Troubleshooting
Why PC Adapter MPI Settings Fail on a PPI S7-200 Port
Short answer
Set the PG/PC interface to PC Adapter (PPI), USB, and the CPU 222 port's factory rate of 9.6 kbit/s and Micro/WIN finds the station; PC Adapter (MPI) at 19.2 kbit/s over COM1 finds nothing because the profile, rate and port are each wrong for an S7-200. Carry the same PPI settings into the WinCC flexible 2008 connection tab and transfer the project over its own separate channel.
On this page
Your working attempt already proved the adapter, the cable and the CPU are fine: PC Adapter (PPI) over USB found the CPU 222 in Micro/WIN. The failed attempt breaks the link three independent ways at once: PC Adapter (MPI) selects a protocol the S7-200 port does not answer, 19.2 kbit/s is double the port's factory PPI rate of 9.6 kbit/s, and COM1 points the driver at a serial port the USB adapter does not occupy. Restore the PPI profile first, confirm Micro/WIN again, then set the WinCC flexible 2008 connection from the CPU's own settings, because PLC programming traffic and HMI project transfer ride separately configured paths.
Why the protocol dropdown decides the link #
The dropdown in the Set PG/PC Interface applet configures the PC side of the link, never the CPU. Choosing PC Adapter (MPI) does not make the CPU 222's port speak MPI; it only tells the driver to send MPI telegrams, and the port answers PPI or nothing. The S7-200 system manual defines PPI as the protocol the integrated port uses for pure S7-200 networks, so a factory CPU 222 is a PPI station until you deliberately change its system block.
With adapter 6ES7 972-0CB20-0XA0 (V1.3) installed, the interface list offers PC Adapter (Auto), documented as available only when STEP 7 is installed, plus PC Adapter (MPI) and PC Adapter (PPI). For this CPU, PC Adapter (PPI) is the profile that matches the hardware. The label on the cable box — an MPI adapter in the catalog sense — has no bearing on which profile is correct; the profile follows the CPU, not the packaging.
The two attempts side by side #
Every difference between your two attempts is a setting the driver reads before it puts a byte on the wire:
| Setting | Working attempt | Failed attempt | What it decides |
|---|---|---|---|
| Interface profile | PC Adapter (PPI) | PC Adapter (MPI) | Protocol the driver speaks; must match the CPU port |
| Rate | 9.6 kbit/s | 19.2 kbit/s | Bit clock; must match the CPU port's configured rate |
| PC-side port | USB | COM1 | Which hardware connection the driver opens |
| Micro/WIN result | CPU 222 visible | No station found | Proof of which combination actually works |
Three settings changed together in the failed attempt, so it cannot isolate a single cause. The next section restores the known-good combination first.
Restore Micro/WIN access step by step #
- Open Set PG/PC Interface and read the access point S7ONLINE (STEP 7); the profile next to it is the one actually in force.
- Set that profile to PC Adapter (PPI).
- In the profile properties, set the PC-side connection to USB and the rate to the CPU port's configured setting — the factory rate on an untouched CPU 222.
- In Micro/WIN, run the station search and confirm the address found belongs to the CPU 222 in front of you; write that address down.
- From here on, change one setting at a time and search again after each change, so any failure isolates one cause.
One safety line: before you go online and write to a CPU driving real outputs, put the machine in a safe state — an online write takes effect immediately.
Match the WinCC flexible 2008 connection separately #
The connection the HMI project uses lives in its Connections view, not in the PG/PC interface you fixed for Micro/WIN. Set the controller driver for the S7-200, choose PPI as the interface, and match the rate and the station address you recorded in step 4 to the CPU port's actual settings. If the project then still refuses the link, the pairing of rate and address it needs is exactly what the article Why a WinCC Flexible PPI Link Fails on Baud Rate and Address works through.
Project transfer to the panel is a further, separate path: set the transfer channel for the panel target and use upload or download; you do not establish an online connection to the panel the way you do to the PLC. Micro/WIN seeing the CPU does not by itself qualify the adapter for the HMI arrangement — the project's own connection tab does that.
Why the MPI attempt could not work, by the numbers #
Take your two attempts as the worked example and check each difference against the port:
- Protocol: PC Adapter (MPI) sends MPI telegrams; a factory CPU 222 port answers PPI, so the station never recognizes the frame and stays silent.
- Rate: 19.2 kbit/s ÷ 9.6 kbit/s = 2.0, so the failed test clocked the line at twice the port's configured rate. MPI's documented rate on S7 networks, 187.5 kbit/s, is 187.5 ÷ 9.6 ≈ 19.5 times the factory PPI value — the two protocols do not even share a starting rate.
- Port: COM1 opens a serial port; adapter 6ES7 972-0CB20-0XA0 connects through USB, so the driver was pointed at hardware that is not there.
Decision: on a factory S7-200 port, run PC Adapter (PPI) over USB at the port's configured rate, and carry that same profile into the HMI project's connection tab. Reserve PC Adapter (MPI) for S7-300 and S7-400 MPI or PROFIBUS ports. A 19.2 kbit/s PPI rate is legitimate only after you set the CPU port to it in the system block and match both ends; on the factory port it fails, and under an MPI profile it fails regardless of rate.
Questions asked
Why does PC Adapter (Auto) not appear in my interface list?
The adapter documentation lists PC Adapter (Auto) as available only when STEP 7 is installed on the PC. On a station running only Micro/WIN and WinCC flexible, the list shows PC Adapter (MPI) and PC Adapter (PPI), and you select the profile yourself. A missing Auto entry is not a fault; pick the profile that matches the CPU port you are addressing.
Does the same USB adapter work with S7-300 and S7-400 CPUs?
Yes. Adapter 6ES7 972-0CB20-0XA0 supports MPI and PROFIBUS as well as PPI. For an S7-300 or S7-400 MPI port, select PC Adapter (MPI), keep the PC side on USB, and set the rate to the value that CPU port is configured for. The rule is the same as on the S7-200: the profile and rate follow the target port, not the cable label.
Can I go online to the panel the same way I go online to the PLC?
No. PLC programming traffic and HMI project transfer ride separately configured paths, and an HMI panel is not something you establish an online session with the way you do a CPU; you upload or download the project. Set the transfer channel for the panel target, and keep the PLC-side communication values in the project's connection tab.
What rate should I expect on an MPI link?
Siemens documentation gives 187.5 kbit/s as the MPI rate on S7 networks, so plan on that value and set it to match the MPI port's own configuration. The profile selection alone is not enough; the rate must match the port as well, exactly as it must on a PPI link.