Why AD short-name logon needs the default domain feature

HMI and touchscreens Published 6 min read

Short answer

A successful Active Directory import does not enable short-name logon. On WinCC Unified V19 Update 5 with UMC V2.15.3, a Windows-backed account must be entered as DOMAIN\username at both the UMC Web UI and the runtime. The option to omit the domain prefix for the default domain is documented from WinCC Unified V21 Update 1, so the upgrade is the supported path; alias fields and config-file edits are not substitutes.

On this page
  1. What a successful import does and does not prove
  2. The version boundary
  3. Three attempts that separate the questions
  4. What is not a V19 substitute
  5. The decision
  6. Questions asked

A bare short name for an Active Directory account is rejected on this installation by design, not by a misconfiguration. With the engineering project and the Unified Comfort Panel both running WinCC Unified V19 Update 5 and UMC V2.15.3 handling central user management, an AD-backed user must be entered as DOMAIN\username at both the UMC Web UI and the runtime login. The feature that supplies the domain for you — default-domain short-name logon — is documented beginning with WinCC Unified V21 Update 1, so no setting on the V19 panel, the UMC server or the server's config files produces it. This article separates the two behaviors, gives a three-attempt test that proves which one is in play, and ends with the decision for each case.

What a successful import does and does not prove #

UMC is the central server that manages logins: users and groups are created through its web interface or imported from Microsoft Active Directory. That import is provisioning. It proves the account and its group relationships are known to UMC. Authentication is the separate step that validates the credentials entered at a login field. With Windows authentication, that validation is delegated to the directory, and the directory resolves an account only inside a domain context. A bare name omits the context. Something in the product has to supply it before the credentials are checked, and the component that supplies it is the runtime version, not an import setting. That is why AD provisioning can import every user and group correctly while the short name still fails at the login field.

The version boundary #

Siemens documents the change in the Unified Comfort Panel user-management documentation, entry ID 109961591: beginning with Unified V21 Update 1, the domain prefix for the default domain is no longer required. The same release adds the combined use of local user management and UMC-based central management on Unified Comfort Panels, so an upgrade moves both the name handling and the configuration model. Note the limit of the feature: it covers the default domain only, and the V21 documentation still directs you to enter the domain as a prefix in some automated paths, such as automatic logon configured in SIMATIC Runtime Manager under its settings. Read the V21 configuration pages for the specific field you automate rather than assuming the prefix is gone everywhere.

Release Bare short name, default-domain AD user Working form
V19 Update 5 and earlier Rejected at runtime and Web UI DOMAIN\username
V21 Update 1 and later Accepted, prefix no longer required username; qualified form still accepted

Three attempts that separate the questions #

Work the example with concrete names. Take a site whose default domain is PLANT1 and an operator account jsmith. The three name forms in play look like this:

PLANT1\jsmith
jsmith@plant1.example
jsmith

The first line is the qualified form, the second is the UPN form, and the third is the bare short name. Run the tests on an isolated bench with a known-valid password, one authentication method at a time, because Password Authentication and Windows Authentication are separate routes and a pass through one cannot be credited to a setting meant for the other:

  1. UMC Web UI, enter PLANT1\jsmith with the valid password. Expected result: logon succeeds. This proves provisioning and the authentication path.
  2. Unified runtime login, same account and password. Expected result: logon succeeds. This proves the runtime path independently of the Web UI.
  3. Runtime login again, bare jsmith, same password and method, nothing else changed. Expected result on V19 Update 5: rejection.

That third result is the decision point. When tests 1 and 2 pass and test 3 fails, nothing is broken — the V19 runtime does not supply a default domain, and the rejection is a version-capability result. Record it as unavailable on the current release in the commissioning record, not as a provisioning fault, so a later reviewer does not reopen a healthy directory integration.

If the qualified form fails instead, the fault precedes any short-name question: check credentials, account state, group mapping in UMC, connectivity to the authentication service and the method actually selected. Do not change multiple settings to compensate for a failed baseline.

What is not a V19 substitute #

Three settings look like candidates and none of them is documented as one for this version pair:

  • The Authentication alias field. No documentation for UMC V2.15.3 defines it as default-domain expansion for Windows password authentication. An alias may serve another identity-selection workflow; its presence in an account record proves nothing about which method consumes it. Alias-driven logon does exist on Unified panels as a different feature — a PLC can switch the logged-in user by alias, as described in the article on PLC triggered user login by alias on a unified panel — but that is a runtime identity switch, not a substitution of one name form for another.
  • Flex authentication. Enabling it is not documented to make a bare name equivalent to the qualified form, and no documented restart or re-provisioning cycle changes that. Return flex-related settings changed only in pursuit of short names to the project baseline.
  • add_alias_to in piisrv_config.json. Its accepted values, target field and effect on existing accounts are not defined in the documentation for this installation. Editing it by trial on a commissioned UMC server is an uncontrolled configuration change that blurs the line between identity import and credential validation. Leave it untouched.

Treat the UPN form the same way on V19: unproven for this scenario, so not something to build operator training around.

The decision #

On V19 Update 5 with UMC V2.15.3, keep the qualified form: operators enter DOMAIN\username at the Web UI and the runtime, and the bare short name stays recorded as a version limitation. Revert any alias, flex or config-file changes made while chasing it, then re-run the three-attempt test to confirm the baseline still passes.

If short-name logon is a requirement rather than a convenience, the supported path is upgrading the engineering system and the panel to V21 Update 1 as one controlled version change, not a UMC field edit. The panel side of that change is an image update, and the article on Unified Comfort Panel image updates when two versions are needed covers keeping two image versions straight during the transition. After the upgrade, re-run the same three attempts: the bare name should pass on the default domain while the qualified form continues to work, and automatic-logon fields that still expect the prefix should be configured as the V21 documentation directs. Domain-backed logon on the classic Comfort panel line is a separate SIMATIC Logon setup, described in the Simatic Logon domain authentication setup guide for WinCC Comfort panels at https://industrialmonitordirect.com/blogs/knowledgebase/simatic-logon-domain-authentication-setup-for-wincc-comfort-panels, if your site runs both panel generations.

One safety note: make these changes on an isolated bench or during a planned stop, and confirm that every operator role still reaches only the functions its provisioned groups grant before the machine returns to production.

Questions asked

Does enabling flex authentication let AD users log on with a bare short name?

No. Nothing in the documentation for this version pair states that flex authentication makes a bare name equivalent to the domain-qualified form, and no restart or re-provisioning cycle changes that. Flex authentication is a separate method with its own documented procedure. If you enabled it only to chase short names, return it to the project baseline and treat the name handling as a runtime-version question.

Is UPN format accepted instead of DOMAIN\username on V19 Update 5?

Nothing in the version documentation for this setup confirms UPN acceptance on the V19 runtime or Web UI, so do not train operators on it. The qualified domain-prefix form is the only format you can rely on here. If UPN matters for your directory, test it on an isolated bench with a known-valid account and record the result before depending on it.

Which component owns the short-name capability, UMC or WinCC Unified?

The runtime does. The change that removes the domain prefix for the default domain is documented on the WinCC Unified side from V21 Update 1, not as a UMC version feature. After an upgrade, check that the engineering project and the panel both report the new release; a UMC version number alone proves nothing about which name forms the login fields accept.

Can local accounts and UMC domain accounts coexist after the upgrade?

Yes. The same V21 Update 1 release that adds default-domain short-name logon also allows the combined use of local user management and UMC-based central user management on Unified Comfort Panels. That means you can upgrade for the login behavior and keep the local account structure your OEM or service users depend on, configured per the V21 user-management documentation.

Keep reading

  • Explainer

    Why a KTP600 Basic DP needs a PC Adapter USB A2 for transfer

    A KTP600 Basic Color DP has no Ethernet port, so its project cannot be loaded through the S7-1200's Ethernet connection: the CM 1243-5 is a DP master for process data, not an engineering gateway. The documented path is a PC Adapter USB A2 (6GK1 571-0BA00-0XA0) on the panel's PROFIBUS socket, with transfer channel, baud rate and station addresses matched. The USB/PPI Multi-Master Cable is a different adapter for the S7-200 world.

    HMI and touchscreens

  • Troubleshooting

    PlantPAx faceplate display not found at runtime creation

    Runtime creation fails with display not found because the PlantPAx faceplate button computes a display name that matches no display in the project. With HMI_Lib = P and HMI_Type = Motor, the expression builds "(P-ME) Motor-Faceplate", not the P_Motor-Faceplate you named. Compare the computed string against the display list character by character, rename the display to the computed name, and rebuild the .mer.

    HMI and touchscreens

  • How-to

    Displaying a Do-More String on a C-More EA9 Panel

    Use the C-More EA9 Dynamic Text object bound to the Do-More short-string tag, and give it a trigger tag that is on whenever the text should update: ST1, the always-on Do-More system bit, works immediately, while a page C-Bit set on at page open and off at page close in the Event Manager ties the display to the open screen.

    HMI and touchscreens