Troubleshooting
Why a WinCC 7.3 client reports no start screen
Short answer
A WinCC 7.3 client that reports no start screen has failed to resolve its server-qualified start picture, usually Server::start.pdl. Confirm the launch chain first: SIMATIC Shell shows every station, the client is in the server project's computer list, and the logon account is known on both stations with a non-empty password. When all of that passes, install WinCC 7.3 Update 7; that is what restored the client in the documented case.
On this page
- What does the no start screen message actually tell you?
- Is the start picture qualified as a server picture?
- Do all stations show in SIMATIC Shell on the right network card?
- Which Windows account may run the client?
- Is the client named in the server project's computer list?
- When do you install WinCC 7.3 Update 7?
- How do you apply the update and prove the fix?
- Questions asked
The no start screen message on a WinCC 7.3 client means Graphics Runtime could not obtain a usable picture from the configured reference; it does not prove that the start-screen field is blank. In the documented case — one server, four clients, a server-qualified start picture, and every configuration check passing — installing WinCC 7.3 Update 7 was the change that restored the client. That makes the update the end of the fix, not the beginning: a wrong picture name, a hidden station, an unknown account, or a missing computer entry all produce the same message. Each section below says what to open, what a pass looks like, and what the pass rules out.
What does the no start screen message actually tell you? #
It tells you Graphics Runtime could not obtain a usable picture from the configured reference, so read it as the last link of a resolution chain, not as proof that the start-screen field is blank or that the picture file is missing.
A client resolves a server picture in a fixed order. It identifies the configured server through the imported server package, reaches that server over the WinCC-selected network interface under the Windows security context of the logon, and only then resolves the qualified picture name and opens the PDL. The server prefix on the picture name is part of the resource identity, so a name that is right for a local project is not the same resource. Match the observed condition to the next check:
- Start-screen field empty or naming a local picture by mistake: runtime has no valid launch target. Inspect Graphics Runtime properties.
- Server-qualified name set, but the server is absent from SIMATIC Shell: station discovery or interface selection is failing. Inspect the SIMATIC Shell parameters.
- Server visible, but the package is stale or will not load: the client cannot resolve the packaged server resources. Reload or update the package.
- Package loads, but the Windows identity is rejected: the client reaches the server without the required operating-system access. Compare account, password, and group membership.
- Every check passes and the message persists: the WinCC software level is the remaining cause. Apply the update as shown in the last section and retest.
Is the start picture qualified as a server picture? #
Open Graphics Runtime properties and confirm the start-screen field reads Server::start.pdl, because a bare local name loads a different resource and never exercises the server package, the selected network interface, or the Windows security context.
Confirm also that the picture exists in the server project and is part of what the package delivers. A local-picture test has one legitimate use: if a local picture also fails to open, the fault is in general Graphics Runtime startup rather than in server-picture resolution. A local picture that opens proves nothing about the package, the interface, or the account, so never accept it as the repair. In the documented case this field was already correct, which moved the search to the next links.
Do all stations show in SIMATIC Shell on the right network card? #
Open SIMATIC Shell in Windows Explorer and confirm the server and every client appear; where a station has more than one network adapter, right-click SIMATIC Shell, open its parameters and the redundancy parameters, and select the card WinCC should use.
Visibility proves basic station discovery and nothing more: it does not validate package contents, the picture name, the server's computer list, or authorization. In the documented case all clients were visible, which cleared discovery and interface selection. Visibility also does not re-test addressing after a change, and why a WinCC server IP change freezes all HMI clients covers that separate failure if the server's address ever moves.
Which Windows account may run the client? #
The account needs a non-empty password and membership in Administrators, or at least in Power Users together with SIMATIC HMI, and the server must know that same account with the same password before the client can reach server resources.
In a workgroup, create the same account, with the same non-empty password and the same memberships, on the server and on every client; that is the simplest workable arrangement. In a domain, one account is enough once the server recognizes the logged-on domain account. The documented case ran a single Administrator account, with server and clients on one domain and that domain defined on the clients, and the identity link passed.
An administrative logon alone does not prove that remote WinCC resources resolve under the correct identity, so judge this link by the client actually opening the server picture, not by the desktop appearing. Changing that shared account's password later is its own procedure, and how to manage WinCC runtime user accounts and password changes covers it without surprising running clients. If the domain Administrator cannot open any session on the server at all, the fault sits before WinCC starts, and resolving the domain administrator RDP logon failure covers that path.
Is the client named in the server project's computer list? #
It must be: open the server project and confirm each client's Windows computer name appears in the computer list, matched character for character, because a station missing from that list cannot act as a client of that project.
Compare the configured name against the Windows computer name of the client; a rename or a typo keeps the station out of the project even while discovery works. While the server project is open, check the preferred-server configuration as well: the intended server must be selected for screens and for each required subsystem, alarms included where they are used. In the documented case the client list was already added on the server, so this link passed and the chain pointed beyond configuration.
When do you install WinCC 7.3 Update 7? #
Install it only after every check above passes, because that is the order the documented case followed: the picture was server-qualified, all stations were visible, the client was listed, one Administrator account served one domain, and the message stayed until the update went on.
In that case, installing the update was the single change that made the client open its start screen again. Treat the software level as the last suspect, never the first: every configuration fault above produces the identical message, and patching a station with a wrong picture name or an unknown account changes nothing. The decision is short. A failing check gets fixed first. All checks passing on WinCC 7.3 with the message still present means the software level, and the fix is the update on the affected client.
How do you apply the update and prove the fix? #
Stop WinCC Runtime on the client, back up the project and package files, install the update from the vendor's package with its stated prerequisites, restart as the package requires, and update the server package again before the first runtime start.
Work in this order:
- Record the WinCC 7.3 update level on the server and on every client before changing anything.
- Stop WinCC Runtime on the station being serviced and back up the project and the package files through the site's backup procedure.
- Install WinCC 7.3 Update 7 using the vendor's package and installation instructions; apply the prerequisites and restart it states, not ones carried over from another release.
- Confirm the installed product reports that update level on the serviced station.
- Open the client project and update
SERVER.pkgso the client reflects the current server project. - Recheck the preferred server for screens and alarms, and the start-screen value.
- Start the client under the production Windows account.
Patch inside a planned window: while the station is down its operator has no view of the machine, so keep the other stations in service or arrange coverage before you stop runtime.
Five results prove the repair:
- Station discovery: SIMATIC Shell shows the server and every client through the intended adapter.
- Package state: the package update completes with no load or server-resolution error.
- Launch target: the start-screen field holds the server-qualified value, and the picture exists in the server project.
- Security context: the server recognizes the production account, with the required membership and a non-empty password.
- Runtime result: the server's start picture opens with no message.
Any failing result sends you back to its section. All five passing with the update in place is the state the documented case ended in, and the client kept working.
Questions asked
What if only one client fails while the others run?
Compare that station against a working client: same server package, same account, same update level, same adapter selection. A single failing station points at something local to it, such as its network card choice in SIMATIC Shell, its entry in the server computer list, or its own update level, rather than at the server project, which the healthy clients are proving good.
Must the server and clients run the same WinCC 7.3 update level?
Keep them on the same level. Compatibility of a mixed combination comes only from the vendor's update documentation, so do not treat different update levels as interchangeable: record every station's level first, then align server and clients inside one maintenance window, which removes the question entirely.
Why is an empty password refused even for an Administrator account?
Windows refuses blank-password accounts for network logons by default, so the server rejects the client's request before WinCC ever checks group membership. Administrator rights do not override that policy, and on the client the refusal appears as a start screen that never loads rather than as a password prompt.
Where do you add the SIMATIC HMI group membership?
In the Windows workstation administration on the station that runs WinCC: open the local users and groups console, select Users, and add the account to the SIMATIC HMI group alongside Administrators or Power Users. For a workgroup, repeat it on the server; for a domain, confirm the membership where the domain is administered.