Why Ctrl+A Deletes a Tag Name in C-More Programming

HMI and touchscreens Published 7 min read

Short answer

In the C-more editor, Ctrl+A is the select-all-objects shortcut: pressed from a tag field whose text is not highlighted, it grabs every object on the screen and the tag name you typed is erased. Highlight the text itself before copying. And when you uncheck an object's Advanced Options, its stored tag references stay in the project and still count as in use — clear each one first, then uncheck, and confirm with the tag cross-reference.

On this page
  1. Why does Ctrl+A delete the tag name in a C-more field?
  2. How do you copy a tag name from a C-more field without erasing it?
  3. Why is a tag still in use after you uncheck Advanced Options?
  4. How do you clear hidden tag references before you uncheck Advanced Options?
  5. Example: how many tag references does one copied pump screen leave behind?
  6. How do you find every object that uses a tag in a C-more project?
  7. Can you rename a whole set of tags across a C-more project at once?
  8. Questions asked

Two C-more editor behaviors waste a technician's time daily: pressing Ctrl+A to grab a tag name you just typed, and unchecking Advanced Options to tidy a copied object. The first erases the tag instead of selecting it, because Ctrl+A is the editor's select-all-objects command and only acts on text once the text itself is highlighted. The second hides the object's assigned tags without removing them, so the project still reports them as in-use tags long after the screen looks clean. Both fixes are mechanical: highlight the text with the mouse before copying, and clear every stored tag reference before you uncheck the option. This article walks through each fix, counts what one copied pump screen leaves behind, and shows how the editor's Tag Cross Reference confirms a tag is truly gone.

Why does Ctrl+A delete the tag name in a C-more field? #

Because Ctrl+A is the C-more editor's select-all-objects command: from a tag field whose text is not highlighted, it selects every object on the screen instead of your text, the field loses its edit session, and the tag name you typed goes with it.

Select-all works on whatever context has focus. An object you selected with a single click is not a text context, so the screen's objects are what the shortcut grabs — which is why every object on the screen sprouts selection handles at the moment your tag disappears. The habit comes from editors where a focused text box turns Ctrl+A into a text selector; in this editor the text only becomes that context once you click into it and highlight it. That makes the fix a keystroke habit rather than a configuration change: highlight first, copy second, and save Ctrl+A for the times you actually want every object on the screen selected.

How do you copy a tag name from a C-more field without erasing it? #

Highlight the text itself — click into the field and drag across the tag name, or double-click the name — then copy while the highlight is on, and never reach for the select-all shortcut while only the object is selected.

The reliable sequence, in order:

  1. Click into the tag field so the cursor sits inside the text.
  2. Drag across the name, or double-click it, until the text itself is highlighted.
  3. Copy the highlighted text.
  4. Click an empty spot on the screen to release the object before you touch anything else.
  5. Reopen the source field and confirm the complete tag is still there.

Step 5 matters when the name is one you will reuse: a copy that silently clipped the text stays invisible until the destination object misbehaves. Retyping is the other safe path, and it deserves the same care, because the project's in-use lists and the Tag Cross Reference follow exact names — a one-character difference creates a second tag instead of reusing the first. Text handling has a separate failure on the runtime side, where entered text reaches the controller with its first characters missing; that fault is covered in why C-more text entry loses first characters in PLC memory.

Why is a tag still in use after you uncheck Advanced Options? #

Because unchecking Advanced Options only hides the options — the tag references stored under them stay inside the object, and the project's in-use tag list still counts every stored reference whether or not the option is enabled.

The sequence that creates the mess: you copy a shape whose visibility is driven from Advanced Options, decide the copy needs no such logic, uncheck Advanced Options, and move on. The screen looks clean; the tag list disagrees, because the stored reference survives inside the copy and the software keeps attributing that tag to an object that displays nothing. The bill arrives later, when you rename or delete that tag and must resolve an in-use flag on objects that appear to use nothing. Treat any tag still listed as in use as live until the cross-reference shows zero objects, because a reference you cannot see can still act on the machine.

How do you clear hidden tag references before you uncheck Advanced Options? #

Open the object and inspect every enabled option first: clear the tag assigned to each one the copy must not keep, and only when the fields are empty uncheck Advanced Options itself.

The order is the whole fix — unchecking first is exactly what creates the hidden state you can no longer see:

  • Copy the object as usual and open the copy's settings.
  • Read every enabled option under Advanced Options and note the tag assigned to it.
  • Empty the tag field of each option the copy must not keep — clear the field itself rather than planning to deal with it later.
  • Uncheck Advanced Options only after the unwanted fields are empty.
  • Run the Tag Cross Reference on each cleared tag name and confirm the list names zero objects.
  • If an object still appears, open it, clear the stored reference, and run the list again.

Example: how many tag references does one copied pump screen leave behind? #

Eight copied shapes carrying four Advanced Options tags each leave 32 hidden-but-in-use references if you uncheck first and clean up later — twice the effort of clearing before unchecking, which for this screen is 8 objects times 30 seconds, about 4 minutes.

Take an illustrative screen: 8 copies of a pump shape, each original configured with 4 tags under Advanced Options. The 4-per-object count is an example input, not a documented figure, so scale the arithmetic to your own objects.

  • Stored references if you uncheck without clearing: 8 objects × 4 tags each = 32 references hidden behind deselected options.
  • Clearing before unchecking: 8 objects × 30 seconds to open, empty the tag fields and uncheck = 240 seconds, about 4 minutes.
  • Cleaning up afterward: 32 references found one at a time through the in-use list and cross-reference at an assumed 15 seconds each = 480 seconds, 8 minutes — and it only works if you still remember which names were hidden.

The 2-to-1 ratio holds for any screen and widens every time a hidden name is one you cannot recall, so clear before you uncheck.

How do you find every object that uses a tag in a C-more project? #

Use the editor's Tag Cross Reference: it lists the screens and objects that reference a given tag name, so one run tells you whether an unwanted tag is truly gone or merely hidden behind a deselected option.

AutomationDirect's own how-to documentation for the software covers the Tag Cross Reference as the tool for tracing tag use through a project. The list follows stored references, not visible settings, which is what makes it the check for deselected-option leftovers: an object with Advanced Options unchecked still appears if its stored reference survives. Run it on the exact tag name and read the result as pass or fail — zero objects means the tag is gone, any object means a reference is left to clear — then repeat until the list comes back empty. None of this covers the panel-to-controller path: if the symptom is not editing but a panel that reads nothing from a controller you know is running, start with why a Micro800 program runs but the C-More panel reads nothing.

Can you rename a whole set of tags across a C-more project at once? #

Treat bulk find-and-replace with wildcard or partial matching as a request, not a feature of the C-more editor: renames must hit fragments like Pump1.PT.Scaled, Pump1PTScaled and Pump(1).PT.Scaled, and no fragment-matching replace tool is documented in the material reviewed here.

A rename from Pump1 to Pump2 has to work on all three shapes below, which is why whole-name matching is not enough:

Tag as written What a partial replace must match Result you want
Pump1.PT.Scaled the Pump1 fragment Pump2.PT.Scaled
Pump1PTScaled the Pump1 fragment Pump2PTScaled
Pump(1).PT.Scaled the equipment index only Pump(2).PT.Scaled

Until your installed version offers a replace tool that matches fragments, plan renames as per-object edits with the Tag Cross Reference as the checklist, and accept any such feature only after it proves fragment matching on a test screen. Exporting screens to text or XML for outside edits is regularly proposed and is not a confirmed C-more capability either, so do not build a renaming procedure on it. A hand rename follows the cleanup order: clear what must not survive, edit what must, then verify the reference count before and after.

Questions asked

Can group names be edited and group visibility toggled in the C-more editor?

Both were open requests raised alongside the Ctrl+A and Advanced Options behavior, and neither capability is confirmed in the material reviewed here. Until your installed version demonstrates them, treat group names as fixed and avoid screen designs that depend on toggling a whole group's visibility at runtime.

Does a deselected option's leftover tag still act at runtime?

The confirmed part is project bookkeeping: the tag stays attributed to the object and shows as in use. The reported behavior does not establish whether the hidden option still executes, so treat the reference as live until the Tag Cross Reference lists zero objects for that name. Clearing the stored reference is the only state you can trust.

Are tag-based range limits available on EA9 panels or only on the CM5?

Tag-based range limits exist in the C-more software, and the open question is whether they extend to the EA9 family or remain limited to the CM5; the question was recorded without a confirmed answer. Check the current software documentation for your exact panel model before building screens that depend on tag-driven limits.

Can the Ctrl+A shortcut be reassigned in the C-more software?

No shortcut remapping is documented for this software, so treat the select-all-objects behavior as fixed and build the replacement habit instead: click into the field, highlight the exact text with a drag or a double-click, then copy. The highlight is also the visual proof that the text, not the object canvas, has focus.

Keep reading

  • How-to

    Set an Idle Screen Timeout That Returns to the Main Page

    The EA9 has no screen-timeout setting: build the idle return from the panel's user-inactivity system tags. Set an Event Manager event on the inactive-minute count with the limits changed to equals and a Screen Change action to the main page, or let an on-delay timer in the PLC write the home screen number to the change-screen command word. Pick the PLC route when the period must be adjustable or bypassed at runtime.

    HMI and touchscreens

  • How-to

    Displaying a Do-More String on a C-More EA9 Panel

    Use the C-More EA9 Dynamic Text object bound to the Do-More short-string tag, and give it a trigger tag that is on whenever the text should update: ST1, the always-on Do-More system bit, works immediately, while a page C-Bit set on at page open and off at page close in the Event Manager ties the display to the open screen.

    HMI and touchscreens

  • How-to

    How to Create and Export GX Works3 Labels for a C-More HMI

    Define the name as a global label in the GX Works3 label editor and give it a device target such as Y5; typing the name on a coil only creates an untargeted entry. Export the global label CSV, then hand-map each row into the C-More tag import template, because the two CSV schemas do not match. Separately, confirm the C-More Mitsubishi driver covers the FX5 before trusting any serial retry.

    HMI and touchscreens