Why a WinCC Flexible project on a server needs the tool on your PC

HMI and touchscreens Published 7 min read

Short answer

The project files can live on the server, but the engineering tool cannot: WinCC Flexible must be installed on the PC you sit at, and Windows Server 2003 cannot host it. In the reported case, Windows 7 Professional and Windows XP Professional clients running WinCC Flexible SP3 opened the server-hosted projects without the message, while matching users and SIMATIC group memberships changed nothing.

On this page
  1. Can a WinCC Flexible project on a remote server be edited from your PC?
  2. Why does WinCC Flexible have to be on the machine you sit at?
  3. Why won't WinCC Flexible install on Windows Server 2003?
  4. Why didn't matching users and the SIMATIC groups fix it?
  5. What setup opened the server-hosted projects cleanly?
  6. Should you put WinCC 7.0 on the server to silence the message?
  7. Can a virtual machine make the server the engineering station?
  8. Which setup should you standardize on now?
  9. Questions asked

Yes — a WinCC Flexible project can stay on a remote server while you edit it, because the project is just files and the engineering tool runs on the PC in front of you. In the reported case, Windows Server 2003 hosted the projects; Windows 7 Professional and Windows XP Professional clients with WinCC Flexible SP3 installed opened them with no message; installing the tool on the server failed as incompatible; and matching users with SIMATIC HMI and SIMATIC NET group memberships changed nothing. What follows is why the tool belongs on the editing machine, which operating systems accept it, and the setup to standardize on.

Can a WinCC Flexible project on a remote server be edited from your PC? #

Yes. The engineering system runs on the client PC and opens the project as ordinary files over the network share, while the server only stores and serves them; in the reported case exactly that arrangement worked.

The phrase "editing remotely" hides two different arrangements. In the first, the tool runs on your client and the project sits on the server: the engineering system reads the project data across the share and writes it back when you save. In the second, you open a remote session onto the server and run the tool there, which requires the tool to be installed on the server — and that is where the reported plant was stuck. The project is a set of files on disk; nothing on the server has to understand them for the first arrangement to work. The text of the message that appeared on the server-side route was never captured, so it is not quoted here; the configuration results below identify the cause without it.

Why does WinCC Flexible have to be on the machine you sit at? #

Because opening a project is more than file access: the engineering system parses the project data, holds it in memory, and rewrites it at save, and only the installed application can do that work.

A remote desktop onto the server does not move that work to your PC — the program still executes on the server, so it still has to be installed there, on an operating system it accepts. The only edits that skip the engineering system are pure data exchanges: recipe values move through a CSV export and import, as described in editing WinCC Flexible recipes from a PC without the engineering tool. Screens, tags, connections and scripts all need the engineering system on the editing machine. And an edit is not finished at save: the changed project must be compiled and downloaded to the panel, the step covered in why an HMI edit needs a new runtime download.

Why won't WinCC Flexible install on Windows Server 2003? #

Because the engineering system is released for workstation editions of Windows, not server editions: the installation on Windows Server 2003 failed as incompatible, and the documented support lists name only client operating systems.

The compatibility overview for WinCC flexible 2008 names Windows XP and Windows 7. The Siemens delivery release for Service Pack 5, WinCC flexible 2008 SP5, names Windows 10 Professional, Windows 10 Enterprise and Windows 10 LTSB Enterprise. Neither list contains a server edition, and a support answer of the same generation gives the matching verdict for Windows Server 2008 SP2: not released, use Windows 7 or a separate machine. The pattern is deliberate — the engineering system is a workstation application — so the decision is firm: never plan a flexible engineering station on a server operating system, and let a server in this architecture play one role, the file store.

Why didn't matching users and the SIMATIC groups fix it? #

Because compatibility is not a permission problem: group membership decides who may log in and who may use communication functions, and no group makes an installer accept an operating system it rejects.

In the reported case, creating the same user account on the client and the server and adding it to SIMATIC HMI and SIMATIC NET produced no change — expected, since the blocker was the installation on the server, not access to the files. The vendor's documentation for WinCC V7.5 shows what the SIMATIC HMI group is for: a user must sit in that group for the login to permit access to WinCC, an access rule rather than an installation rule.

Membership problems do cause real faults elsewhere in the family — in the WinCC 7.0 SP3 generation, a domain membership problem produces an unspecified error when a new project is created — but that is a defect with a documented resolution, a different mechanism from an operating-system rejection. Tell the symptoms apart: a permissions fault appears at the share as access denied, a compatibility fault appears at installation or launch.

What setup opened the server-hosted projects cleanly? #

The reported working setup is a Windows 7 Professional or Windows XP Professional client with WinCC Flexible SP3 installed, opening the project from its network path on the server share; with that, the message no longer appeared.

Reproduce it as a worked procedure, and accept a client only when every step passes:

  1. Copy the project on the server before the first open from a new client; that copy is the rollback if an open or a save goes wrong.
  2. Sign in with an account that holds read and write rights to the share, and prove the write right by creating and deleting a scratch file in the project folder.
  3. Open the project from its network path, for example \\filesrv01\hmi-projects\line3, not from a local copy.
  4. Confirm the project opens with no message.
  5. Make one controlled edit, a tag comment or a static text, save, close, and reopen from the same client to prove the write path.
  6. Compile the result and run it on a bench station first — the procedure in running a WinCC flexible 2008 project in PC Runtime — before any download to the production panel.

The reported outcomes behind that procedure:

Configuration Reported result Decision
Windows 7 Professional client, WinCC Flexible SP3, project on the server Opened cleanly Standard setup, keep it
Windows XP Professional client, WinCC Flexible SP3, project on the server Opened cleanly Works, but move off that OS at the next hardware change
WinCC Flexible installed on Windows Server 2003 Installation failed as incompatible Do not attempt
Matching users added to SIMATIC HMI and SIMATIC NET No change Not a fix for compatibility

Should you put WinCC 7.0 on the server to silence the message? #

No. Treat the reported disappearance of the message after a WinCC 7.0 installation on the server as an unexplained observation: nothing in the report identifies which installed component changed the behavior, and the working editing path never needed anything installed on the server.

Deploying an extra SCADA package on that machine to imitate the report buys nothing and adds a second system to maintain on hardware that should be a plain file server. If the message appears on a client that follows the procedure above, diagnose that client — its installation and its share rights — instead of loading software onto the server.

Can a virtual machine make the server the engineering station? #

In principle, yes: a virtual machine with a supported guest system can host the engineering tool and be reached by remote session, but the report only proposed that route, never tested it, and the Server 2003 machine is the wrong host to build it on.

If the plant wants central engineering sessions rather than installed clients, the sound architecture is a current hypervisor running a guest operating system from the supported lists — Windows 7 for the SP3-era tool, a Windows 10 edition for WinCC flexible 2008 SP5 — with the engineering system inside, accepted by the same open, save and reopen test. For a plant with a handful of flexible projects, installed clients are simpler to maintain, and that is the committed recommendation; a virtual engineering station earns its keep only where clients cannot be installed at all.

Which setup should you standardize on now? #

Standardize on this: projects on a file server, WinCC flexible 2008 SP5 installed on every editing client running one of its documented Windows 10 editions, and the open, save and reopen check as the acceptance test for each new client.

SP5 is the final service pack of the flexible 2008 line and the only one released for Windows 10, so it is the engineering system for new client hardware; the Windows XP and Windows 7 clients from the report run operating systems that no longer receive updates and are not a plan. When the Server 2003 machine retires, copy the project share to a current file server — the engineering system does not care which Windows file server hosts the share, and the same acceptance test proves the move. The decisions, collected: keep the projects on the server, keep the tool on the client, never install the engineering system on a server operating system, treat group membership as an access matter only, and leave the WinCC 7.0 observation out of the design.

Questions asked

Can two engineers edit the same server-hosted WinCC Flexible project at the same time?

No. WinCC flexible has no multi-user engineering and no merge of concurrent edits, so two stations saving the same project overwrite each other's changes. Keep one editor on a project at a time, or hand out copies and fold the changes back by hand. Multi-user engineering belongs to TIA Portal; WinCC flexible never gained it.

Can WinCC 7.0 open or edit WinCC Flexible projects?

No. WinCC 7.0 belongs to the WinCC V7 line, a PC-based SCADA system with its own project format, while WinCC flexible serves operator panels and PC Runtime with a different format. Neither program opens or edits the other's projects, so the reported change after that installation cannot have been project conversion; it stays an unexplained environment effect.

Does the editing PC need SIMATIC NET installed to reach the project on the server?

No. Opening and saving project files across the share is ordinary Windows file sharing, so what matters is that the editing account holds read and write rights to the project folder. SIMATIC NET is the vendor's communication stack for PLC and network connections; file access to the project folder does not pass through it.

Should Windows Server 2003 stay as the project file server?

It can keep serving files, but do not invest in it. Extended support for Windows Server 2003 ended in July 2015, so plan the move of the project share to a current file server or NAS. The engineering system does not care which Windows file server hosts the share, so the migration is a file copy plus the same open, save and reopen check.

Keep reading

  • Troubleshooting

    Why a WebIQ Project Link Loads on the PC but Not the HMI Screen

    No universal WebIQ link exists: a browser HMI loads only when the screen has a routed path to the WebIQ server, at http[s]://{SERVER HOSTNAME OR IP}:{LISTENER PORT}/{FOLDER NAME OF PROJECT}/. When the link works on the PC but not the screen, fix the address, subnet, listener binding or routing — in that order.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC flexible Runtime Cannot Control an S7-1200

    WinCC flexible Runtime on the PC is a separate HMI station, not a view into the MP277, so a working panel proves nothing about the PC path. Ping the S7-1200 from the Runtime PC, confirm the project connection uses the S7Online access point, then map that access point in Set PG/PC Interface to the adapter that reaches the real PLC, or to the simulation path when PLCSIM is the destination.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Flexible transfer to a TP177B PN/DP fails instantly

    The error appears instantly and identically with or without the panel and cable attached, so WinCC Flexible 2008 stops while opening the local interface, before any message reaches the TP177B. Use the PC Adapter USB 6ES7 972-0CB20-0XA0 instead of the serial cable through a converter, assign its entry in Set PG/PC Interface, activate the matching data channel on the TP177B 6AV6 642-0BA01-1AX1, and start the transfer again.

    HMI and touchscreens

Change the HMI screen from the PLC in WinCC Unified