IMDTouchKnowledge BaseShop main store

Troubleshooting

Using a PC Adapter USB A2 as the WinCC runtime MPI channel

HMI and touchscreens Published 7 min read

Short answer

Yes. The PC Adapter USB A2 (6GK1571-0BA00-0AA0) works as a permanent WinCC runtime channel over MPI, not only for PG functions. The runtime routes its project connection through whatever interface the S7ONLINE access point is assigned to, so install the runtime without SIMATIC NET, assign the adapter in Set PG/PC Interface, and keep the tag load on the segment modest.

On this page
  1. Yes, the A2 is a runtime channel, not only a programming adapter
  2. Symptom patterns after the ProTool swap
  3. Why the S7ONLINE access point decides the outcome
  4. Adapter, CP5711 or MPI-to-Ethernet gateway
  5. Worked example: bus load for a 200-tag screen on a 187.5 kbit/s MPI segment
  6. Keeping the refresh steady
  7. Before it goes on shift
  8. The decision for each case
  9. Questions asked

Yes, the PC Adapter USB A2 (6GK1571-0BA00-0AA0) works as a permanent communication channel for WinCC runtime over MPI, not only for download, online status and diagnostics. The runtime never talks to the adapter directly: it opens the S7ONLINE access point, and the PG/PC interface layer routes that connection through whatever interface you assigned to the name. This page walks through the migration case where a Windows XP PC running ProTool is replaced by a Windows 11 PC running WinCC RT Advanced against an existing S7-300 CPU 315-2DP that has only MPI and DP ports, lists the fault patterns that swap produces, works a bus-load example for the segment and ends with the interface decision for each layout.

Yes, the A2 is a runtime channel, not only a programming adapter #

The doubt is fair, because vendor documentation presents the A2 as a programming adapter. Functionally it makes no difference to the runtime. WinCC opens its project connection through S7ONLINE, the same access point STEP 7 uses, and the Set PG/PC Interface dialog decides which physical interface sits behind that name. The runtime cannot tell whether the frames leave through the A2 adapter, a CP5711 or an Ethernet gateway; it only sees the access point. This is the same mechanism that routes WinCC to PLCSIM on a bench, described in how WinCC connects to PLCSIM through the S7ONLINE access point. Field practice on S7-300 retrofits of this kind reports no restriction, no reconnection problems after a PC or PLC restart, and page refresh matching what the old ProTool station delivered.

Symptom patterns after the ProTool swap #

The faults this migration produces fall into a small set. Each has one deciding check:

  • Every tag shows a communication error when the runtime starts. The S7ONLINE access point is unassigned or points at another interface parameterization. Open Set PG/PC Interface and check which entry is assigned to it.
  • The adapter shows as an unknown device on the new PC. The old PC Adapter USB 6ES7972-0CB20-0XA0 at version V1.3 ships 32-bit drivers only and does not run on 64-bit Windows 11. The A2 is its direct replacement.
  • The adapter is online but no partner is found, or other MPI stations drop off the bus. Duplicate MPI address, or a baud rate and highest-station-address profile that does not match the network. Check from the same dialog with the accessible-nodes function.
  • Pages refresh in steps. Too many tags at short acquisition cycles for the segment. Work through the example below.
  • Standard CPU tags read fine but data from an older function module does not. The module's communication driver is absent from the TIA Portal WinCC version; the FM357 is the classic case. Keep a legacy virtual machine with its own interface for that data instead of forcing it into the new station.

Why the S7ONLINE access point decides the outcome #

An access point is a named logical path that applications open instead of addressing hardware. The interface parameterization is the concrete driver and bus profile behind it, for example the adapter configured for MPI. Set PG/PC Interface in the Windows Control Panel binds the two together. The most common cause of a dead HMI connection after a hardware swap is therefore an unassigned or wrongly assigned access point; a defective interface is much less likely.

Install WinCC RT Advanced and its licenses first, and set the access point afterwards, because the assignment is made against the drivers the installation registers. SIMATIC NET is not required for this path. The mechanism is not new either; it is the same one behind running WinCC flexible runtime on a PC over MPI, only with newer tooling on both ends.

Adapter, CP5711 or MPI-to-Ethernet gateway #

The CP5611 and CP5512 named in older runtime documentation need PCI and CardBus slots that current industrial PCs no longer offer, so on a Windows 11 station the realistic choices are:

Option Connection Choose it when
PC Adapter USB A2 (6GK1571-0BA00-0AA0) USB to MPI/DP The PC sits at the cabinet, no remote access is needed, and no legacy virtual machine must share the interface. Sufficient for a test bench.
CP5711 USB communication processor You want a dedicated communication processor, or pass-through into virtual machines must work. Standardize on it once one machine has it qualified.
MPI/DP-to-Ethernet gateway Ethernet to MPI/DP The PC is away from the cabinet, remote access matters, or the USB port must stay free. Adds a device to the power and maintenance plan.

All three present themselves to the runtime through S7ONLINE, so the choice is a hardware and maintenance decision, not a software one.

Worked example: bus load for a 200-tag screen on a 187.5 kbit/s MPI segment #

Inputs for this example: the MPI segment runs at 187.5 kbit/s (the project's bus profile); the active screen holds 200 tags averaging 2 bytes each (example counts for a test bench); the driver reads 20 bytes of payload per request when the tags sit in contiguous DB areas (example assumption); each request and reply costs about 40 bytes of frame and token overhead around that payload (example assumption); the acquisition cycle is 250 ms.

The rule in words: segment capacity in bytes each second equals the bus bit rate divided by 8. The screen's load equals the number of requests per update, times the bytes each request puts on the wire, divided by the acquisition cycle. Keep that load below half of capacity; above half, pages begin to update in steps.

The arithmetic: capacity is 187,500 bit/s divided by 8, giving 23,437 bytes each second. The 200 tags carry 200 times 2, which is 400 bytes of payload, so at 20 bytes per request the driver needs 20 requests. Each request moves 20 plus 40, or 60 bytes on the wire, so one screen update costs 20 times 60, which is 1,200 bytes. At a 250 ms cycle the screen polls 4 times each second, giving 1,200 times 4, or 4,800 bytes each second. The share is 4,800 divided by 23,437, which is about 0.20, so roughly 21 percent of the segment.

The result: this screen consumes about 4.8 kB each second, a fifth of what the segment carries. The decision: at 21 percent the page refreshes steadily. Run the same screen at a 100 ms cycle and the load passes 40 percent; scatter the tags across M, I and several DBs so packing fails, or add screens of the same size, and the load crosses the half mark and the page updates in steps. The fix is packing and slower cycles for setpoints and recipe data, not a faster interface. Confirm on the running page rather than trusting the estimate: the numbers above are illustrative, and the real request count depends on your addressing.

Keeping the refresh steady #

  • Place HMI-visible data in contiguous DB areas. The driver packs adjacent addresses into fewer requests, while scattered bits multiply the request count.
  • Assign short acquisition cycles only to values operators watch change. Put setpoints, recipe data and static text on slower cycles.
  • Audit tags set to continuous acquisition. Alarms, trends and area pointers consume bus time on every screen, not only where they are displayed.
  • Keep programming-device online sessions off the segment during production runs, because online monitoring competes for the same token time.

Before it goes on shift #

Make these changes with the bench stopped: the link only reads, but a bus profile entered wrongly can stall every station on the MPI segment. Then verify in this order: install the runtime at the version that matches the engineering project and transfer its licenses; connect the adapter and confirm in Device Manager that it enumerates without a warning; assign S7ONLINE to the adapter's MPI parameterization in Set PG/PC Interface; power-cycle the PLC once, unplug and replug the USB cable once, and restart the runtime once, watching with timestamps that each case reconnects by itself.

The decision for each case #

  • Bench PC next to the cabinet, no remote access: the PC Adapter USB A2 with S7ONLINE assigned is sufficient, and no requalification of a second interface type is needed.
  • Site where a CP5711 is already qualified: stay on the CP5711 rather than introducing a second interface type.
  • PC away from the machine, or remote diagnostics required: an MPI/DP-to-Ethernet gateway, which frees the USB port and puts the HMI PC on the plant network.
  • Legacy function module whose communication driver TIA Portal WinCC lacks: keep the old virtual machine with its own interface and leave that data out of the new station.

Questions asked

Do I need SIMATIC NET on the WinCC runtime PC to use the PC Adapter USB A2?

No. Install only the WinCC runtime at the version that matches the TIA Portal engineering project, plus its licenses. The runtime installation brings its own PG/PC interface components. Install the runtime first, then assign the adapter in Set PG/PC Interface, because the assignment is made against the drivers that installation registers.

Why did my old PC Adapter USB stop working on the new Windows 11 PC?

The older adapter with the order number 6ES7972-0CB20-0XA0 at hardware version V1.3 ships 32-bit drivers only, so 64-bit Windows 11 shows no usable driver and Device Manager lists an unknown device. The PC Adapter USB A2 with order number 6GK1571-0BA00-0AA0 is the direct replacement and carries 64-bit support.

Does the runtime connection recover after a PLC power cycle or unplugging the adapter?

The S7ONLINE assignment is stored against the interface and survives reboots, so once it is set correctly the runtime re-establishes the connection on its own when the PLC returns or the USB cable is replugged, without a runtime restart. Retrofits of this kind report exactly that behavior. Still verify once on your bench: power-cycle the PLC, replug the cable and watch the reconnect with timestamps before the shift starts.

What refresh can I expect with a few hundred tags over MPI?

There is no single figure. Refresh is governed by the tags on the active screen, their acquisition cycles and how well the addresses pack into contiguous DB areas. A 200-tag screen at a 250 ms cycle costs roughly 4,800 bytes per second, about a fifth of what a 187.5 kbit/s MPI segment carries. The reliable answer comes from watching the running page, not from a catalog number.

Can a CP5711 be used inside a virtual machine?

Yes, and that is one of its strengths in this migration. When the PLC carries an older function module such as an FM357 whose communication driver the current TIA Portal WinCC no longer provides, a legacy virtual machine with its own installed tooling keeps reading that data, and a CP5711 passes through to such virtual machines reliably.

Keep reading

  • How-to

    Replacing a CP5611 PCI Card in a New WinCC Station

    Yes. Keep the project's channel, connection and tag addresses exactly as they are and change only the PC-side interface: install a USB or PCI Express PROFIBUS adapter the channel supports, then select it in SIMATIC PG/PC Interface and in the WinCC connection. A converter on the Ethernet port is the one option that can force tag rework, so leave it for distance or shared-access cases.

    HMI and touchscreens

  • Troubleshooting

    Fix RSLinx Not Seeing a PanelView 550 on the 1747-UIC

    The PanelView Standard DH-485 port is DCE and the 1747-UIC RS-232 port is DTE, so the link between them is straight-through, never null modem. Set the UIC switch to RS232 (DH485), run the DH-485 UIC Devices driver on the COM number Device Manager shows (COM 8 at address 00 in the working case), and the panel appears in RSWho in about 10 seconds, ready for the PanelBuilder 32 upload.

    HMI and touchscreens

  • Troubleshooting

    Why a WinCC Flexible PPI Link Fails on Baud Rate and Address

    Matching baud rates satisfies only one of the five settings a PPI link needs between a WinCC flexible 2008 PC Runtime and an S7-200. Check the other four in order — cable mode, the CPU station address in the system block (typically address 2 at 9.6 kbps), the master address with the highest station address, and the tag binding — with Micro/WIN closed so Runtime can open the COM port.

    HMI and touchscreens

Using a Mouse and VNC When an HMI Touchscreen Fails