IMDTouchKnowledge BaseShop main store

Troubleshooting

Why an HMI loses contrast in the center of the display

HMI and touchscreens Published 7 min read

Short answer

A light patch that keeps the same position on every screen and barely reacts to the contrast control is a fault in the panel's display cell or backlight, not in the project. Confirm it on the firmware start-up screen, then replace the panel, saving the project and its ProTool or WinCC flexible origin first.

On this page
  1. Why is my HMI screen light in the middle and clear at the edges?
  2. Is the contrast setting causing the washed-out center?
  3. How do I prove the patch is the panel and not the project?
  4. What fails inside an STN display to cause a light patch?
  5. Will a TP700 Comfort swap straight in for a TP177?
  6. What should be saved before the old panel comes off the door?
  7. How do I accept the replacement once it is wired?
  8. Questions asked

A light patch that sits in the same physical spot on every screen and barely reacts to the contrast control is a fault inside the panel itself — the display cell or its illumination — not in your project. On a unit like the TP177-PN/DP-6CST, a 6-inch STN panel, no setting, re-download or screen edit will remove it, so the repair is a replacement panel and the real work is protecting the project during the swap. The two tests below prove the diagnosis, and the closing sections give the order of work for moving to a TP700 Comfort: source first, migration path second, old panel off the door last.

Why is my HMI screen light in the middle and clear at the edges? #

Because the liquid-crystal layer is no longer holding uniform contrast across its area: a fixed light patch at the same spot on every page is produced by the display hardware, and the project only decides what is drawn, not how evenly it shows. The pattern that defines this fault has three parts, and each one eliminates a different suspect:

Observation What it eliminates
The patch sits in the same physical area on every screen page A screen object, graphic or page background — those move or vanish between pages
The outer area stays clear while the center is washed Uniform aging, such as a lamp at end of life, which dims the whole image or one edge
The contrast control changes the image only slightly A wrong setting, which would pull the patch and its surroundings back together

Read the three together and the decision is made: stop editing screens, stop reloading the project, and treat this as hardware.

Is the contrast setting causing the washed-out center? #

No: the contrast control shifts the drive voltage for every pixel at once, so it lightens or darkens the whole image together, and a patch that stays lighter than its surroundings at both extremes of the adjustment cannot be a setting. Run the check once, properly, in the panel's on-device settings where the display adjustment lives:

  • Set the contrast control to one end of its range and look at the patch against a clear area next to it.
  • Set it to the other end and compare again.
  • Watch whether the patch and the background ever merge into one shade.

On this fault the two move together and never merge: you get a minor global change and the same relative difference. Record the value you found, put it back, and stop adjusting — the control is ruled out, and a panel left at a random contrast value is harder for the next technician to judge.

How do I prove the patch is the panel and not the project? #

Power-cycle and watch the start-up screen: the splash image is drawn by firmware before any project loads, so a light patch already visible there places the fault in the display and ends project debugging in one look. Two more checks make the case complete:

  • Open at least three very different pages — one mostly dark, one mostly light, one dense with objects — and confirm the patch holds the same shape and position on all of them.
  • Photograph a page filled with a single background color, straight on, and compare the patch against a clear area.

Illustrative worked example, not a measurement of your unit: on the single-color photo, the middle of the patch samples at 210 and a clear corner at 180 on the 0–255 brightness scale. The offset is 210 − 180 = 30 levels, and 30 ÷ 255 ≈ 0.12, so about 12% of the scale. The project painted that field with one color, so the offset belongs to the glass, and no tag, script or conversion will close it. With the splash screen, the fixed position and the sampling all agreeing, the diagnosis is closed: replacement.

What fails inside an STN display to cause a light patch? #

Two candidates remain, and both live behind the glass: the liquid-crystal cell and its polarizers, which haze or stain with age and heat cycles, or the illumination, although a failing CCFL tube shows as a dark band from an edge rather than a light patch in the middle. That second point settles the diagnosis: this generation of panel is lit by a cold-cathode lamp, and lamps fail by dimming, so a washed center that survives both contrast extremes points at the cell, not the lamp.

Which of the two it is does not change the decision, because on a panel this size neither the cell nor the lamp is a field-replaceable spare: the display is a sealed unit and the serviceable item is the whole panel. Until the swap, run normally — the patch is a readability problem, and the HMI is an operator interface, not a safety device, so no safety function depends on that glass.

Will a TP700 Comfort swap straight in for a TP177? #

No: the TP700 Comfort is a 7-inch TFT unit engineered with WinCC in TIA Portal, while the TP177-PN/DP-6CST is a 6-inch panel from an earlier generation, so the swap is a project migration plus a new cut-out, not a like-for-like substitution. For the pair in question — a TP177-PN/DP-6CST, order number 6AV6642-0BA01-1AX1, and a TP700 Comfort, order number 6AV2124-0GC01-0AX0 — three things change at once:

  • Engineering tool. The old project comes from ProTool or WinCC flexible; the new panel is engineered with WinCC in TIA Portal.
  • Opening. A 7-inch unit will not drop into the cut-out of a smaller frame, so compare the new panel's dimensions and depth against the existing opening with the panel cut-out reference before the spare is committed.
  • Network. The old designation ends in PN/DP, so the machine may use PROFIBUS DP or PROFINET at the HMI; Comfort panels come in PROFINET and PROFINET/DP variants, and the datasheet of the exact order number decides which one the machine needs.

Treat the spare as a migration with engineering time, not a bolt-on: budget the conversion, the cut-out work and the network check before the old panel is touched.

What should be saved before the old panel comes off the door? #

The project source and a recoverable backup, in that order: a panel that still runs can still give up its data, and once it is unplugged every recovery gets harder, so nothing leaves the door until the source is safe. Work through this list in order:

  • Find the source on the engineering PC or its backups and identify which tool created it, ProTool or WinCC flexible — the migration path forks on that answer.
  • If no source turns up, pull what the device holds over its backup route first; the difference between a restore image and an editable source, and the steps for each, are covered in HMI replacement: recover the project before converting.
  • Record the panel's settings by hand: network address, bus parameters, the contrast value you found, and any recipes or user lists in use.

The path itself: a WinCC flexible project, including one integrated in a STEP 7 project, migrates directly into WinCC (TIA Portal), while a ProTool project goes to WinCC flexible first, on the route in how to migrate a ProTool HMI project to a new touch panel. Confirm you hold a TIA Portal version that supports both the migration source and a Comfort target before the old unit is removed, as described in checking HMI engineering software before a panel replacement.

How do I accept the replacement once it is wired? #

With a full function check against the machine, because a migrated project compiles without proving it behaves: accept only when the display is uniform corner to corner and every operator action, alarm and controller value works on the new panel. Run the checks in this order and write down each result:

  • Display: open a single-color screen and confirm the field is even from corner to corner — the reverse of the tests that diagnosed the fault.
  • Pages: open every screen and look for graphics, fonts or symbols lost or shifted in conversion.
  • Inputs: enter one value and toggle one bit from each screen family, and confirm them in the controller, not on the HMI's own display.
  • Alarms: force one alarm, confirm it appears, and acknowledge it.
  • Communication: on an isolated bench, pull the controller connection and watch the fault behavior, restore it and confirm the values resume, then power-cycle the panel and confirm the project restarts on its own.

The replacement is accepted when the patch is gone and every line of that list has a result next to it — until then, keep the old panel on the shelf as the fallback.

Questions asked

Does heat make the washed-out center worse?

STN contrast is temperature dependent, so the patch often looks worse on a hot afternoon or after hours of running and improves when the panel is cold. That shift is a property of the failing cell, not a clue to a setting, and it also tells you the condition will keep drifting with heat cycles until the panel is replaced.

Is the light patch image sticking or burn-in?

Image sticking is a faint ghost of a screen that was displayed for a long time, and it usually fades over hours or days of varied content. A washed patch that never fades and already shows on the start-up screen is a hardware fault instead. Re-downloading the project fixes neither, but only the ghost can recover on its own.

Can the machine keep running until the replacement arrives?

Yes, as long as the values and alarm rows inside the patch stay readable, because the fault is in the glass, not in the controller or the project logic. Watch whether the patch grows week to week, and treat the first unreadable measurement as the signal to schedule the replacement rather than guessing at what the screen shows.

Why does the patch stay in the same place when the screens change?

Every pixel is a physical cell at a fixed position, so damage in the cell layer keeps its location no matter what the project draws over it. Graphics move between screens because the project repaints them; the patch does not move, and that difference is the core of the diagnosis.

Keep reading

  • Troubleshooting

    PanelView 1000 No Display or Dark Screen Troubleshooting

    If your PanelView 1000 screen is lit but the application is invisible, look at it at a steep angle: an image you can trace means intensity or contrast was turned down, so raise it in Configuration mode before ordering parts. If part of the lit area is dark, the lamp is failing; if the controls are already at maximum, replace the lamp before suspecting the inverter. A PLC reset fixes none of this.

    HMI and touchscreens

  • Selection guide

    Choosing the Right HMI Panel Screen Size for the Job

    Match the diagonal to the operator's task: 3–7 in for localized control, 7–15 in for standalone machines, and 15–24 in or larger for complex process overview. Then verify viewing distance, resolution against physical size, touch targets, enclosure cutout, and application compatibility before committing.

    HMI and touchscreens

  • Troubleshooting

    HMI Screen Goes Blank for Seconds Then Recovers

    A blank of a few seconds that recovers on its own, and survives a project reload, points first at a PLC-controlled backlight, screen-saver or visibility tag being overwritten at runtime. Separate backlight loss from a panel restart by checking the rear status LEDs and tracing the tags the Reset action writes before swapping hardware.

    HMI and touchscreens