Troubleshooting
Why MP370 Touch Calibration Never Completes
Short answer
Calibration that opens but never accepts every target is a failed touch-input path, not an interrupted calibration. Confirm the panel by nameplate and MLFB, isolate the fault with a USB mouse, classify total versus partial sensor loss, run one factory-reset OS update, and send a panel that still fails to repair or replacement.
On this page
Calibration that opens but never accepts every target is not a calibration fault you can patch — it is a failed touch-input path. The panel boots, the runtime works from a USB mouse, the calibration routine starts, the pointer follows your finger, and still one or more targets never register. The routine cannot finish without input at every target, so it never saves a map, and after the next power cycle the touch screen is dead again. Work through four checks: confirm the panel identity, isolate the fault with a mouse, classify total versus partial sensor loss, then perform one factory-reset OS update. A panel that still fails after that reset has a touch hardware fault, and the decision is repair or replacement.
What an incomplete calibration means #
Calibration writes the map between raw sensor coordinates and display coordinates. It completes only when the touch controller reports a valid press at every target in the sequence. Two different failures look alike here, and separating them decides what you do next.
An interrupted calibration — power removed before the map was saved — leaves a stale or missing map. The touch hardware is fine, and one fresh calibration run normally recovers it. An incomplete calibration is the opposite: the routine runs, but the touch path does not deliver a valid press at one or more targets, so the sequence stalls no matter how many times you repeat it. The pointer moving across a target is raw coordinate motion; the target only advances when the press is accepted as valid calibration input. Repeating the routine cannot create input from a sensor region that no longer reports.
Confirm the panel identity #
Read the nameplate before you select any recovery image or procedure. The work order on this fault listed the panel as an MP377, but the MLFB on the nameplate, 6AV6 5450DB100AX0, identifies a 15-inch MP370 Touch multipanel. The MLFB decides the OS image and the reset procedure, so do not take a procedure written for the wrong generation. If your nameplate shows a different MLFB, stop and get the image and steps for that exact device. The same discipline applies to any out-of-support panel, as in getting the right firmware file for a legacy HMI panel: match the recovery file by the documented identifiers, never by the job title.
Narrow the fault with a USB mouse #
- Connect a USB mouse and power-cycle the panel. If the pointer moves and clicks work, the boot, the display and the operating system are healthy and the fault is confined to the touch path. If the mouse also fails, stop and diagnose the boot state first — that is a broader fault than calibration.
- Open the touch calibration entry in the panel's Control Panel from the mouse. If the routine and its targets display normally, the display and the calibration application are working, which is what you expect in this symptom pattern.
- Keep the mouse connected for the rest of the diagnosis so you can drive the dialogs without depending on touch.
Mouse control also keeps the machine operable while you decide: using a mouse and VNC when an HMI touchscreen fails covers that interim setup.
Classify total versus partial sensor loss #
Touch each calibration target once, deliberately, and watch two things: whether the press is accepted, and whether the sequence advances.
- No target registers anywhere: classify the symptom as total touch loss — the complete touch-input path is unavailable.
- Some targets register and others never do: classify it as partial sensor loss, and note whether the dead area is always the same region.
Illustrative example: a pass that requests five targets across the screen and accepts 2 of 5 gives 2 divided by 5, or 40 percent coverage, with the same three locations dead on every attempt. A healthy panel accepts 5 of 5 and finishes; zero of five is total loss. That repeatable dead region is the signature of a damaged sensor matrix or its signal connection, commonly from hard pressing or impact on the overlay.
A repeatable local dead zone points at the sensor. Touch behavior that changes with machine state — drives running or stopped — would instead keep environmental causes open. The reported fleet had ten units failing the same way, projected with ProTool Pro, WinCC flexible 2007 and WinCC flexible 2008 SP2 across different installations. Projects that old and that varied make a single software defect an unlikely common cause, so the evidence points at hardware in every unit.
Run one factory-reset OS update #
This is the decisive software test, and one attempt is enough. The reset wipes the project and all panel settings, so prepare before you start.
- Record the nameplate data, the engineering package that created the project (ProTool Pro or the applicable WinCC flexible release), the communications settings, and the coverage classification from the previous check.
- Back up the project archive and everything needed to restore communications with the PLC.
- Prepare the OS update image that matches the MLFB.
- Run the OS update and select the Reset to Factory Settings option.
- Let the update and the restart run to completion; never remove power during the update.
- Before restoring any project, open calibration and touch every target.
One safety note: the machine runs without its operator station while the panel is reset, so confirm it can be brought to a safe stop without the panel before you begin.
If calibration now completes, the fault was a corrupted software state; restore the project and retest touch in the runtime. If calibration still stalls on the same targets, the fault is in the touch sensor or its controller path, and no software step remains.
The repair or replacement decision #
After one factory-reset OS update, a panel whose calibration still cannot complete has a hardware fault in the touch path, and the remaining options are a repair center or replacement. With a single unit and a project you must keep on that exact device, repair is the shorter path. When several units of a legacy multipanel generation fail the same way — ten in the reported fleet — replacement is the realistic route. The fallback is to re-host the project as a PC runtime on one of today's industrial panel PCs, which keeps the operator station at the machine and ends the recurring sensor failures.
Questions asked
Power cycling in the middle of calibration caused this — will calibrating again fix it?
An interrupted calibration leaves a stale coordinate map, and one fresh calibration run normally recovers it. Your symptom is different: the routine runs but targets never register, so the touch path delivers no valid input and calibration has nothing to save. One factory-reset OS update separates a corrupted software state from a hardware fault; a panel that still fails after the reset needs repair.
The pointer moves during calibration, so doesn't that mean touch works?
Pointer position shows raw motion from the sensor, but a calibration target only advances when the press is accepted as valid input at that location. Movement without acceptance means the coordinate data does not satisfy the routine at that target, which is why the sequence never finishes even though the pointer follows your finger.
Can we keep running the machine on the USB mouse alone?
Yes, as an interim measure. Mouse control confirms the rest of the panel is healthy and keeps alarms and setpoint changes reachable, but every operator action slows down and some runtime functions are awkward by pointer alone. Treat it as temporary while the touch fault is repaired or the panel is replaced.
Why would ten panels fail the same way at once?
With projects from ProTool Pro, WinCC flexible 2007 and WinCC flexible 2008 SP2 in the mix, a single software defect cannot explain all ten units. Look instead at shared hardware and practice causes: hard pressing or impact that damages the sensor grid, mechanical stress at the overlay, and the electrical environment shared with the drives. A repeatable dead region on every unit supports the sensor-fault conclusion.