Why OP77B Softkeys Are Missing in Direct .fwx Runtime

HMI and touchscreens Published 5 min read By IMDTouch engineering team

Short answer

The missing softkeys are not a project fault. A direct .fwx start runs WinCC flexible Runtime without the simulated panel face, so only the screen area appears and only the PC keys F1 to F4 and ESC work; start Runtime from the engineering system instead, and the simulator draws the complete OP77B with softkeys, numeric keys, arrow keys and status LEDs, all operable with the mouse. The SimulateSystemKey function covers K1 to K4 in .fwx mode.

On this page
  1. Two starts, two different shells
  2. Start the full simulation from the engineering system
  3. What the PC keyboard can do in .fwx mode
  4. Reach K1 to K4 with SimulateSystemKey
  5. Pick the start by what the test must prove
  6. Leave unofficial launchers alone
  7. Questions asked

Your OP77B project is not damaged, and neither start is defective. Both launches run the same WinCC flexible Runtime 2008 on the same compiled project; they differ only in the shell drawn around the screen. The start from the engineering system — the START RUNTIME SYSTEM button — opens the simulator, which draws the complete panel face with softkeys, numeric keys, arrow keys and status LEDs and accepts mouse clicks on every key. Opening the .fwx file directly opens Runtime without that face: you get the screen area plus the PC keys F1 to F4 and ESC. Below is what each mode can test, how to reach K1 to K4 anyway, and which start to pick.

Two starts, two different shells #

The .fwx file is the compiled runtime project, and executing it is Runtime's job; opening it directly is the launch pattern a runtime PC uses in production. The observed result in this project: the screen window renders, the key layout does not. The simulator launch is different in kind. The WinCC flexible 2008 Runtime manual describes the simulator as launched directly from the running configuration software, and it adds the drawn panel around the screen window, with mouse clicks routed to the drawn keys. The panel face belongs to the simulator; the .fwx start is not the simulator and was never meant to show it.

Start What is drawn What you can operate
From the engineering system: START RUNTIME SYSTEM, or Project > Compiler > start Runtime with simulator The complete simulated OP77B: screen area, softkeys, numeric keys, arrow keys, status LEDs Mouse clicks on every drawn key
Direct .fwx open in WinCC flexible Runtime 2008 The screen area only PC keys F1, F2, F3, F4 and ESC; the hard keys and the LEDs are unavailable
  • The project is identical in both cases: one compiled file, two shells. Navigation that works in one is present in both.
  • The same result was reported with other panels that have keys, so the missing layout belongs to the .fwx start mode, not to the OP77B or to anything in your configuration.

Start the full simulation from the engineering system #

  1. Open the project in the engineering system.
  2. Launch the simulator with the START RUNTIME SYSTEM button or with the documented menu command Project > Compiler > start Runtime with simulator.
  3. When the simulated OP77B appears, operate it with the mouse: click the softkeys, use the drawn numeric and arrow keys, and watch the status LEDs as you navigate.
  4. Expect hash marks in process fields while no controller is connected; why a simulated HMI shows hash marks, not PLC values explains what they mean and how to feed the test real values.

What the PC keyboard can do in .fwx mode #

In the reported project, the PC keys F1, F2, F3, F4 and ESC stayed live in the .fwx start, so navigation and the functions behind those keys remain testable from the keyboard. Work with two limits:

  • Each PC key runs whatever function the project assigned to the matching panel key. Check that assignment in the engineering system before trusting a test result; an unassigned key doing nothing is not a start-mode fault.
  • The hard keys K1 to K4 have no PC-key substitute in this mode, and the status LEDs are not drawn, so neither the hard keys nor LED behavior can be checked from the keyboard. The hard keys have a documented workaround below.

LED behavior is a configuration item you set and verify in the engineering system; on a Comfort Panel that same job looks like configuring TP1200 screen indicators and KP1200 key LEDs.

Reach K1 to K4 with SimulateSystemKey #

Siemens documents the workaround in the support entry How do you simulate the system keyboard via K or F-keys?: the SimulateSystemKey function, available since WinCC flexible 2005, issues a system-key event from inside the project — the same event a press on the physical key generates.

  1. Add a temporary test screen to the project.
  2. Place a button for each hard key you need to exercise.
  3. Assign SimulateSystemKey to the button's press event and choose which key it issues, for example K1.
  4. Compile, open the .fwx in Runtime, and click: Runtime reacts as it would to the physical key.

Delete the test screen before the final compile you transfer to the panel, so the test buttons never reach the machine.

Pick the start by what the test must prove #

  • The softkey layout, the numeric and arrow keys, or the LED response must be visible while you operate: use the simulator start. It is the only one of the two that draws the face.
  • The test is screen flow and the functions behind the F keys and ESC, or the compiled file must run exactly as a runtime PC runs it: the .fwx start is enough, with SimulateSystemKey buttons covering the hard keys. Launching a compiled runtime directly is also the normal production pattern; for the TIA-era version of that job, see create a desktop shortcut for WinCC Runtime Advanced.
  • A function fails in one mode: switch to the other before touching the configuration. A failure present in both modes is a project fault; a failure present only in .fwx mode is a missing key mapping, not broken logic.

Leave unofficial launchers alone #

Tools circulate that claim to start Runtime with the panel face straight from a .fwx file. The only working report covers WinCC flexible 2007, not the 2008 version in question, and none of it is vendor software. Do not run an unverified third-party executable on an engineering PC or on anything connected to the machine network; the engineering-system start gives you the same full face with software that is already installed. If a production runtime PC must show panel keys, take that requirement to the vendor's runtime documentation, not to a downloaded launcher.

Questions asked

Does the missing softkey layout mean my .fwx file is damaged?

No. The file is the same compiled project in both starts; the .fwx launch simply draws no panel face around it. Prove it in a minute: start the simulator from the engineering system with the same project. If the full OP77B face appears and navigation works, the compiled file is good. Recompile only when the simulator start also misbehaves.

What exactly is the .fwx file?

It is the compiled runtime project that the WinCC flexible compiler produces from your engineering data: screens, scripts, tags and functions in the form Runtime executes. You cannot edit it. Make changes in the engineering system, compile again, and the file is rewritten, so always test the newest .fwx after a compile.

Can the simulator replace a test on the real OP77B?

No. The simulator proves screen flow, key-to-function assignment and the logic that drives the status LEDs, all without a controller. The physical keys, the LED hardware and the panel's behavior in the machine are confirmed on the real device after transfer. Treat the simulator as the fast logic check and the panel as the acceptance test.

Keep reading

  • How-to

    Running a WinCC Flexible 2008 Project in PC Runtime

    Yes — WinCC flexible 2008 Advanced targets a PC station. Compile the project to a .fwx file and run it with the separately installed, tag-licensed WinCC flexible Runtime through its loader; the compile never produces an .exe.

    HMI and touchscreens

  • Explainer

    Why no HSP adds the Panel PC 477B to WinCC flexible 2005

    There is no HSP for the Panel PC 477B under WinCC flexible 2005, and none was published. The x77 panel PC family (477B, 677B, 877B, 670) appears only in the WinCC flexible 2007 and 2008 hardware catalogs. Configure in WinCC flexible 2008 and migrate any 2005 or 2007 project there before transferring it to the panel's preinstalled 2008 runtime.

    HMI and touchscreens

  • How-to

    How to Make Arrow Bitmap Buttons in WinCC Touch Panels

    Export each arrow as a 24-bit BMP at the button's exact pixel size, 64×64 px on a 320×240 TP177B, put it on a Button or an invisible button over a Graphic, and wire Press to SetBit and Release to ResetBit on discrete bits V100.0 to V100.3. The dot you see is a bitmap much larger than the button being clipped, not a broken import.

    HMI and touchscreens