HMI and touchscreens Published 6 min read By IMDTouch engineering team

Short answer

The question-mark quality is a COM activation failure, not a bad ItemID: when every other OPC client on the same PC reads the tag, the syntax is proven and the WinCC OPC DA client is being denied activation of the server. From WinCC V7.3 on, run Simatic Security Control, grant the local SIMATIC HMI group launch, activation and access rights on the server's COM application, allow the CCDmRtChannelHost callback through the firewall, and restart the computer.

On this page
  1. What the symptom tells you before you change anything
  2. What changed in WinCC V7.3 and later
  3. Run Simatic Security Control, then reboot
  4. Grant the SIMATIC HMI group the rights at each layer
  5. Worked example: the MK8000 server on a WinCC V7.4 SP1 UPD2 station
  6. Bridge, stopgap or OPC UA
  7. Questions asked

A question-mark quality on every tag from a third-party server is not a tag-management problem. When standalone OPC clients, another WinCC runtime and a bridge server all read the same items correctly on the same PC, the ItemIDs are proven and the fault sits in one place: the WinCC OPC DA client is denied COM activation of the server. From WinCC V7.3 on, the client's security policy only activates out-of-process servers for users that hold launch, activation and access rights through the local SIMATIC HMI group; Siemens documents the change in support entry 109483815. The fix is one security wizard pass, one per-application grant, one firewall rule and a full restart of the computer — not a re-import of tags. This article covers the same-station case, where client and server share one machine.

What the symptom tells you before you change anything #

Read the reported case first, because it already eliminates the usual suspects:

  • Standalone OPC test clients read every item of the third-party server correctly on the same PC, so the ItemID syntax is valid.
  • A second OPC server, loaded with the third-party server's items and serving them to WinCC, delivers correct values, so Windows itself can reach the data.
  • WinCC Advanced V14 SP1 reads the same tags, so the fault isolates to the classic WinCC OPC channel rather than to the server, the network or the operating system.
  • The values appeared correctly twice, then failed again with nothing changed — the signature of a connection that works once and is dropped at the next update cycle, not of a typo.
  • The diagnose folder reports a syntax problem, yet the same syntax validates in every other client; treat that line as the channel's generic failure output, not as proof of a bad ItemID.

With the tags and the server exonerated, only the activation path is left to fix.

What changed in WinCC V7.3 and later #

Siemens tightened the security policies of the WinCC OPC Client with WinCC V7.3 and, on the TIA side, with WinCC Professional V13 SP1; support entry 109483815 documents the resulting connection failures to third-party servers. In practice, an out-of-process COM server is activated only for a user that holds the required rights, and the vehicle for those rights is the local user group SIMATIC HMI. Two consequences follow for a station that used to work. Machine-wide DCOM defaults alone are not enough, because the permissions are per object: the specific COM application of the third-party server must grant them too. And the account the server runs under has to resolve into that grant, which is why a server installed under its own service account is the typical victim. The fault usually surfaces at the moment of an upgrade to the affected versions, exactly as in the reported case.

Run Simatic Security Control, then reboot #

The station's security wizard writes several of the required settings in one pass:

  1. On the station itself, open Start > Simatic > Simatic Security Control and select Settings.
  2. Apply the recommended entries so that the launch, activation and access permissions for the SIMATIC HMI group and the firewall rules for the WinCC runtime processes are written to the station.
  3. Restart the computer. Restarting the runtime alone does not apply the rewritten security database; the documented procedure for this change includes the computer restart.
  4. Reconnect the channel and check whether the qualities turn from ??? to good.

If group policy blocks the Start button on that station, Start button blocking still leaves other launch paths open, so the wizard stays reachable.

If the qualities stay unknown after the restart, the machine-wide pass was not the missing layer — grant the rights on the server's own COM application next.

Grant the SIMATIC HMI group the rights at each layer #

Record the current entries in every permissions dialog before you edit, so the station can be put back if something else breaks. Three layers carry the rights, and all three must pass:

  • Machine defaults. Confirm the local user group SIMATIC HMI exists on the station, then in Component Services follow DCOM > My Computer > COM Security > Access Permissions > Edit Default and grant the group Local Access. The same console holds the matching launch and activation defaults; grant the group local launch and local activation there as well.
  • The server's own COM application. In Component Services, open DCOM Config, select the third-party server's entry and, on its Security tab, give the SIMATIC HMI group local launch, local activation and local access. On the Identity tab, run the server under an account that holds those rights. This layer is not covered by the wizard's machine-wide pass, and it is the layer a server installed under its own service account most often fails.
  • The callback host. An OPC DA server reports value changes by opening a new TCP connection back to the client, separate from the connection the client opened. Create an inbound program rule for CCDmRtChannelHost in Windows Defender Firewall with Advanced Security so that connection is not silently dropped; this is what turns a read-twice-then-fail case into a stable one.

When the server moves to its own machine instead, the same grants switch to their remote variants and the failure set grows; that situation is its own procedure: why a remote OPC DA client fails to reach a LAN OPC server.

Worked example: the MK8000 server on a WinCC V7.4 SP1 UPD2 station #

Inputs, all from the reported case: WinCC V7.4 SP1 UPD2 and the MK8000 OPC server installed on one PC; every standalone OPC client reads the items; WinCC Advanced V14 SP1 reads them; a KEPware bridge between the MK8000 and WinCC delivers correct values; the diagnose folder reports a syntax problem; the values appeared twice, then failed again. The station sits above the version threshold where the tightened policy began.

Rule: from that threshold on, the WinCC OPC DA client activates an out-of-process server only when the launching user holds launch-and-activation and access rights through the SIMATIC HMI group at the machine defaults and on that server's COM application, and the server's callback connection may enter through the firewall.

Arithmetic: two permission families — launch-and-activation, access — across three enforcement points — machine defaults, the server's COM application, the firewall rule for the callback host — give 2 × 3 = 6 settings, and one denied setting among the six fails the whole activation.

Result: the ItemIDs are proven by every other client, so the fault is activation, not syntax. After the wizard pass, the per-application grant, the firewall rule and a full restart, the qualities turn good and hold across refresh cycles instead of appearing twice and dropping.

Decision: on any station at WinCC V7.3 or later, or WinCC Professional V13 SP1 or later, where any other client reads the same tag, apply all six settings in the order above and restart the computer — plan on one restart, not tag surgery. Keep the bridge running only until that restart is done.

Bridge, stopgap or OPC UA #

The bridge in the reported case is a working workaround, not a configuration: it adds a server installation, its license and one more process in the path of every value change, and a restart of the bridge host blanks the station again. Apply the rights fix and retire it. If the third-party server also offers OPC UA, moving the exchange to UA removes DCOM from the station entirely, because UA carries its own security over a single configured endpoint; the design question then becomes direction, which which direction works between an HMI OPC UA server and client answers. On the TIA side, when the Professional runtime still refuses data access with the group and the defaults already correct, the remaining checks are covered in why WinCC Professional OPC Data Access fails despite DCOM settings.

Questions asked

Does the same fix apply when the OPC server runs on a second machine?

The rights model is the same, but the grants change: the SIMATIC HMI group must exist on the server machine too, and that server's COM application needs remote launch, remote activation and remote access for the account the client runs under, not only the local variants. The right to access the computer from the network and the firewalls on both machines join the checklist. The remote case adds failure modes of its own, so work it as its own procedure.

Is WinCC Professional in TIA Portal affected the same way?

Yes, from V13 SP1 the same support entry names the Professional runtime, and its configuration uses the same SIMATIC HMI group and machine-default permissions. If the group and the defaults are already in place and data access still fails, the Professional runtime adds checks of its own around the runtime station and its configured identity; those are covered in the article on Professional data access failing despite DCOM settings.

Do I need to import the tags again after fixing the permissions?

No. The ItemIDs were never the problem; the standalone clients proved the syntax before anything was changed. After the rights are granted and the computer has been restarted, the existing channel reconnects and the qualities turn from unknown to good on the next update cycle. Re-importing the tags costs time and invites new typos without touching the denied COM activation at all.

Can I keep the second server as a bridge permanently?

It can bridge the gap, but understand the cost: every value now crosses two servers and two COM activations, so a restart of the bridge host blanks the station again, and the bridge needs its own license and maintenance. Keep it only while the rights fix on the WinCC station is scheduled. If the third-party server also speaks OPC UA, moving the exchange to UA removes DCOM from the station entirely and ends this class of fault.

Keep reading

  • Troubleshooting

    Why a remote OPC DA client fails to reach a LAN OPC server

    A classic OPC DA server that answers a client on its own PC but not one on another LAN computer is almost always blocked at DCOM or by the Windows firewall, not by the OPC server. Prove the server locally, confirm the transport is DA, open TCP 135 plus a sized RPC port window, then grant the client account access and launch rights in Component Services.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Professional OPC Data Access Fails Despite DCOM Settings

    Your PLC reads prove only that WinCC Professional acts as an OPC client. Matrikon reading WinCC needs the opposite direction: the WinCC OPC server activated and covered by the Runtime Professional license, live tags over OPC DA and archives over OPC HDA, verified locally before any DCOM change.

    HMI and touchscreens

  • How-to

    Connecting Operator Terminal Expert to a Third-Party PLC

    Operator Terminal Expert connects to a third-party PLC through a protocol both ends document — typically Modbus TCP or RTU, or OPC UA with the HMI as client and the PLC as server. Select the driver for your exact terminal target, match the driver's address notation to the PLC's register references, and prove one read and one controlled write on the deployed terminal before mapping the rest.