TD, not the QL-820NWB. The QL650TD driver speaks ESC/P while the printer ships in raster mode for Windows, so switch the printer to ESC/P, keep the ProSave-transferred driver, set B5 with autocut, and replace the printer if a bench report still prints nothing.

    HMI and touchscreens

  • How-to

    Printing images and PDFs from a Unified Comfort Panel

    A Unified Comfort Panel has no built-in function that prints the runtime screen or a document to a printer. Print through the panel's LibreOffice install: open the PDF directly, or wrap a JPG in a one-line HTML file, then submit with -p or --pt and automate via runLibreoffice.sh. Use the CUPS lp command only after the printer queue prints a known-good file on the panel.