IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a Vijeo Designer runtime freezes after a few days

HMI and touchscreens Published 6 min read

Short answer

The freeze sits inside the Vijeo Designer runtime process, not the PC: the displayed clock stops, other Windows applications keep running, and relaunching only the runtime recovers it. Rebuild and retransfer the project from a development environment set to English, then run it at least four days before calling it fixed.

On this page
  1. Why does the runtime freeze while Windows keeps working?
  2. What hardware and software was this freeze reported on?
  3. Could the Italian development environment be the cause?
  4. How do I rebuild and retransfer the project in English?
  5. How long should the retransferred project run before I call it fixed?
  6. When is replacing the panel PC the better option?
  7. What should I record if the freeze comes back?
  8. Questions asked

Your runtime is not locking up the PC, it is dying inside its own process. On the reported installation, a Vijeo Designer 6.1 SP2.1 runtime on a fanless Atom-based panel PC stopped responding after roughly two days of continuous operation, its on-screen clock stopped updating, and other Windows applications kept working. Ending the runtime from Task Manager and relaunching it restored operation without a reboot. The one fix reported to hold is rebuilding the project in a development environment set to English and transferring it again; test it with a four-day acceptance run.

Why does the runtime freeze while Windows keeps working? #

The failure boundary is the Vijeo Designer runtime process itself: the clock it paints on screen stops, every other Windows application keeps running, and ending and relaunching only the runtime recovers the panel, so the operating system, memory and drives are not the fault. Read the observations together and the PC-level suspects drop out:

  • The runtime stops responding to touches and commands, so the HMI process is stalled, not the machine.
  • The on-screen clock stops updating, so the runtime's execution and repaint loop have stopped with it.
  • Other Windows applications keep working, so CPU, memory and the operating system are healthy.
  • Ending the runtime and relaunching it restores operation without a reboot, so replacing the process and the project state it carries clears the fault.

A whole-PC hang from overheating, power supply or disk failure would not leave other applications running. Whatever stalls here travels with the runtime process, and the tests below are ordered by cost, cheapest first.

What hardware and software was this freeze reported on? #

The reported installation is a Vijeo Designer runtime 6.1 SP2.1 on Windows XP Professional Version 2002 with Service Pack 3, running on a 12.1-inch fanless panel PC with an Intel Atom N270 processor at 1.6 GHz and 1 GB of DDR2 memory.

The record does not show the exact panel model, the project size, the communication load, the driver set, the memory usage at the moment of the freeze, or the Windows event logs, so none of those can be assigned as the cause. Nothing in the record rules the aging PC out either. The language rebuild comes first because it costs one rebuild and one transfer; the hardware question only comes up if that test fails.

Could the Italian development environment be the cause? #

It is the one contributing factor reported for this version: a project built with the development environment running in Italian is said to produce the multi-day freeze, and opening that project with the environment set to English and retransferring it is said to stop the freeze.

Treat that as a hypothesis to test, not a confirmed defect: no service bulletin, affected-version range or diagnostic code backs it in the available record. It is still the first move, because it is fast, reversible and needs no spare parts. Note the scope: the setting in question is the language the engineering tool itself runs in, not the operator languages your project serves. Changing it does not remove multilanguage texts from the screens; it changes the environment the project is compiled under.

How do I rebuild and retransfer the project in English? #

Switch the Vijeo Designer environment language to English, rebuild the full project and transfer it to the runtime PC again; the reported case needed nothing more. Work through it in this order:

  1. Copy the editable project source off the runtime PC before touching anything. If only the panel holds a project and the source is gone, recovering a Magelis HMI project with Vijeo Designer covers how to pull a project back before you overwrite it.
  2. In the development environment options, set the tool's interface language to English.
  3. Rebuild the complete project, not a partial download.
  4. Transfer to the runtime PC over the same path used at commissioning, stopping the runtime on the target first as the transfer tool requires. Check the transfer settings for which run-time data is preserved, because a full transfer can reset target settings, recipes and security data.
  5. Relaunch the runtime and confirm every screen, alarm and controller connection comes up as before.

One safety note: the transfer takes the operator panel out of service, so do the rebuild and retransfer during a planned stop, not on a machine that is running.

How long should the retransferred project run before I call it fixed? #

Run it for at least four days of continuous operation, twice the reported two-day failure interval, with operator commands responding and the displayed clock updating throughout. Those two signs are the whole test: command response proves the runtime is processing, and the on-screen clock proves it is still repainting.

If four clean days pass, log the environment language used for the build and build every future project for that PC the same way. If the freeze returns inside the window, the language workaround did not hold, and the next documented suspect is retentive data: the vendor's published guidance names bad retentive (SRAM) data among the main causes of random runtime crashes and application halts on industrial PCs, and clearing the retentive data area through the target's operation settings is the documented step to take next.

When is replacing the panel PC the better option? #

Replace the hardware only after the English rebuild and the retentive-data clear have both failed, because this PC runs an operating system that no longer receives security fixes, with 1 GB of memory, and a software-level fix is far cheaper than a panel swap. When the repair stops being worth it, a current industrial panel PC gives the same runtime a supported operating system, more memory and a modern touch surface. Plan the migration around the project file: an English-built source transfers to a new target with far less friction than a recovered one.

What should I record if the freeze comes back? #

Record enough to hand the vendor a complete case: the runtime build, the operating system build, the failure interval and what was still alive at the moment of the freeze. Capture these fields:

  • Vijeo Designer runtime version and service pack (6.1 SP2.1 on this installation)
  • Windows version and service pack
  • Time from project transfer to freeze, which becomes your comparison number for every fix you try
  • Whether the on-screen clock had stopped while the taskbar clock kept running
  • Whether other Windows applications still responded
  • The development environment language used for the last build
  • Whether the retentive data area was cleared, and when

Escalate through the vendor's official support channel with that record. Those fields let support match your case against known defects and service-pack fixes instead of starting from a symptom description.

Questions asked

Why does the displayed clock stop when the runtime freezes?

The clock on the screen is drawn by the runtime process itself. When the runtime stops executing, it stops repainting, so the screen time freezes even though the clock in the Windows taskbar keeps counting. That split, taskbar time moving while screen time stands still, is the quickest confirmation that the fault sits in the runtime and not in the PC.

Can a wrong runtime license cause these symptoms?

No. A licensing problem keeps the runtime from starting at all: the vendor's published guidance ties an invalid runtime license to a startup failure, most often after registering the wrong license for the installed version, on releases before version 6.2 Service Pack 11. A runtime that starts and runs for days before freezing points somewhere else entirely.

Does the two-day interval itself point to a cause?

Not on its own. A repeatable interval suggests the fault accumulates, in retentive data, a counter or a resource, but this case gives no diagnostic code or bulletin naming one. Treat the interval as your acceptance number: the retransferred project has to outlast the old two-day failure window, which is why the verification run is set at four days.

Keep reading

  • How-to

    Replacing an MP277 Touch Panel with a Panel PC

    A Panel PC 677 can replace an MP277, but as a migration, not a swap: retarget a copy of the project with WinCC flexible Advanced (a Powerpack upgrades an existing Standard license), then buy a PC Runtime license sized to the project's PowerTag count. The engineering license on the development PC does not authorize Runtime on the Panel PC.

    HMI and touchscreens

  • Selection guide

    Running Third-Party HMI Software on a Marine Display Host

    Keep the marine monitor: it only displays what the industrial PC host draws, so the software decision belongs on the host. Test whether the installed Infilink runtime can deliver the graphics and the smartphone or tablet access; where it cannot, select a replacement runtime with documented operating-system support, licensing and a Modbus TCP driver, and prove it on an isolated bench before rebuilding screens.

    HMI and touchscreens

  • Selection guide

    How to Prove a PC-Based HMI Before Replacing Panel Terminals

    Use an isolated bench controller to compare candidate PC-based HMI runtimes. Test the read path, one write to a spare test tag, touch response, communication loss and automatic recovery. Check the deployed license on the target PC.

    HMI and touchscreens