Troubleshooting
TP1500 Comfort V2 INOX missing from TIA Portal catalog
Short answer
There is no separate catalog entry or HSP for the TP1500 Comfort V2 INOX: configure the standard TP1500 Comfort V2, order number 6AV2124-0QC02-0AX1, update TIA Portal V16 past its shipping baseline, and install the separately delivered WinCC images. After those three steps the download succeeds against firmware 16.0.0.3.
On this page
- Why the INOX variant is not in the catalog
- Fix the firmware mismatch first in the project tree
- Update TIA Portal V16 past the shipping baseline
- Install the separately delivered panel images
- Choose the download path that fits your firmware pair
- Verify the commissioning
- Worked example
- Decision
- Questions asked
The TP1500 Comfort V2 INOX will never appear in the TIA Portal V16 hardware catalog, and no HSP fixes that: the INOX variants are deliberately consolidated under the standard article. Configure the standard TP1500 Comfort V2, order number 6AV2124-0QC02-0AX1, which is in the V16 catalog by default. Then update V16 past its shipping baseline and install the panel images that ship on their own disc, because the download fails until both are in place. Here is the sequence to commission the panel.
Why the INOX variant is not in the catalog #
The stainless-steel-front INOX panels share their electronics with the corresponding standard Comfort panel; only the bezel and housing differ. The engineering tool therefore carries one catalog entry per panel class, under the standard order number, and lists the INOX article nowhere. Selecting an HSP cannot add what the catalog design intentionally omits.
That means the wrong order number in the project is the first fault. The INOX unit here carries article 6AV2144-8QC10-0AA1, but the project must reference 6AV2124-0QC02-0AX1, the standard 15-inch widescreen touch Comfort V2. If you instead load a V1 project, the firmware classes do not line up and the download faults no matter what else you fix. We cover the V15-side version of this in article:tp1500-comfort-inox-not-in-tia-portal-v15-hardware-catalog.
Fix the firmware mismatch first in the project tree #
With a valid WinCC Advanced license, replace the device entry:
- Open the project in TIA Portal V16.
- Delete the existing HMI device from the project tree.
- In the hardware catalog, navigate to the Comfort panels and insert the TP1500 Comfort V2 with order number 6AV2124-0QC02-0AX1.
- Reconnect the screens, tags and alarms to the new device, then recompile.
Once the standard V2 article is selected, the firmware class matches the panel's V16 runtime, and the mismatch reported between the panel and the project disappears at the device level.
Update TIA Portal V16 past the shipping baseline #
A fresh V16 installation engineers Comfort panels at image 16.0.0.0, and the installation the reader in this case had reported the baseline build V16.00.00.00_31.02.00.01. Panels shipped later carry runtime 16.0.0.3 or higher. TIA Portal refuses a download that would move the panel firmware backwards, so the dialog reports that the firmware on the HMI is higher than in the project, and the adapt option then fails because the hardware entry does not correspond to the connected panel.
The fix is to raise the project, not to lower the panel:
- Close all TIA Portal instances.
- Start the TIA software updater and check for updates for V16.
- Apply the latest cumulative V16 update, then reopen the project.
After the update, the engineering image reaches 16.0.0.3 and matches the panel, so a normal download succeeds without touching the panel firmware.
Install the separately delivered panel images #
The panel runtime image files are not bundled with the engineering DVDs. They arrive on a separate third disc in the media set, or as a download from the vendor's support portal. Without them, the download dialog cannot read or adjust panel images, which is why the adapt case errors out even after the device entry is corrected.
- Locate the third disc of the V16 media set, the one carrying the WinCC images, or download the matching image package from the vendor's support portal.
- Run its setup with administrator rights and install the images for the Comfort panel family.
- Reopen TIA Portal. The download dialog's operating-system update option now lists the available panel images.
Choose the download path that fits your firmware pair #
With catalog entry, update and images aligned, pick the workflow for the versions you actually have:
| Project image | Panel image | Action | Result |
|---|---|---|---|
| 16.0.0.0 | 16.0.0.3 | Update the engineering installation first | Match at 16.0.0.3, plain download |
| 16.0.0.3 | 16.0.0.3 | Plain download | Project transfers, firmware untouched |
| 16.0.0.3 | lower | Operating-system update from the download dialog | Panel upgraded to the project image |
| lower | higher | Never a direct download | Refused; raise the project or re-flash the panel |
Verify the commissioning #
- Recompile the HMI device; it must finish without errors.
- Download to the device and confirm the firmware-higher-than-project warning is gone.
- If the panel needed a re-flash, let it reboot into the new image and confirm the version on the panel's properties screen.
- Force a tag value from the PLC side and confirm it moves on the panel screen.
Worked example #
Say your bench panel reports 16.0.0.3 and your project engineers at 16.0.0.0. The gap is 0.0.3: three update steps of the V16 image line. Applying the latest V16 cumulative update raises the project image from 16.0.0.0 to 16.0.0.3, the gap closes to 0, and the download dialog transfers the project with the firmware untouched. If instead you must run the panel at 16.0.0.0, you would re-flash it from the installed image files with the vendor's OS update tool, accepting that a download from the updated project would then raise it again. Commit to the update direction: it needs one installation and no downtime on the panel.
Decision #
- Project shows the INOX article or a V1 article: replace it with the standard TP1500 Comfort V2, 6AV2124-0QC02-0AX1. No HSP, ever.
- Panel firmware above the project image: update TIA Portal V16 to its latest cumulative patch; do not downgrade the panel on a machine that will run.
- Adapt still fails after both: install the separately delivered WinCC images, then re-attempt the download.
If the panel itself is dead or the touch surface has failed and the repair is not worth it, the same 15-inch class of operator interface is available today as industrial panel PCs that run the visualization directly on the panel.
Questions asked
Do I need an HSP to add the Comfort INOX panel to TIA Portal V16?
No. The INOX variant is intentionally absent from the hardware catalog, and no HSP exists for it. The INOX version shares the panel's electronics and differs only in the stainless-steel front, so the engineering data is identical.
Can I downgrade the panel firmware instead of updating the project?
Yes, if the panel is not running production. Flash the panel back to the project's engineering image using the vendor's OS update tool and the V16 image files. In practice the better fix is the opposite direction: update TIA Portal V16 with its latest cumulative patch so the project firmware reaches 16.0.0.3 and matches the panel without a re-flash.
Why does the adapt option say the hardware does not correspond with the HMI?
Two causes combine here. The project still references a V1 or wrong panel article, and the engineering installation lacks the panel runtime image files, which ship on their own DVD rather than with the engineering DVDs. Without those files the download dialog cannot match or adjust the panel image, so the adapt attempt fails with that mismatch message.
What firmware version does the project need for a V16 INOX panel?
An example project needs at least 16.0.0.3 to match a panel reporting 16.0.0.3. A fresh V16 install engineers at 16.0.0.0, which is lower than the panel, and the download refuses because the panel firmware would have to go backwards. Applying the latest V16 update raises the engineering image to match.