IMDTouchKnowledge BaseShop main store

Explainer

Why an OP7 or OP77A Has No Built-In Remote Screen Viewer

HMI and touchscreens Published 8 min read

Short answer

Neither the OP7 nor the OP77A implements a remote-display service: every documented interface function is controller communication or project transfer. For an exact picture of the panel use a camera or replace the terminal. For process visibility, build a separate view from PLC data, because controller reads cannot reveal the active screen, the message wording or an uncommitted operator entry.

On this page
  1. Can I see what an OP7 or OP77A displays over a serial or network connection?
  2. What do the panel's connection ports actually provide?
  3. Why can't reading the PLC data rebuild the screen?
  4. How do I confirm which panel is installed before choosing a fix?
  5. How can I check which screen the operator is on right now?
  6. What works when I need an exact image of the panel display?
  7. What works when watching the process values is enough?
  8. When does replacing the panel make more sense than viewing it?
  9. Questions asked

No — neither panel can show you its screen, and no accessory changes that. The OP7 and the OP77A expose every documented interface function as controller communication or project transfer; none implements a remote-display service. That forces a two-way decision: an exact picture of the physical panel, which means a camera or a panel replacement, or a separate process view built from PLC data, which cannot show which screen, message or uncommitted entry the operator has in front of them.

Can I see what an OP7 or OP77A displays over a serial or network connection? #

No. Neither panel implements a remote-display or mirroring service on any of its interfaces: every documented function of the OP7 and OP77A ports is controller communication or project transfer, so no cable, adapter or gateway choice turns either panel into a screen server.

It helps to separate the two halves of the word "remote". Mirroring means transmitting the panel's rendered display — text, bitmaps, active screen, cursor, messages — to another device. A communication interface only supplies transport; the device on the other end must also implement a service that packages its display for export. Adding hardware in the middle does not create that service. Newer panel families document exactly such services, which is how the technique described in the guide to using a VNC Viewer object on an HMI to display other panels works; on the OP7 and OP77A, the service simply is not there, so that approach has nothing to connect to.

What do the panel's connection ports actually provide? #

Their ports do two jobs: talking to the controller and moving project data. The operating instructions for the OP 73, OP 77A and OP 77B describe each interface as controller communication or project transfer, and no firmware option turns any of them into a live display export.

Work through the installed connections before buying anything:

  • Record each connector's configured role: controller communication, project transfer, or another documented function. A connector's shape does not identify its electrical interface or protocol.
  • Read the documentation for that exact model, not a neighbouring one. The instruction set you need is the one whose title names your panel.
  • Treat a gateway as a translator only. It routes and converts protocol data the panel already exchanges; it cannot extract a display buffer the panel never offers, and it cannot convert project-transfer access into live viewing access.

If a vendor document for your exact model and firmware does not name a display-access function, the port does not have one. Stop there and choose one of the two architectures below.

Why can't reading the PLC data rebuild the screen? #

Three things you see on the panel live in the panel, not the controller: which screen is active, the wording of locally configured messages, and any operator entry not yet written to the PLC. A controller read exposes only the tag values feeding the display.

The panel reads tags, then applies its own project configuration to produce formatted text, screens, messages and navigation. A tag is an application variable in the controller; the picture is panel-local. That split looks like this:

What the operator sees Where it lives What a controller read gives you
Process value Controller tag plus panel scaling and formatting The raw count, not the formatted figure
Active screen Panel navigation state Nothing, unless the project writes a screen number
Message text The panel project's message definitions The trigger bit, never the wording
Uncommitted operator entry Panel-local editing buffer The last value the panel actually wrote
Cursor or menu position Panel-local user-interface state Nothing

A worked example makes the split concrete. Suppose the project scales a temperature tag at 0.1 °F per count, and the controller word holds 235. The panel shows 23.5 °F, because 235 × 0.1 = 23.5. Your controller read gives you 235; applying the scaling from the panel project reproduces the number. Now the operator switches to a different screen without touching the process: the word still holds 235. The value proves the process and never the screen, which is why process reads alone cannot substitute for a viewer.

How do I confirm which panel is installed before choosing a fix? #

Read the nameplate and the full ordering identification before anything else. The OP7 and the OP77A are different products with different displays — the OP77A documentation describes a fully graphical 4.5-inch display with bitmap and bar graph support — and a capability documented for another panel family never transfers by name similarity.

Then verify three things in sequence, and correct any mismatch before proceeding:

  • The manual in your hand names your exact model and ordering number.
  • Each installed connection has an identified, documented role.
  • The documented function list contains no display-access service for this panel. If it did, the direct path would exist; for these two models it does not.

This matters more than it seems, because sellers and forums routinely attach another panel's features to a legacy unit by resemblance. The feature list travels with the ordering number, not the look.

How can I check which screen the operator is on right now? #

Change the panel's screen while holding the process steady, then watch the controller data: if nothing in the PLC changes with the screen, the project exchanges no screen-state information, and no amount of extra polling will find one.

Run the check on a bench or during a quiet window, with a known trigger:

  1. Open the panel project and list how the operator navigates: keys, screen selection logic, any configured controller interaction.
  2. Look for an explicit screen-state exchange — a value the panel writes when the screen changes. Many projects never defined one, because the panel and the operator shared a room.
  3. Perform the test: hold the process values constant, change screens several times, and record every controller address that moves. A fixed set of addresses that tracks the screen is your screen-state signal; silence confirms there is none.

If the test finds nothing and you need a remote view that follows the operator, add the signal yourself: have the panel project write an explicit screen number to the controller on every navigation. That one addition is what turns a process view into one that tracks the station.

What works when I need an exact image of the panel display? #

A camera aimed at the glass. It is the only way to get a true image of these panels without replacing them, because it reads the same physical display the operator reads and needs no cooperation from the panel at all.

A camera reproduces everything the previous sections said a data connection cannot: the active screen, the message wording, the half-finished entry, the cursor. Judge it the way you would judge an operator's sightline:

  • Every screen must be legible in the image, including the worst-case text screen and any small status fields.
  • Check reflections, cabinet lighting and viewing angle at the times the machine actually runs, not once at noon.
  • Confirm the mounting and cabling suit the area; an enclosure door or a washdown location changes the hardware you select.

The camera does not let a remote engineer operate the panel, and it shows nothing when the display or its backlight fails. It is an observation tool, sized to the question "what does the operator see".

What works when watching the process values is enough? #

Build a separate visualization from PLC data and label it as a process view, not a mirror. It can show every value, state and alarm the controller holds, but it will not follow the panel's navigation, message priorities or uncommitted operator entries.

Trace each required indication to a source before building anything:

  • For each displayed value, confirm the controller address, data type, scaling and engineering units, so the remote figure matches the panel's formatted figure. The scaling check in the worked example above — 235 × 0.1 = 23.5 °F — is exactly this step.
  • For each message, decide whether the remote view needs the trigger bit only or the wording too. The wording lives in the panel project, so an independent view must carry its own text definitions.
  • Check the controller communication resources: protocol, addressing and capacity for one more client and its polling load. Resolve that before ordering any interface hardware.

Use the maintained panel and controller projects as the source of truth for all of this; a device backup is not an editable engineering project. If files are missing, obtain them from the equipment owner, the machine builder or the manufacturer's supported channels. If any required information exists only inside the panel and you cannot move it out, exclude it from the remote view explicitly rather than implying the view equals the station. And if the remote view is later expected to operate the machine, treat that as a separate control-system change: keep a local stop that works when the remote link is down.

When does replacing the panel make more sense than viewing it? #

When remote viewing is a standing requirement rather than a one-time look. A replacement terminal with supported remote access ends the problem permanently, but it is an engineering migration with its own project work, not a connector swap.

The selection criteria in the guide to planning an HMI terminal replacement from an older operator panel apply directly here, and if the same panel sits on many machines, the guide to choosing a legacy HMI replacement for a machine fleet extends the decision across the whole installed base. For a single station, the decision reduces to this: if the requirement is an exact picture, the camera answers it today at zero project cost; if the requirement is ongoing remote access, budget the migration — recreate the screens, map the tags, rework the messages, and compare the door opening before ordering. A PC-based unit that mounts flush in the cut-out, such as the embedded panel-mount PCs range, is the usual shape that replacement takes.

The deciding question, stated plainly: an OP7 or OP77A will never serve its own screen, so choose the camera for a look, the separate process view for the data, and the replacement when the remote station itself must stay.

Questions asked

Does the OP77A have a video output I could extend to another monitor?

No. The OP77A has no external monitor or video output; its display is driven internally, so an extension cable or capture device has nothing to connect to. That is why an exact picture of an unchanged panel needs a camera aimed at the glass, and why replacement is the durable fix when remote viewing is a standing requirement.

Can a protocol gateway give me the screen contents?

No. A gateway translates between protocols and routes data the panel already exchanges. The panel itself would still have to run a display-export service, and neither the OP7 nor the OP77A implements one, so no gateway converts the panel's communication traffic into a picture of its display.

Do current operator panels support remote viewing natively?

Many current panels do. They expose a VNC server or a web client, so an engineer can watch the operator station from a PC or mobile device. Support is model dependent: check the specific panel's documentation for the viewer protocol, the number of simultaneous sessions, and whether a viewer can operate the panel or only watch it.

What should I add to the PLC project so a remote process view follows the operator?

Add an explicit screen-number tag that the panel writes on every screen change, plus the message texts and acknowledgment states that currently live only in the panel project. Without a screen-state tag, a remote view shows valid process values but cannot tell which screen the operator is actually looking at.

Is the OP77A display graphical or text only?

Graphical. The OP77A documentation describes a fully graphical 4.5-inch display that supports bitmap and bar graph elements, which is why an independent process view can be made to resemble the panel closely. The OP7 is the older, text-oriented unit of the pair.

Keep reading

  • Selection guide

    Choosing the Right HMI Panel Screen Size for the Job

    Match the diagonal to the operator's task: 3–7 in for localized control, 7–15 in for standalone machines, and 15–24 in or larger for complex process overview. Then verify viewing distance, resolution against physical size, touch targets, enclosure cutout, and application compatibility before committing.

    HMI and touchscreens

  • Selection guide

    How to Choose an HMI Display Size by Operator Task

    Sort panels by operator task: 3–7 in for local control of one machine, 7–15 in for standalone machines and lines, 15–24 in or larger for process overview. Then take the smallest panel whose smallest text and touch targets pass at the operator's real viewing distance — about 0.25 in of character height at a 30 in stand — and confirm bezel, cut-out and depth from the installation drawing.

    HMI and touchscreens

  • Selection guide

    Industrial HMI device types and how to choose between them

    An HMI device is the hardware that presents the operator interface: touchscreen panel, button panel, panel PC, panel-mount display, mobile device, web client or virtual HMI. Three questions pick the type — where the operator stands, what the location does to hardware, and who else needs the same view. Score each candidate 0 to 2 on those three; the highest total is the station's device.

    HMI and touchscreens