How-to
How to Back Up an HMI With a Scratched Touchscreen Before Replacement
Short answer
A deep scratch usually destroys only the touch layer, while the application keeps running in the panel. Confirm the display still updates, bridge input with a USB mouse or keyboard, upload the project with the model-matched engineering software before disturbing anything, then download it to the identical replacement. If the upload is password-protected, get the credentials or the original project from the machine builder instead of guessing.
On this page
- Is the scratch the only failure on the panel?
- Can a mouse or keyboard hold the machine over until the swap?
- Which EasyBuilder version lists the MT6100i?
- Why does the engineering software crash after a few minutes?
- How do I upload the project before touching anything?
- What if the upload is password-protected?
- Do I get an editable project or only a runtime?
- How do I load the backup onto the identical replacement?
- Questions asked
The fix is an upload, not a rescue: connect a PC to the panel's mini-USB programming port with the USB cable, run the project-transfer function in EasyBuilder8000 V4.66.02.016, and set the direction to upload, HMI to PC, before anything on the machine is disconnected. A scratch deep enough to kill touch response usually destroys only the input layer; the application keeps running in the terminal's memory and can still be uploaded. The case this article follows is a Weintek MT6100i on a mandrel bending machine with a badly scored screen and an identical panel on order as the replacement. The sequence is fixed: confirm the display and communication are alive, bridge operator input with a mouse or keyboard if you can see what you are doing, upload the project through the programming port before anything is disturbed, then download the recovered file to the new unit.
Is the scratch the only failure on the panel? #
In most cases yes: the scratch has destroyed the touch layer, and the application, its controller communication, and the display itself are unaffected, so read the screen without pressing it and confirm that process values still update.
The touch assembly and the terminal electronics are separate parts. The glass supplies operator input; the board stores and executes the application. Dead zones and missing response point at the input hardware and say nothing about the stored project, so the lost-program fear is usually unfounded at this stage.
Keep the machine in a controlled stop while you test: a damaged touch layer can generate phantom input, and any substitute input device you add can issue real commands.
- Application draws normally and values update, touch dead: input-hardware failure. Recover the project, then replace the panel.
- Values freeze or communication alarms appear: that is a controller-link fault, separate from the scratch. Verify or fix it before judging the terminal.
- A USB mouse produces no pointer: the cursor may be hidden by configuration, which is not proof of a dead USB port.
Can a mouse or keyboard hold the machine over until the swap? #
Yes, through the panel's single USB-A host port — the mini-USB socket beside it is the programming connection — as long as the pointer has not been hidden in the application and the machine is held in a safe state.
If the mouse moves nothing, the cursor has most likely been disabled in the project or terminal settings, and those settings are reached through the engineering software, not through the dead glass. That is a configuration condition, not a failed port. Do not click blind: unseen input can change machine state.
A keyboard helps where the application shows focus: arrow keys move between objects and Enter activates the highlighted one. Not every on-screen button or system dialog is reachable that way, so try navigation only on screens where you can see what has focus. If input stays invisible or erratic, remove the device and move straight to the upload.
Which EasyBuilder version lists the MT6100i? #
EasyBuilder8000 V4.66.02.016 is the package for this panel: Weintek splits its terminals across engineering software by series, and the MT6100i belongs to the MT6000 series served by the EasyBuilder8000 line.
A newer package is not automatically the right package. Installing the latest tool and finding the model missing from the list means you have the wrong line, not a dead panel. Take the installer from the manufacturer's official download pages, which use a registered account, and write down which version you installed.
Version check, worked example:
- Requirement: the i-series USB cable transfer needs EB8000 V2.0.0 or newer.
- Installed: EasyBuilder8000 V4.66.02.016.
- Compare: 4.66.02.016 against 2.0.0 — major version 4 is above 2, so the minimum is met and the cable route is supported.
- Model check: the MT6100i is a member of the MT6000 series, so it appears in the model list.
Decision: use this package over the programming cable, and skip experiments with other versions.
Why does the engineering software crash after a few minutes? #
Because a package of this age is unstable on a current Windows installation, and the first practical move is to set the program executable's compatibility mode to Windows 7, then prove the fix by completing one full transfer before trusting it.
A crash five minutes into a session is a host-computer problem, not a panel fault, so leave the terminal and its wiring alone while you chase it. Change the compatibility setting on the executable, restart the software, and require it to stay open through a complete connection and transfer before you call it cured.
If it still closes, move the software to an older PC or a virtual machine with a period-correct Windows version. The recovery needs one clean upload, and an unstable tool is how working panels get overwritten by mistake.
How do I upload the project before touching anything? #
Run the upload from the engineering software over the mini-USB programming cable while the old panel still powers its application: that upload is the entire backup, and it must finish before any wiring is disturbed.
- Connect the PC to the panel's programming port and let the USB driver install. If you do not have the right cable, how to upload an HMI program without the right cable pinout covers the alternatives.
- Open the project-transfer function, set the connection to match the cable, select the MT6100i as the HMI model, and choose a destination folder and project name on the PC.
- Confirm the direction is upload, HMI to PC. A download in this state would overwrite the application you are trying to save.
- Start the transfer and enter the upload password when the panel asks for it.
- Copy the recovered file to a second location and leave one copy untouched; open, convert, or edit only the working copy.
While the panel is still connected, back up recipes and retained data through the software's own export function, and write down the communication settings. The upload discipline is the same across vendors: how to upload a program from an old touchscreen HMI walks the same steps on other brands.
What if the upload is password-protected? #
Get the password, or the original project file, from the machine owner or builder: the upload password is stored with the application on the panel, replacing the glass changes nothing, and there is no legitimate route around it.
Two hard rules follow. Never guess at the password, because repeated failures waste the window in which the panel is still healthy. Never download a test or blank project to probe the terminal, because it overwrites the only working copy of the application.
The legitimate hardware path, when credentials are simply not obtainable, is a board swap: buy an identical model as the donor, power both units down, and move the intact electronics assembly into the donor housing without bending any connector. The application and its protection travel with the board, so nothing is bypassed. Handle the assembly with ESD precautions and match on the exact model designation. Decisions: credentials obtainable, upload; no credentials but a donor exists, board swap; neither, get the source project from the builder or rebuild the screens.
Do I get an editable project or only a runtime? #
Often only a runtime: the upload can return a compiled application that downloads to the identical panel without change, while opening and editing it needs separate protection passwords, and the two results must not be confused.
For a one-for-one swap, the runtime is sufficient: it restores exactly what the old panel was running. Editing is a different permission — project protection in the EasyBuilder line can set a password on compiling and decompiling, and the Window Copy function asks for the source file's EMTP password before copying a protected window. Decide accordingly: archive the runtime for the replacement, and ask the machine builder for the editable source so future changes do not depend on a compiled file.
How do I load the backup onto the identical replacement? #
Download the recovered file to the new panel with the same engineering software and the same cable, keep the original backup untouched, and bring the machine up with motion inhibited until touch response, navigation, and live values all check out.
- With power isolated, compare the replacement's label, connectors, and supply voltage against the old panel, and rewire exactly as documented. The complete model designation is the match, not the screen size.
- Download the recovered file from the engineering software over the programming cable. As an alternative on supported setups, [Tools] » [Build Data for USB Disk or SD Card Download] in EasyBuilder prepares the files for a stick-based download.
- First start with machine motion inhibited. Check the startup sequence, touch response across the whole face of the screen, and navigation through the application.
- Compare displayed values against known machine states before releasing anything: a correctly drawn screen does not prove the data connection works.
- Verify recipes and retained settings, return the machine to normal operation, and shelf the old panel, untouched, as the fallback.
If an identical model cannot be found at all, the job turns into a terminal migration: planning an HMI terminal replacement from an older operator panel covers what to compare before ordering. When the application is rebuilt on a PC-based HMI instead of a look-alike terminal, industrial panel PCs are the hardware class that takes over at the machine.
Questions asked
Can I replace just the touchscreen glass instead of the whole panel?
Sometimes, and it is the least invasive fix because the application stays untouched. If a touch glass for the exact model is available, swapping it restores input with no project transfer at all. On panels where the glass is bonded to the display, separating the two risks cracking the LCD, so weigh that risk against the panel swap before you start.
Do recipes and stored settings travel inside the uploaded project file?
No. Recipe data and retained values live in the panel's memory, separate from the project file, so the upload alone does not carry them. Export them with the engineering software's recipe backup function while the old panel is still connected, or plan to re-enter them on the replacement and verify each one after the download.
What should I record before disconnecting the old panel?
Photograph the rating label with the complete model designation, every connector with its wiring, the communication cable routing, and any system setting screens you can still reach through the keyboard. Terminals that look identical can differ in port layout and supply voltage, and the label is the reference the replacement is ordered against.
Will a factory reset clear the upload password?
Treat that as the wrong question. A reset or memory-clear operation erases the application you are trying to save, so it destroys the backup instead of enabling it. The documented routes are the password or the source project from the machine owner or builder, or moving the intact electronics into an identical housing.