IMDTouchKnowledge BaseShop main store

Troubleshooting

Why a WinCC standby server downloads a master-named folder

HMI and touchscreens Published 10 min read By IMDTouch engineering team

Short answer

A correct OS download generates the project folder under the standby host's own name, so a folder named for the master means the target identity or the SIMATIC HMI share and Security permissions are wrong. Read the load log entry that names the computer the project was changed to, fix the target definition or the rights it exposes, then download again. Renaming the folder by hand is a symptom mask, not a repair.

On this page
  1. Why does a download to the standby server create a folder named for the master?
  2. Which load log entry decides whether the standby download is correct?
  3. What must the download target on the engineering station point to?
  4. Which account rights does the standby download need?
  5. Which share and Security permissions must the target folder carry?
  6. Is renaming the downloaded folder to the standby's name a valid fix?
  7. Why can clients still not change screens after failover to the standby?
  8. How do you prove the standby is repaired before it goes back in service?
  9. Questions asked

A standby WinCC server that starts only after you rename its downloaded project folder is not repaired — it is reporting that the OS download finished the file copy but applied the wrong computer identity, or was stopped before it could apply the right one. A correct download to the standby generates the folder under the standby host's own name and closes the load log with an entry that names that host. This article reads that log step by step, then walks the four things a Windows rebuild on a redundant standby breaks: the engineering station's target definition, the Security Controller settings, the download account's SIMATIC HMI membership, and the share and Security permissions on the target folder. The manual rename is treated throughout as a symptom to read, never as the repair.

Why does a download to the standby server create a folder named for the master? #

During a correct OS download the engineering station transfers the project, generates its server data, closes it and changes the project computer name to the target host, so a folder named for the master means that final identity step ran against the wrong name.

An OS download is not a file copy with a name attached. The engineering station locks the project, transfers the whole WinCC project to the runtime OS, opens it, updates the picture tree, generates the server data, closes the project, locks it again and only then changes the computer name stored inside the project to the target host. That closing step is what makes the folder generated on the target carry the target host's own name.

The worked case behind this checklist: a redundant server pair on a PCS 7 project with a CPU 417-5H, the master named 00-ser-01 and the standby named 00-ser-02, healthy until Windows and WinCC were reinstalled on the standby. The download addressed to the standby then produced a folder named 00-ser-01; Runtime would not start from it, and renaming the folder made Runtime start. That pattern pins the fault to one step: the files arrived intact, but the identity written into them belongs to the master. Two things decide that identity — the target the engineering station addresses and the rights that let the closing steps run — and the load log in the next section tells you which one failed.

Which load log entry decides whether the standby download is correct? #

The deciding line is the tenth of the twelve log entries a complete OS download writes: "The computer name was changed in the project" followed by the host name, and on a healthy standby download it names the standby host, never the master.

Open the OS project on the engineering station, right-click the OS under WinCC Appl and select Display load log. A finished file copy proves nothing on its own, so hold the download against every step of this sequence:

  1. "The project was locked" — the download took the project lock before touching anything.
  2. "The entire WinCC project will be transferred to the runtime OS" — the whole project crossed, not a partial set.
  3. "The target directory can be read and written to" — the standby folder accepted writes.
  4. "No project is open" — nothing on the target blocks the load.
  5. "The project was opened successfully" — the copied project opened.
  6. "The picture tree was updated" — the entry carries the update's processing time.
  7. "Server data were created successfully" — server data were generated for this target.
  8. "The WinCC project is being closed" — a clean close before identity processing.
  9. "The project was locked" — the second lock, taken before the name change.
  10. "The computer name was changed in the project" followed by the host name — the deciding entry; it must name the standby host, not the master.
  11. The project lock is removed.
  12. The download is reported as completed.

Where the sequence stops names the branch. A stop at steps 1 through 4 is an access fault: the account or the folder refused the download, and the next two sections clear it. A stop between steps 5 and 9 means the project would not open or regenerate on the target; rerun the security settings and make sure no other session holds the project. A complete log whose step 10 names the master is an identity fault: the engineering station applied the wrong computer to a transfer that otherwise worked. A complete log naming the standby host, with Runtime opening on its own, leaves only the failover test at the end of this article.

What must the download target on the engineering station point to? #

The OS object's download target on the engineering station must address the standby host and only the standby host, so compare the Windows computer name on the rebuilt machine with that target character for character before trusting any other check.

Leading zeros, the hyphen and the case all count; reusing the hardware does not preserve the name, and a target that still says the master sends every download to the wrong identity before any file moves. Then inspect the destination itself: in the OS project, open the OS object under WinCC Appl, read the configured target host and folder, and browse to the standby's resource from that dialog. If the browser resolves the master, or offers a master-named destination, correct the selection there — a target pointed at the master is the most direct cause of a master-named folder on a standby that did receive the files. If the standby's resource cannot be browsed at all, the fault is access rather than identity, and the folder-permission section below is the next stop.

Decision: once the target reads the standby host and its folder opens from the dialog, run a complete OS download and watch the folder it generates, touching nothing by hand.

Which account rights does the standby download need? #

The account that performs the download needs membership of the SIMATIC HMI user group, and administrator rights on their own do not satisfy that requirement, so verify the group membership and rerun the security settings after every Windows rebuild.

A rebuild resets local accounts, group memberships and access-control entries even when the host name survives, so reapply the security configuration on all three machines: Start > Siemens Automation > Security Controller > Repeat settings, run on the engineering station and on both OS servers. The documented bar for users is Administrator or User rights plus SIMATIC HMI membership, and the membership is the right the transfer actually checks, together with the effective read and write access it grants on the target folder. If the account lacks the membership, correct it, sign out and back in under that account so the new rights take effect, then rerun Repeat settings before the next attempt.

Decision: with the right account in place, the load log should clear steps 1 through 4; a stop that persists past the transfer points at the folder, not the account.

Which share and Security permissions must the target folder carry? #

The target folder must give the SIMATIC HMI group read and write access at two separate layers, in the share Permissions list and on the Security tab, because either layer alone can leave the download with a read-only destination.

On the standby, create or select the target folder and give it the name you intend to download into. Open Properties, then Sharing, then Advanced Sharing, share the folder and open Permissions: the SIMATIC HMI group needs read and write there. Then open the Security tab of the same Properties window and grant the same group read and write at the filesystem layer. The two layers are checked separately and both must pass: share permissions govern access over the network path the engineering station uses, Security permissions govern the files underneath, and effective access is the combination, so a generous share over a restrictive folder still behaves as read-only to the download. The same split — share versus NTFS folder permissions deciding what a program may do to files — is what NTFS folder permissions control whether applications can delete files works through for image files.

Decision: with both layers granting the SIMATIC HMI group read and write, the log's directory-access step should pass, and nothing after it has a reason to block.

Is renaming the downloaded folder to the standby's name a valid fix? #

No — a rename that makes Runtime start proves only that the copied files are usable, while it leaves the project computer entry, the generated server data, the redundancy configuration and every client assignment exactly as wrong as the download left them.

A rename changes one thing, the name of a directory on disk, and it has to be repeated after every download, because the next download regenerates the folder under the identity the project carries. The workaround becomes permanent maintenance and hides which step of the log is failing. Renaming across a network share is itself a permission-gated operation, needing the right to create one directory entry and remove another — the mechanics behind rename errors on network folders in other automation software.

Decision: keep no renamed folder in service. Fix the identity or the rights the load log exposed, download again, and accept the result only when the download itself generates the standby-named folder.

Why can clients still not change screens after failover to the standby? #

A clean download and a running standby Runtime do not make failover work, because each client switches screens through the server data in its own project, and that project must list the standby as an assigned OS server.

The follow-on symptom to watch for fits that rule: the download is now clean and Runtime runs, yet when the master drops, the clients on the standby read values but cannot switch pictures. Runtime running on the standby is a server-side fact; switching screens is a client-side function driven by the server data in each client's project. On the client, under WinCC Appl, check the OS Server assignment, make sure the standby is listed alongside the master, and download the client project again, because server data reach a client only through its own download. Check the network path as well: a Windows rebuild can hand the standby a new address, and clients still holding the old one freeze in exactly the way why a WinCC server IP change freezes all HMI clients describes.

Run the master-failure test in a window agreed with operations, because stopping the master on a live plant changes what every connected operator station displays.

Decision: clients that switch screens and keep writing through the standby during a planned master stop close the case.

How do you prove the standby is repaired before it goes back in service? #

The repair is proven only when a full OS download generates the standby-named folder by itself, Runtime opens from that folder without any rename, and a planned master failure lets every client switch screens and keep writing through the standby.

Run the acceptance in order and stop at the first failure, because each step depends on the one before it:

  • A full OS download whose load log completes all twelve steps, with step 10 naming the standby host.
  • Runtime opening from the folder the download generated, with no rename performed anywhere in the sequence.
  • A planned master stop in the agreed window, with every client switching screens and writing through the standby.
  • The master returned to service, resynchronizing and taking the stations back without a second download.

Those steps close each case this article opened. A folder named for the master after a download is an identity fault: correct the engineering station's target and download again. A log that stops within the first four steps is an access fault: grant the SIMATIC HMI right, rerun Repeat settings and clear the share and Security layers on the folder. A clean download with broken failover is a client fault: correct the server data in each client project and download the client. None of the three cases ends in a rename.

Questions asked

Does the standby server need its own download, or does redundancy copy the project across?

Each server in a redundant pair receives its own download; redundancy synchronizes runtime data in operation but never replaces a download. The vendor redundancy documentation requires a separate download on both the master and the standby server when a redundant plant is upgraded during operation, so plan two full downloads for every project change.

What does the error "An error occured while changing the computer name in project" mean?

It is a documented OS download error: the transfer reached the final identity step and could not complete the computer-name change inside the project. Work the same four checks as for a master-named folder — the target definition, the Security Controller settings, the SIMATIC HMI right, and read and write for that group at both the share and the Security layer.

Why did a fresh Windows and WinCC install clear the fault on the standby?

A fresh install rebuilds the local accounts, group memberships and access entries a rebuild had wiped, which is why a recovery that repeated the Windows and WinCC installation with a new administrator account has been reported to clear this fault. Treat that as clearing the path, not as the fix: the acceptance is still a download whose log completes with the standby's name at the identity step.

Can the same account install the server software and run the download?

Install the server software while signed in with an account that has administrator rights, then run downloads under an account holding the SIMATIC HMI right. The two can be the same person, and often are, but the download checks the SIMATIC HMI membership and its effective read and write on the target folder, not the administrator badge alone.

Keep reading

  • Troubleshooting

    Why a WinCC server IP change freezes all HMI clients

    Treat the synchronized freeze as a server-side fault with two leads: pin the process server to its fixed address instead of dynamic addressing, and find any add-on such as OPC software running on a demonstration license whose documented runtime limit matches the interval between freezes. Rebooting only resets the running session. Run the server without its SCADA software to rule the machine itself in or out.

    HMI and touchscreens

  • Explainer

    Does SCADA need a master and slave PLC to run

    No. A single S7-300 with one WinCC station is a complete SCADA system for one boiler: the PLC runs control and interlocks, WinCC supervises, and web clients only display. A master and slave PLC pair is needed only when two controllers must exchange data or share one polled serial network.

    HMI and touchscreens

  • Troubleshooting

    Replacing RSView32 DDE Server Links for Excel Reports

    FactoryTalk View SE supports legacy DDE only as a client, so it cannot serve the values your Excel reports request the way RSView32 did. The working replacement is a script that pushes each mapped tag into its report cell, proven one tag-to-cell pair at a time. Keep the old workbook as the mapping record and never let a failed read write a zero.

    HMI and touchscreens