Why an HMI shows communication error popup 40001 on the bench

HMI and touchscreens Published 5 min read

Short answer

The Communication Information 40001 window is the panel's system prompt for failed driver polls, so it repeats on any bench run with no PLC connected. Disable Show System Prompt under GlobalSet, System Setting in DTools Pro 1.10, compile and download, and the popup stops while screens and macros keep working. For anything that ships, keep the prompt or handle the link status with your own alarm logic, because a suppressed popup silences a real lost link.

On this page
  1. What the Communication Information 40001 window is
  2. Turning Show System Prompt off in DTools Pro 1.10
  3. The LW9296 suppression bit, and what DTools Pro does with it
  4. Choosing between the two methods
  5. Bench popup or real link fault
  6. A 30 second bench proof on a G2100E with no PLC attached
  7. Questions asked

A Communication Information 40001 window that keeps coming back on the bench is not a download fault. It is the panel's own system prompt for a failed driver poll, and with no PLC connected every poll fails, so the window returns as fast as you dismiss it. The fix confirmed on a Kinco G2100E running a project from DTools Pro 1.10 is a single setting: open GlobalSet, select System Setting, disable Show System Prompt, then compile and download again. Screens, macros and page navigation keep working. The older DTools generation reaches the same result with the LW9296 suppression bit, which DTools Pro 1.10 does not offer as a freely enterable address. Treat it as a bench measure only: on a machine that runs production, a hidden 40001 hides a real lost link too, so build your own link indicator before you release the project.

What the Communication Information 40001 window is #

The runtime raises window 40001 by itself whenever a communication error occurs: the configured driver sends its poll and no valid reply arrives before the timeout. With no controller on the desk, every cycle fails, so the prompt sits over the current screen and comes back on the next failed poll. The DTools configuration manual documents a default system prompt display time of 10 seconds, so each occurrence holds the screen for that long unless you close it first.

A repeating 40001 says exactly one thing: the panel cannot reach the controller it was configured for. In the reported case the project itself was healthy, with all 43 screens displaying, macros executing and navigation working while the window kept reappearing. On an empty port the popup is expected behavior; suspect the project or the panel only when a controller is attached and the window still shows.

Turning Show System Prompt off in DTools Pro 1.10 #

  1. Open the project in DTools Pro 1.10.
  2. Open the GlobalSet menu and choose System Setting.
  3. Disable Show System Prompt.
  4. Compile the project and download it to the panel.
  5. Let the panel restart into the project with the port still unplugged.

This is the route confirmed to stop the repeated window on the G2100E, and it needs no tag, macro or screen object. It silences the system prompt messages as a whole, not only the communication one. That is exactly what a bench project wants, and exactly what a production project must not keep unless your own logic announces the lost link.

The LW9296 suppression bit, and what DTools Pro does with it #

In the older DTools generation the communication error popup suppression is a single system bit addressed as LW9296, with documented behavior: FALSE means the popup appears on a communication error, TRUE means it does not. Set it TRUE from a startup macro or from a switch on a maintenance screen and you hide only this popup, leaving every other system message in place, which is the better tool while a machine has to keep running.

In DTools Pro 1.10 that address is not freely addressable, so entering LW9296 by hand in the tag editor does not take. Look for a named popup suppression or communication status entry in the project's system variable list; if the Pro project offers one, drive it the same way and evaluate the communication status variables yourself to display faults. If it does not, the Show System Prompt setting is the lever Pro 1.10 gives you.

Choosing between the two methods #

Method What it hides Where it is set Use it for
Show System Prompt disabled Every system prompt window, project-wide GlobalSet, System Setting Bench projects with no controller attached
Popup suppression bit TRUE Only the communication error popup LW9296 in the older DTools generation; a named system variable if DTools Pro offers one Commissioning and maintenance screens on a machine that keeps running

For an office bench with no PLC, take the global setting: one menu, no code. For anything that stays powered on a real machine, prefer the bit route during commissioning and pair it with your own fault display.

Safety note: a machine that keeps running with the communication prompt suppressed and no replacement indicator will keep moving while its controller is disconnected, so restore the prompt or drive your own alarm before the project goes into production.

  • No controller connected: the window is expected. Suppress it with the setting above and carry on testing.
  • Controller connected and the window still appears: the poll genuinely fails. Match port type, baud rate, parity, stop bits, protocol and station number between the project's device settings and the controller, then rule out controller-side delays the way separating PLC scan time from real HMI communication faults describes.
  • Window appears only now and then on an Ethernet panel: suspect shielding, terminations or a busy or stopped controller first, and work through diagnosing intermittent HMI to PLC Ethernet comms hangs.
  • While a live connection is being debugged, leave Show System Prompt enabled: the popup is the fastest signal that polling has failed.

A 30 second bench proof on a G2100E with no PLC attached #

Inputs: the documented default system prompt display time of 10 seconds from the DTools manual; the bench condition of no PLC connected, so every driver poll fails; an observation target of three consecutive prompt windows, an example duration chosen to span several failed polls in a row.

Rule: a suppression that works must keep the screen clean through every prompt window in the run, because with no controller each window would otherwise return once the previous one ends. Observation time equals the number of windows covered times the default display time.

Arithmetic: 3 windows × 10 s = 30 s.

Result: run the downloaded project with the port unplugged and the screen untouched for 30 seconds.

Decision: the pass threshold is zero windows, so no 40001 popup in those 30 seconds proves the change reached the panel. If one appears, the download did not carry the new setting, so recompile, redownload and repeat the proof. After the proof, page through several of the 43 screens and run one macro to confirm the project itself is untouched. When a controller is available, reconnect it and watch one live value update, because with prompts hidden a stale value is the only visible fault sign.

Questions asked

Does disabling Show System Prompt hide the alarms from my PLC program too?

No. The setting controls only the panel's own system prompt windows, such as the communication window 40001. Alarms, messages and event displays that you configured on the screens are separate objects and keep working. What you do lose is every other system message as well, not just communication ones, so a bench project can hide them all while a production project needs its own link indicator.

Can I enter LW9296 as a tag address in DTools Pro 1.10?

No. In the older DTools generation the communication error popup suppression bit sits at LW9296, where TRUE suppresses the popup and FALSE lets it appear on a fault. DTools Pro 1.10 does not expose that address as a freely enterable tag, so typing it in fails. Check the project's system variable list for a named suppression or communication status entry instead; if none exists, use the Show System Prompt setting.

How do I put the popup back before the panel goes into production?

Enable Show System Prompt again under GlobalSet, System Setting, compile and download, and return the suppression bit to FALSE if you used one during commissioning. Then pull the cable once with the machine stopped and confirm the communication window appears again, so you know a real lost link will be announced to the operator rather than silently ignored.

Why does the 40001 window appear when the download reported success?

A successful download only transfers the project to the panel; it makes no statement about the driver link. As soon as the project runs, the panel polls the configured controller, and with no PLC on the bench every poll fails, which raises window 40001 again after each dismissal. Screens, macros and navigation are unaffected, so the popup on an empty port is expected behavior rather than a project error.

Does the popup stop macros or screen changes while it is open?

No. In the reported case all 43 screens displayed, macros ran and navigation between screens worked normally while the window kept reappearing on top of the current screen. The window only overlays the display; it does not interrupt the runtime. The project needs no change to keep working, because the popup is purely the communication prompt doing its job on an empty port.

Keep reading

  • Troubleshooting

    Why an HMI OS update error points at the wrong device

    When EasyBuilder Pro reports that a Weintek HMI needs an OS update during a project download, the address it dialed often belongs to another active device — in the reported case, a PLC. Stop the download, reboot the panel, verify the target address against the HMI's network settings, and retry. Request an OS file from Weintek or a distributor only when the verified target still prompts.

    HMI and touchscreens

  • How-to

    Editing a Delta DOP HMI project without breaking PLC comms

    Downloading a revised project to a Delta DOP panel replaces only the panel's project; the PLC program and its port configuration are untouched. The link survives because the driver and serial parameters are stored separately in each device and a revision leaves them matching. Record both sides first, then prove read and write after the download.

    HMI and touchscreens

  • Troubleshooting

    Fixing an HMI Project Upload That Reports Communication Failed

    Treat a failed HMI project upload as three separate branches: the installer's parallel-port dongle driver message is a licensing fault, a "communication failed" report before any progress is a transfer-path mismatch, and a "file system error" after the panel answers is a storage or destination fault. Identify the layer from the message and the moment it appears, fix that layer only, and retest. A dongle fault never blocks the cable, and a successful ping never proves the transfer service is up.

    HMI and touchscreens

HMI Project Opens With a Repeating Error Popup: Isolate It