IMDTouchKnowledge BaseShop main store

Selection guide

How to Select HMI Specifications That Match the Machine and Site

HMI and touchscreens Published 8 min read

Short answer

Select an HMI by walking each machine and site requirement back to the one specification that controls it: display resolution against viewing distance, the exact driver against your controller, the OS against the toolchain, the rating against the cleaning method. Hold smallest text at 3.5 mm cap height for a 600 mm stand, treat IP65 as a front-face rating that converts to no NEMA type, and keep safety functions out of the project file.

On this page
  1. Start from the symptom, not the catalog sheet
  2. Display: fix the viewing distance before the diagonal
  3. Communications: a protocol name is not a driver
  4. Operating system and toolchain: software picks the platform
  5. Environment: IP65 is one face, and no IP converts
  6. Power and certificates: the two lines most often skipped
  7. Safety functions are not HMI features
  8. The specification page you write before comparing panels
  9. Questions asked

An HMI fails in service for reasons you can name before you open a catalog: text too small at the operator's real standing distance, a driver that does not exist for your controller, a front gasket never rated for the hose, a runtime that needs an OS the panel does not run. Select the panel by walking each requirement back to the one specification that controls it, and hold four commitments as you go: smallest text at 3.5 mm cap height for a 600 mm viewing distance, the exact driver verified at both ends of every link, IP65 treated as a front-face rating, and no IP code converted to a NEMA type. The method below turns that into a table, one worked example with the arithmetic, and a decision for each area.

Start from the symptom, not the catalog sheet #

Every HMI complaint maps to one controlling specification. Write the complaint in the installer's words, find its row, and check that specification first:

What you observe Controlling specification First check
Operators lean in or misread values Resolution at the viewing distance, not diagonal Smallest text cap height in mm at the real standing spot
No data reaches the panel Ports and the device driver for your controller Protocol on both ends, then the vendor's driver list for your controller family and firmware
Values lag behind the machine Driver polling and network loading Poll list and refresh rate before processor speed
Panel leaks, fogs or drifts after cleaning Ingress rating, front face only Cleaning method versus the IP or NEMA 250 rating and mounting instructions
Panel misbehaves at temperature extremes Operating temperature range Site worst case with the door closed, plus cold start
Project will not build, load or run Engineering tool, target model, firmware, runtime Compatibility matrix for the exact tool and target
Argument about the e-stop Safety function design Machine risk assessment, not HMI features

A bigger display never adds a protocol. A faster processor never seals a gasket. Reject the panel when its data sheet cannot answer the row you started from.

Display: fix the viewing distance before the diagonal #

Display ergonomics holds minimum character height near 20 arc-minutes of visual angle; smaller text stays legible only with effort and becomes the leaning-in row above. Height equals distance times tan(20/60 degrees), which works out to distance divided by 172: 2.9 mm at 500 mm, 3.5 mm at 600 mm, 5.8 mm at 1 m, 8.7 mm at 1.5 m.

Worked example, with example inputs you would replace with your own. Candidate: a 10.1 in diagonal panel at 1280 x 800, operator standing 600 mm away.

  • Diagonal pixel count: sqrt(1280^2 + 800^2) = sqrt(1,638,400 + 640,000) = sqrt(2,278,400) = 1509 px
  • Density: 1509 px / 10.1 in = 149 px per inch
  • Pixel pitch: 25.4 mm / 149 = 0.17 mm per pixel
  • Smallest project font, 20 px cap height: 20 x 0.17 mm = 3.4 mm
  • Floor at 600 mm: 600 / 172 = 3.5 mm

Decision: 3.4 mm misses the 3.5 mm floor, so raise the smallest font to 21 px (21 x 0.17 = 3.6 mm) rather than asking operators to step closer. Buttons: a 100 px target is 100 x 0.17 = 17 mm, which clears the 15 mm floor for a bare finger but not the 20 mm you want for gloved hands, so size routine targets to 120 px (20.4 mm) wherever gloves are worn. Glove sensing, meaning whether a capacitive screen registers a gloved finger at all, is model dependent and a separate check from target geometry.

Size the diagonal to the task mix, the way choosing an HMI display size by operator task works through it, then hold the text floor above whatever diagonal you land on.

Communications: a protocol name is not a driver #

Ports on the sheet, such as Ethernet, RS-232 and RS-485, and protocol names such as EtherNet/IP, Modbus RTU or TCP, PROFIBUS and PROFINET, describe what the panel can be configured to speak, not what it can drive. The driver is written against a controller family and a firmware generation, and it is a separate line in the compatibility matrix from the port it runs over.

List every device the panel must reach: controller, drives, remote I/O, meters, scanners. For each, write the protocol, the port, and the driver version the vendor documents for that firmware. Any device with no matching driver is a rejection, or a documented gateway with a real conversion path, never a hope.

Decision: selecting a Modbus TCP HMI panel for an existing controller shows the full check for one protocol; run the same check per device, and count simultaneous connections against the panel's documented limit before committing to a shared medium.

Operating system and toolchain: software picks the platform #

An HMI runs Windows in some embedded or IoT edition, Linux, or a proprietary real-time operating system, and your project software runs on some of that, not all of it. The OS name alone proves nothing. Check three things separately, because each fails independently: the engineering tool and target model it supports, the firmware on the target, and the runtime license. For PC-based runtimes, match the runtime device version configured in the project to the runtime version installed on the station, and check host OS support and license terms as two more separate lines.

Decision: pick the software you must run first, then the platform it is documented on, which is the path choosing a PC-based HMI runtime for a Modbus TCP PLC follows. A panel that cannot run the toolchain is out, whatever its other numbers.

Environment: IP65 is one face, and no IP converts #

IEC 60529 defines the IP codes. IP65 means dust-tight plus water jets, and the IPX5 jet is a 6.3 mm nozzle delivering 12.5 L/min, a rinse rather than a pressure wash. On a panel-mount HMI that rating covers the front face only, mounted to the vendor's instructions for cut-out flatness, gasket and fasteners; the rear of the housing is typically IP20 and belongs inside a cabinet that provides that protection.

NEMA 250 tests things no IP digit tests, and the two standards convert in neither direction. If the installation requires Type 4X, the enclosure carries its own NEMA 250 type rating, and 4X corrosion resistance is exactly what an IP65 front face cannot demonstrate. The washdown rating versus NEMA 4X versus IP65 comparison lays out what each test actually does.

Decisions by cleaning regime. Wiped or blown dust: IP65 front with the gasket verified, the case selecting an IP65 industrial touchscreen for a dusty HMI covers. Rinse at the machine: IP65 front still, mounted per instructions. High-pressure hot washdown: IP69K, whose spray heads in ISO 20653 deliver on the order of 80 bar at 80 degrees C; when the station itself sits in that zone rather than behind a door, specify IP69K washdown panel PCs and monitors. Salt or corrosive air: demand corrosion test evidence or a 4X marking, because no IP digit addresses it.

Temperature and vibration: compare the data sheet's operating range to the mounting spot's worst case with the door closed, and expect LCDs run below their rating to ghost and respond slowly, the failure running a PanelView HMI at -20 C without ghosting the LCD works through.

Power and certificates: the two lines most often skipped #

Power: a typical data-sheet line reads 24 VDC +/-20%, which is 24 x 0.8 = 19.2 V to 24 x 1.2 = 28.8 V. Example check: a panel drawing 30 W at 24 V pulls 30 / 24 = 1.25 A, and the same 30 W at 19.2 V pulls 30 / 19.2 = 1.56 A, so size the supply and wiring for the low end. Confirm the rail's worst case, meaning supply tolerance, cable drop and brownout during motor starting, stays inside the printed range.

Certificates: CE and a North American listing such as UL or CSA are the baseline for most plants. ATEX matters only where the area is classified, and then the zone and group marked on the panel must match the area's. Marine class notations such as DNV or ABS apply on vessels and offshore; they are not a proxy for anything on a factory floor. A candidate missing the certificate your site audits for is out, no matter its display.

Safety functions are not HMI features #

A safety integrity level under IEC 62061 or a performance level under ISO 13849-1 attaches to a safety function, defined by the machine's risk assessment, and that function runs through safety-rated components and validated channels. An e-stop drawn on an HMI screen executes nothing. A physical e-stop on the panel housing is part of the function only as a safety-rated device wired into the safety chain; the HMI may display the state, it does not perform the stop. Put the stop in the safety chain and keep the project file for operations.

The specification page you write before comparing panels #

Before you compare two candidates, write one page; it is the tool that makes every later decision fast:

  • Screens: how many, and the smallest text height at the stated viewing distance.
  • Touch: bare or gloved, target floor 15 mm bare and 20 mm gloved, technology the site accepts.
  • Devices: every controller, drive and meter with protocol, port, driver and firmware.
  • Toolchain: engineering tool, target, firmware, runtime version, licenses.
  • Environment: worst-case temperature, cleaning method with its pressure and temperature, dust, corrosion, vibration.
  • Mounting: the opening it must fit, comparing candidates against the existing cut-out the way selecting a thin-bezel industrial HMI display for a cutout does.
  • Power: rail range and the panel's consumption at the low line.
  • Certificates: CE, UL or CSA, ATEX zone if classified, marine class if offshore.
  • Safety: each function with its required performance level or safety integrity level.

A candidate missing one of these lines is out. That single rule is the selection method.

Questions asked

Can I treat IP65 as equivalent to NEMA 4X on a data sheet?

No. IEC 60529 and NEMA 250 are separate standards and no conversion exists between them: Type 4X includes corrosion testing that no IP digit covers, and IP codes say nothing about outdoor construction. If the installation requires 4X, require the enclosure's own NEMA 250 type marking. Where a vendor offers only IP data for a corrosive site, ask for the corrosion and gasket-aging test evidence before accepting the panel.

How do I size text when operators read the panel from far away?

Size to the farthest position where an operator routinely reads the panel. The floor is distance divided by 172: at 2 m across a loading bay that is 2000 / 172 = 11.6 mm cap height, and at 1.5 m it is 8.7 mm. Values an operator only glances at from farther away belong on a separate, larger readout, not on the HMI at smaller text.

The screens are slow. Will a faster processor fix it?

Run one test with the controller cable unplugged and navigate through the screens. If navigation itself is sluggish with no controller attached, the platform is short on processor or memory and a faster panel is the fix. If navigation is instant and only the values lag, the limit is driver polling and the network, so fix the poll list and refresh rate, because a faster processor will not change it.

Do I need an HMI with SIL certification?

No HMI needs it as such: the performance level or safety integrity level attaches to each safety function, set by the machine's risk assessment under ISO 13849-1 or IEC 62061. The panel can host the button and show the state, but the stop runs through safety-rated devices and validated wiring. When a vendor quotes a safety rating for an operator panel, it applies to one defined function in one architecture, so read which one.

Does the IP65 rating apply to the whole panel?

No. On a panel-mount unit the IP65 covers the front face only, and only when the cut-out flatness, gasket and fasteners match the vendor's mounting instructions. The back of the housing is typically IP20, so the cabinet behind it carries the rest of the protection, including sealed cable entries, which undo an installation faster than anything happening on the front.

Keep reading

  • Explainer

    Portrait HMI Panel Mounting and Temperature Derating Explained

    No. Portrait mounting does not derate an HMI panel's temperature rating — the vendor's release information for the panels that gained portrait mode states the landscape specifications continue to apply, because rotation in the screen's own plane leaves tilt, convection and dissipation unchanged. The derating that still governs is mounting angle: the 15-inch model's angle table reads the same row in portrait as in landscape.

    HMI and touchscreens

  • Comparison

    Headless HMI Server Versus Operator Panel Selection

    Pick by sessions and screen location, not by programming: both run one project in the same tool. A panel gives one built-in touchscreen that VNC mirrors as a single shared session; a headless cMT-SVR has no screen and no VNC, serves up to three independent app clients, and takes its trend history on SD/SDHC beside 256 MB of flash.

    HMI and touchscreens

  • Selection guide

    Selecting a Touch Panel for CODESYS WebVisu in Salt Environments

    A panel qualifies as a CODESYS WebVisu client only when it runs a current Firefox, Chrome, Edge or Chromium engine that renders the served visualization, can be locked into full-screen kiosk operation, and comes with a written no-aluminum material declaration for salt and corrosive dust. Front IP66/IP69 ratings and marine approvals do not satisfy the material rule, so check each requirement independently and pass all three gates before purchase.

    HMI and touchscreens