Troubleshooting
Why Graphics Change During Runtime After Project Migration
Short answer
When migrated WinCC 7.3 pictures start swapping tanks and pipes for pump symbols while reports stop and operator commands fail, treat the completed 6.2-to-7.3 migration as the primary suspect: audit each affected object's bold Properties and Actions headings and its Tag Substitution list, rebuild clean objects fresh instead of copying them, and hold a pilot picture past the observed recurrence before trusting the fix.

On this page
- Why do graphic objects change by themselves during runtime?
- What should you record before restarting WinCC?
- How do you audit a migrated object for hidden dynamics?
- Is the fault in one object or in the whole runtime?
- When should you rebuild an object instead of editing it?
- How long should a pilot picture run before you trust the fix?
- Does a successful migration message prove the pictures are correct?
- What should you verify on the runtime workstation itself?
- Which correction do you apply first?
- Questions asked
Tanks and pipes that swap into pump symbols while reports stop and operator commands go dead is a migrated-project fault until proven otherwise: the pictures ran clean in WinCC 6.2, the symptom appeared only after conversion to WinCC 7.3, and other 7.3 projects on the same workstation never show it. Audit every affected object for dynamics inherited during migration, rebuild the clean ones as fresh objects — copying a suspect object copies its converted definition — and prove the fix with a pilot picture that runs past the observed two-to-three-day recurrence. Restarting the runtime is recovery, not repair, and a success message from the migration certifies conversion, not the pictures.
Why do graphic objects change by themselves during runtime? #
A graphic changes by itself only when something in runtime drives it: a property dynamic, an action or a tag connection attached to the object, so a genuinely static icon cannot redraw itself and every self-changing symbol is carrying inherited or corrupted configuration.
Copying is the usual inheritance path. An object drawn with a property dynamic or an action, then copied and reshaped into a tank wall or a pipe corner, keeps that binding even after its geometry and colors change. Migration adds a second path: a converted project can preserve configuration the 7.3 editor no longer presents the way the 6.2 editor did, so a binding that was visible in the old editor sits hidden in the new one. Keep the boundary sharp while you decide which fault you have. One wrong symbol on one picture is an object problem; wrong symbols across many pictures, with stopped reports and dead operator input, means the runtime session itself is failing, and both branches below apply.
What should you record before restarting WinCC? #
Record the incident before restarting, because the restart clears the volatile diagnostics that explain the failure; the recurrence is reliable enough to give you another sample, but every restart erases the evidence from the one before it.
One safety note before anything else: dead operator input on the SCADA screen is a stop condition, the crew must still be able to stop the machine from local pushbuttons that do not depend on the screen, and the restart belongs after the process is in a safe state.
Capture, before the restart:
- a screen capture of the affected picture with its timestamp
- which objects changed, and whether the same objects change every time
- runtime hours since the last start, next to the wall-clock time
- the timestamp of the last successful report
- the timestamp of the first rejected operator command
- whether tag values kept updating while the screen was wrong
- the WinCC diagnostics and the Windows event records covering the window
If the session length repeats across incidents, count the coming pilot in runtime hours; if only the calendar repeats, count it in days.
How do you audit a migrated object for hidden dynamics? #
Open each affected object in the graphics editor and read two places: bold headings on the Properties and Actions tabs mark dynamically configured properties, and the Tag Substitution dialog lists every tag linked to the object — a genuinely static icon should show neither.
Work one object at a time:
- List every dynamic the object is supposed to have before you change anything.
- Record each bold property heading on the Properties tab and on the Actions tab.
- Open Tag Substitution on the object and record every tag it lists.
- Audit the parent group as well as the visible child — a clean child does not clear a dynamic attached at group level.
- Remove any property dynamic or action with no documented process function, and correct every unexpected tag reference.
- Save, rebuild the picture through the normal project workflow, and test the picture in runtime.
In the case as reported, the tanks and pipes had an empty Tag Substitution list, so this audit alone does not close the fault. An object that audits clean moves to the rebuild decision, and the list from step 1 becomes the specification its replacement has to meet.
Is the fault in one object or in the whole runtime? #
Reports stopping and operator commands failing at the same time as the graphic changes point at a runtime-wide disturbance rather than one object, because graphics, actions, reporting and communication all run through the same workstation processes and one stalled component produces all three symptoms together.
| Observation | Diagnostic direction | A healthy session shows |
|---|---|---|
| One object changes; reports and commands still work | Object dynamics or converted picture data | Only the intentional bindings execute |
| Many objects change while reports stop | Runtime component or shared resource | Graphics and reporting stay active together |
| Tag values update but commands fail | The command path, separate from acquisition | Read and write paths both operate |
| The failure clears only after a restart | A volatile process, resource or project-data fault | No recurring error across sessions |
Read the diagnostics before any recovery: the WinCC runtime diagnostics and the Windows event records for the incident window, taking the first event rather than the later cascade. Compare three timestamps — first graphic anomaly, last completed report, first rejected command — and check memory, free storage, processor load and whether every required WinCC process is still alive. A report stoppage has its own harder failure mode, covered in why WinCC Runtime deactivates when the alarm report fails; if your session dies outright instead of freezing, that page is the closer match.
When should you rebuild an object instead of editing it? #
Rebuild instead of editing when an affected object passes the audit with no visible dynamic and no tag substitution: the converted definition is the suspect, and copying that object to a new picture carries the same definition along, so the replacement must be drawn fresh in the WinCC 7.3 editor.
- Back up the project and keep the original affected picture for comparison.
- Create the object directly in the WinCC 7.3 graphics editor — never copy the suspect object or another migrated one.
- Set the geometry and static appearance manually.
- Add only the tags, dynamics and actions the audit documented.
- Replace one suspect object on a pilot picture and rebuild that picture.
- Leave the remaining pictures untouched until the pilot has run its interval.
The controlled pilot separates a defective object definition from a broader runtime fault. If the freshly drawn object holds its type, appearance and dynamics while an adjacent migrated object still changes, keep going object by object. If both change together and the reports stop again, the runtime-wide branch is the live one and the captures you took before the last restart decide it.
How long should a pilot picture run before you trust the fix? #
Run the pilot through at least two full recurrence intervals: with failures landing every two to three days, the worst case gives 2 × 3 days = 6 days, so plan a seven-day pilot with two timed inspections a day — fourteen observations — before you trust it.
Worked example with illustrative timestamps: restart on Monday at 06:00; the first wrong symbol appears on Wednesday at 18:00, which is 60 hours into the session. After the next restart the same picture fails 55 hours in. Both sit inside the 48-to-72-hour window a two-to-three-day recurrence implies, so the clock to beat is session uptime: the seven-day pilot must total 168 continuous runtime hours, and any restart inside the pilot resets the count to zero.
The pass condition is concrete: zero object substitutions, reports completing on schedule and operator commands answering, across the whole interval. Anything less leaves the fault open.
Does a successful migration message prove the pictures are correct? #
No: a migration that reports success proves the conversion process finished without throwing an error, and nothing more — it validates no individual picture's behavior in runtime, which is why the fault that is absent in 6.2 and absent in other 7.3 projects lands on migrated content first.
The WinCC compatibility documentation draws the same split for upgraded projects: an older project is upgraded automatically when it is opened, and matching objects after upgrading is documented as its own task. Conversion and verification are different jobs, and only the second one touches runtime.
Picture conversion on this migration path can also fail loudly — the CoLeException error is the failure name reported in connection with 6.2-to-7.3 picture conversion. Your migration logged no error and no warning, which is precisely why the pilot, not the migration log, has to certify the pictures.
The tag side of the same discipline — checking converted variables against the controller after a migration — is covered in validating HMI variables during a software migration. Whole pictures that vanish in a 6.2-era runtime are a different converted-project fault; why WinCC 6.2 runtime pictures disappear during operation covers that failure mode.
What should you verify on the runtime workstation itself? #
Project content stays the primary branch, but the workstation gets its own checks: memory, free storage, processor load and the required WinCC processes at the moment of the incident, plus the platform pairing of WinCC 7.3, Update 10 and Windows 7 Professional 64-bit against the compatibility list.
Windows 7 left Microsoft support in January 2020, so this workstation runs without security fixes. That fact does not cause this fault — other 7.3 projects run clean on the same PC — but it sets the end of the road for the platform. Update 10 is already installed and the fault continues, so applying the same update again, or restarting repeatedly, is not corrective action; the corrective action is the object audit and rebuild. When that work ends in moving the runtime onto a supported platform, put the SCADA picture on hardware built for the job — an industrial panel PC mounted at the machine rather than a desktop tower behind the console.
Which correction do you apply first? #
Work the branches in order — capture the next incident before restarting, audit and document every affected object, rebuild the clean ones fresh on one pilot picture, hold that pilot for the full seven-day interval, and let the recorded diagnostics decide between a content fix and a runtime fault.
- The audit finds an undocumented dynamic or tag reference: remove or correct it, rebuild the picture, run the pilot.
- The object audits clean: draw it fresh on the pilot picture and hold the pilot; if the new object holds while an adjacent migrated one still changes, continue the rebuild object by object.
- Many objects change together with stopped reports and dead commands: the runtime-wide path decides — compare the first-event timestamps from the pre-restart captures.
- A clean rebuilt object and the session both fail inside the pilot: verify the matched installation and the platform pairing, and plan the move to a supported platform.
Questions asked
Why does restarting the runtime fix it if the project data is the problem?
A restart clears stalled runtime processes and re-reads the project from storage, so it restores service without changing any configuration. That is why it works every time and why the fault always returns: whatever drives the wrong graphics is still in the converted pictures. If a restart ever failed to restore the screen, the fault would no longer be volatile and the diagnosis would change.
Some objects only change color here, is that the same fault?
No. A status change that follows the process, such as grey to green on a running pump, is an intended dynamic doing its job, and it belongs on the documented list you make during the audit. The fault in question is the object type changing, a tank icon redrawing itself as a pump icon, which no intended status dynamic ever does. Judge the two separately.
What does a CoLeException during a 6.2 to 7.3 migration mean?
It is the error reported in connection with picture conversion failures on that migration path, and a migration log containing it points at pictures that did not convert cleanly. A run that reports only success produced no such entry, which is exactly why the runtime pilot, not the migration log, has to certify the pictures in a case like this one.
How do I know the rebuild worked rather than a quiet week?
Compare against the established baseline. Failures landed inside the 48-to-72-hour window after each session start, so a migrated picture had never survived a full session. A rebuilt pilot that holds one continuous seven-day session, 168 runtime hours, with no substitution, intact reports and working commands has outperformed every session on record, and only then do you stage the rebuild into the remaining pictures.

