Selection guide
How to Choose an HMI Display Size by Operator Task
Short answer
Sort panels by operator task: 3–7 in for local control of one machine, 7–15 in for standalone machines and lines, 15–24 in or larger for process overview. Then take the smallest panel whose smallest text and touch targets pass at the operator's real viewing distance — about 0.25 in of character height at a 30 in stand — and confirm bezel, cut-out and depth from the installation drawing.
On this page
HMI panels sort into three working groups: 3–7 in for local control of one machine, 7–15 in for standalone machines and production lines, and 15–24 in or larger for process overview. The decision is not the smallest panel that renders the application; it is the smallest panel whose smallest text and touch targets still work at the distance people actually stand. Comfortable reading needs about 1 in of character height per 10 ft of viewing distance, half that as the readable floor — 0.25 in at a 30 in machine-side stand. A panel that passes at the stand can still fail a 10 ft glance from across the aisle, and the right answer there is usually a second display, not a bigger operator panel. Confirm cut-out, depth and connectors last, because same-size panels are not mechanically interchangeable.
The three size groups and where each fits #
The diagonal on the datasheet is the glass diagonal, and the group boundaries are where applications sit, not where products divide: the ranges overlap at 7 in and 15 in, and a boundary panel serves either neighbor depending on layout and mounting.
| Group | Diagonal range | Operator task it fits | What you trade |
|---|---|---|---|
| Local control | 3–7 in | Running one machine or skid at arm's length: state, commands, immediate faults | A few square inches of glass, so you choose what stays visible |
| Machine and line | 7–15 in | Standalone machines, production lines, small-to-medium processes with context and navigation | More door area and a navigation structure operators must learn |
| Overview | 15–24 in and larger | Complex processes, multi-line supervision, detailed visualization | Mounting space and real layout discipline; empty area helps no one |
Drawn by information volume instead of task, a common industry grouping lands on the same map: 5.7–12.1 in covers basic monitoring and control, and above 15 in is where advanced analytics and dense trending live. Use either map to pick candidates; the tests below pick the panel.
The reading test: character height against distance #
ISO 9241 is the ergonomics standard series for human–system interaction, and its display guidance sets character size against the design viewing distance: characters must subtend enough visual angle at the distance people work from. The field approximation is the long-standing typography rule of 1 in of letter height per 10 ft of viewing distance for comfortable reading, with 1 in per 20 ft as the readable floor. With distance in inches, divide by 120 for the comfortable cap height and by 240 for the floor.
| Viewing distance | Comfortable cap height | Readable floor |
|---|---|---|
| 24 in (0.6 m) | 0.20 in | 0.10 in |
| 30 in (0.76 m) | 0.25 in | 0.125 in |
| 36 in (0.9 m) | 0.30 in | 0.15 in |
| 6 ft (1.8 m) | 0.60 in | 0.30 in |
| 10 ft (3.0 m) | 1.0 in | 0.50 in |
Cap height is the height of a capital letter, not the font's point size. Measure it at full scale — in the runtime preview at 100 % or with a ruler on the installed glass — because a layout that reads fine at desk distance fails regularly once it is mounted on the machine.
Sizing a 7-inch panel for a 30-inch stand and a 10-foot glance #
Inputs:
- Operator's normal position: 30 in (0.76 m) from the glass, a typical machine-side standing reach for this case.
- Line lead's glance position: 10 ft (3.0 m), across the aisle.
- Legibility rule from above: comfortable cap height = distance ÷ 120, floor = distance ÷ 240.
- Candidate: a 7 in diagonal panel from the small/medium boundary. Its glass is 3.4 in tall in a 16:9 format (7 × 9 ÷ 18.36) or 4.2 in tall in 4:3 (7 × 0.6).
At the stand: 30 ÷ 120 = 0.25 in comfortable, 30 ÷ 240 = 0.125 in floor. The 16:9 glass holds 3.4 ÷ 0.25 = 13.6, call it 13 rows of comfortable text once margins count, and 4.2 ÷ 0.25 = 16.8, so about 16 rows in 4:3; after a status banner and navigation, plan on ten usable rows. That passes local control with room to spare.
At the glance: 120 ÷ 120 = 1.0 in comfortable, 120 ÷ 240 = 0.50 in floor. The same 3.4 in glass fits at most three rows of comfortable text, or 3.4 ÷ 0.50 = 6.8, six rows at the floor once anything else shares the screen. Below 0.50 in of cap height nothing on that panel is readable at 10 ft — that is the pass/fail line for the glance duty, and the 7 in panel fails it.
Decision: keep the 7 in panel for the operator, and put the overview values and alarms where the glance happens, on a 15–24 in display or a large andon. A 15 in 4:3 glass is 9.0 in tall (15 × 0.6) and carries 9.0 ÷ 0.50 = 18 rows of floor-height text for that duty. If one panel must serve both duties, the glance distance sets the size, not the stand distance.
The touch test #
The other half of the decision is whether a finger hits what it aims at. Glass area sets the room a layout gets: at equal aspect ratio a 15 in panel offers (15 ÷ 7)² ≈ 4.6 times the area of a 7 in one, which is why grids that demand a stylus on small glass work bare-fingered on large glass. On small panels, fewer and larger targets beat a dense matrix — for the target dimensions themselves, use the method for how to size HMI touch buttons in a dense matrix. Glove and stylus behavior depends on the specific panel's touch technology, so test it on the candidate model rather than trusting the diagonal. And whatever size you choose, emergency stop and safety functions stay on hardwired devices, never behind an HMI page or touch target.
When more inches is the wrong fix #
Three complaints that look like a small screen are not. Crowding is usually a hierarchy problem: when every value, command and status indicator carries equal weight, operators hunt for the current condition, so strip the operating view down and push setup screens to their own pages before buying area. Resolution is not physical size: more pixels add graphical detail and enlarge nothing, an application that sizes text in pixels renders physically smaller characters on a denser panel of the same diagonal, and whole-application scaling depends on the runtime and can distort proportions. And a stale or wrong value is a tag-binding or communication fault, not an area fault — trace the object's tag, the driver connection and the controller value first; a bigger panel shows the same wrong number, larger.
Mechanical fit: cut-out, depth and connectors #
The advertised diagonal says nothing about the metalwork. Two panels with the same diagonal can differ in bezel, cut-out, depth and connector position, so read the installation drawing of the specific model for overall dimensions, cut-out, rear clearance — depth behind the door plus connectors and cable bend — and the mounting arrangement. When a replacement must drop into an existing opening, compare its cut-out against the panel cut-out reference before ordering. A tall, narrow opening can argue for portrait mounting, but portrait orientation changes cooling and temperature derating, so read portrait HMI panel mounting and temperature derating before committing the orientation.
The decision, step by step #
- List the operator tasks; mark the values, states, commands and fault indications that must be visible at the same time.
- Measure the normal working distance and any glance distance from the aisle or the neighboring machine.
- Apply the reading test above to each distance, in inches, to get the comfortable cap height and the floor for each position.
- Build the most demanding screen with real labels and live-length values, and measure its smallest text at full scale; enlarge text or split pages until it clears the comfortable height, never below the floor.
- Check the touch targets at that same physical size, with the gloves operators actually wear.
- Confirm the runtime supports the application at that panel's resolution, and confirm cut-out, depth and connectors from the installation drawing. If this selection replaces an older terminal, fold in the steps for planning an HMI terminal replacement from an older operator panel.
- Buy the smallest diagonal that passes reading, touch and fit. When only a distant glance duty fails, split the duty onto a second, larger display instead of upsizing the operator's panel.
Questions asked
Does a higher-resolution panel make text easier to read?
Not by itself. Resolution is the pixel count; physical glass size sets how large each character is. Text sized in pixels gets physically smaller as pixel density rises, so the same application can become harder to read on a sharper panel of the same diagonal. After any resolution change, measure the smallest cap height at full scale again and hold it to the distance rule.
How far away can a 15-inch panel be read?
Invert the rule: maximum distance equals cap height × 120 for comfortable reading and × 240 as the floor. Text with 0.25 in caps reads comfortably at 30 in and bottoms out at 60 in; 0.5 in overview text reaches 60 in comfortable and 120 in at the floor. Size overview text to the farthest person who must act on it, not to the nearest.
Can one large panel replace several small local panels?
Only when the machines share one operator position, one viewing distance and one person watching at a time. Keep a local panel wherever an operator runs a single machine at arm's length, because walking to a shared screen costs more than the extra panel. Machine-specific interlocks and hardwired stops stay at the machine regardless of how large the central display is.
Is a 5.7-inch panel still enough for basic machine control?
At arm's length, yes: common selection guidance puts basic monitoring and control between 5.7 and 12.1 in. The test does not change — at a 24 in stand the smallest text needs 0.20 in caps to read comfortably, and the touch targets must pass on that glass. If either fails, move up to the 7 to 10 in class rather than shrinking the text.